Tensile, compressive and flexural strength reduction of timber in fire/Medienos tempiamojo, gniuzdomojo ir lenkiamojo stiprio mazejimas gaisro salygomis.

Introduction

A number of buildings and works of civil engineering are at high risk of fire. Therefore, an accurate prediction of the behaviour of structures subjected to fire is of primary importance for the evacuation of persons as well as for the safety of rescue teams.

Steel and concrete members (Bednarek 1996; Bednarek, Ogrodnik 2007; Gribniak et al. 2006) under fire have been extensively investigated in the last decades. However, far fewer investigations into timber structures have been conducted (Bednarek et al. 2002; Bednarek, Kaliszuk-Wietecka 2004; Frangi, Fontana 2003; Jong, Clancy 2004; Krakovsky, kral 2004; Sauciuvenas, Griskevicius 2009). Wood is a perfect material for constructional purpose, however, it is flammable. Fire resistance to any wood structures is determined by fire resistance to its components because joints and nodes between components provide no fire resistance. Fire resistance to wood structures depends on various factors, i.e. the charring rate and charring shape, the dimensions and strength of the undamaged components.

Wood combustion characteristics and the related fire hazard are shown in Table 1 (Huntierova 1995).

The thickness of the charring rate and the charred layer are the starting points of determining the dimensions of the undamaged core at any fire time and defining temperature layout inside the core. These characteristics are important problems while learning about fire resistance to timber components using the analytical method.

The charring rate depends on a number of factors such as timber species, timber density, moisture content, chemical composition, timber defects (e.g. fissures). The charring rate also depends on actual specimen geometry (dimensions, shape and surface quality), heat stream density (per component surface area), the method of heat stream transport for the specimen (radiation, convection and conduction), heat operation type depending on the ignition source layout (one, two, three, four-sided thermal exposition).

Particular attention was paid to the influence of timber density on the charring rate. Schaffer (1997) suggests that timber species featuring a higher density range are specific for their lower charring rates.

The charring rate for various timber species is widely discussed in references (Huntierova 1995; Tran, White 1992; Lache 1992; Lipinskas, Maciulaitis 2005). Besides, a discussion on the reduced charring rate versus increased timber moisture content is included.

Lithuanian Standards (LST) do not cover the issues related to structure dimensioning with regard to fire requirements. Therefore, to solve these problems, Eurocode 5 (ENV 1995-1-2: 2000) is used in Lithuania.

The present research was dedicated to investigation into the strength of timber structures under fire conditions. Two species of timber comprising oak and pine were used. The conducted investigation included static tests on tensile strength, compressive strength along the grain, compressive strength perpendicular to the grain and flexural strength. The specimens were tested under the temperatures of 50[degrees]C, 100[degrees]C, 150[degrees]C, 200[degrees]C and 230[degrees]C.

2. Calculation of Charred Layer Thickness and the Core Strength of Timber Structure According to EC5 Principles

Eurocode 5 (EN 1995-1-2:2004) uses the term 'an effective cross-section' which means 'the cross-section obtained by subtracting charred layer thickness from the original cross-section'. The thickness of the design charred layer can be calculated as follows:

[d.sub.char,0] = [[beta].sub.0]t, (1)

where [d.sub.char,0] is charred layer thickness in mm; [[beta].sub.0] is the one-dimensional design charring rate under standard fire exposure; t is the time of fire exposure.

The timber charring rate, [[beta].sub.0], in the standardized heat test is assumed constant and independent from the charring process direction. The value of [[beta].sub.0] = 0.65 mm/min of softwood was adopted for the analytical calculations of fire resistance. In practice, the charring rate varied within 0.5-0.9 mm/min and as much as 1 mm/min for component corners (Holm 1980).

The notional design charring depth with the effect of corner roundings can be calculated as

[d.sub.char,n] = [[beta].sub.n]t, (2)

where [[beta].sub.n] is the notional design charring rate the magnitude of which includes for the effect of corner roundings and fissures, t is the time of standard fire exposure

The thickness of the layer of no mechanical strength should be determined by the following expression:

[d.sub.ef] = [d.sub.char,n] + [k.sub.0][d.sub.0], (3)

where [d.sub.char,n] is calculated using formula (2); [d.sub.0] = 7m is the thickness of the additional layer with no mechanical strength; [k.sub.0] is a coefficient taken from Eurocode 5 (EN 1995-1-2:2004).

In practice, an effective core cross-section largely resembles oval due to a higher charring rate for component corners. The oval core cross-section was taken into account in several proposed calculation models (Debowska 2004).

While calculating bearing capacity for timber structures, reduction in material strength due to high temperature should be taken into account. Two issues should stand apart:

--temperature distribution inside the core;

--reduction in material strength due to the effect of temperature.

Thanks to its porous structure (approx. 15% of solid material is created in timber pyrolysis), the charred layer features a low heat conductivity coefficient of approx 0.5 W/mk, thus limiting the access of both heat and oxygen to the non-charred structural component core that reduces and delays temperature growth inside the core. During the process of wood combustion, the thickness of the superficial charred layer increases at the beginning as quickly as the core dimensions decrease, and then, this process slows down due to the protective properties of the charred layer and due to the moisture evaporating into the material.

Fig. 1 shows temperature distribution across a pine board of 16x36 (mm) after 60 min.

It was determined by the performed tests that the specimens were still keeping sufficient bearing capacity and temperature in the core middle did not exceed 100[degrees]C in most cases. At the same time, temperature in the core reached 200[degrees]C.

Core temperature has a significant influence on the bearing capacity of the component and fire resistance. For standard fire, the average core temperature can be determined by the following formula (ENV 1995-1-2:2000):

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII]

[FIGURE 1 OMITTED]

where [eta] = 0.398[t.sup.0.62.sub.f]; b and h are the initial width and height of the element cross-section, respectively; [t.sub.f] is fire duration time; [beta] is timber charring rate; k is the coefficient accounting the number of sides for fire exposition:

--two-sided k = 0;

--three-sided k = 0.25;

--four-sided k = 0.4.

The later expression has a good agreement with test results given in reference Kordina et al. (1994).

According to Eurocode 5, the core strength can be calculated by:

[F.sub.d,fi] = ([k.sub.mod,fi] x [f.sub.20]/[[gamms].sub.m,fi]), (4)

where [f.sub.fi,d] is reduced strength; [[gamma].sub.m,f] is the partial safety coefficient for fire condition equal to 1.0; [k.sub.fi] is the coefficient accounting safety level under fire conditions for solid wood [k.sub.fi] = 1.25; [f.sub.20] is 20% fractile of strength property under normal temperature; [k.sub.mod,fi] is coefficient accounting strength reduction due to high temperature.

3. Experimental Investigation

The main objective of the test was to investigate the influence of high temperature on the strength of timber structures. Testing results were presented in terms of coefficients making consideration on reducing wood strength under high temperatures recommended for an analytical calculation of fire resistance. The carried out investigation included the following static tests:

--tensile strength;

--compressive strength along the grain;

--compressive strength perpendicular to grain;

--flexural strength.

Static investigation was performed at the Department of Applied Mechanics in the Main school of Fire Service (MSFS) in Warsaw. A special test stand placed in the heating chamber was manufactured for this investigation.

3.1. Thermal Investigation

Before commencing tests, a comparative thermal investigation was performed the results of which are shown in Fig. 2. The tests were made applying the Q500 thermo gravimetric analyzer based on response to changes in substance weight considering temperature. Testing was performed in the atmosphere of environment air. The warming-up rate of 10[degrees]C/min was adopted.

[FIGURE 2 OMITTED]

It can be assumed for pine and oak wood specimens that thermal decomposition begins at approx. 240[degrees]C and follows two stages. The process is probably related to creating a charred layer reducing the thermal decomposition ratio for a certain time length. For pine wood, the weight loss is the quickest at temperature of 430[degrees]C, whereas for oak wood it occurs at 460[degrees]C. Pine wood self-ignition temperature was determined at approx. 400[degrees]C and that of oak wood--at approx. 430[degrees]C. As the given figures show, both curves for both specimens are very similar and located close to each other.

3.2. Preparing for the Test

The specimens were manufactured from timber without fissures. The dimension and shape of the specimens were selected according to regulation. The specimens were taken from pine and oak sapwoods. Fig. 3 shows the manner taking specimens from sapwood.

[FIGURE 3 OMITTED]

Compressive strength testing

The dimension of the specimens was 20x20x30 mm (Fig. 4). These specimens were tested along and perpendicularly to the direction of its grain. Overall, 720 elements were manufactured (360 for testing compressive strength along the direction of the grain and 360 for testing compressive strength perpendicular to the direction of the grain).

[FIGURE 4 OMITTED]

Flexural strength testing

The dimension of the specimens was 20x20x300 mm (Fig. 5). Overall, 120 elements were manufactured.

[FIGURE 5 OMITTED]

Tensile strength testing

The shape of the specimens for tensile strength testing is shown in Fig. 6.

[FIGURE 6 OMITTED]

Tests were performed under the following thermal conditions:

Start temperature was approx. 20[degrees]C (normal temperature) within 50[degrees]C-230[degrees]C. Taking into account that temperature increases inside the undamaged component core from 20[degrees]C to 200[degrees]C and that thermal decomposition begins at approx. 240[degrees]C, testing temperatures were selected for determining strength reduction as follows: 50[degrees]C, 100[degrees]C, 150[degrees]C, 200[degrees]C, 230[degrees]C.

Preliminary tests were used for determining the sample heating program in order to uniformly raise the temperature of the whole sample material.

4. Analysis of Testing Results

The results of strength testing collected as the average results obtained from 10 tests at high temperatures for both wood species and compared to those at 20[degrees]C are shown in Figures from 7 to 10.

Reduction in strength versus temperature was defined by a linear function y = ax + b for both wood species. The functions of linear regression with reliability level curves are shown in Figures from 11 to 18. Table 2 includes data (inclination, offset) on these functions and correlation coefficients equal to approx. 1.

[FIGURE 11 OMITTED]

[FIGURE 12 OMITTED]

[FIGURE 13 OMITTED]

[FIGURE 14 OMITTED]

[FIGURE 15 OMITTED]

[FIGURE 16 OMITTED]

[FIGURE 17 OMITTED]

[FIGURE 18 OMITTED]

The graphics of the coefficient of pine and oak timber strength reduction in comparison with the curve of Eurocode 5 strength reductions are shown in Figs 19-21.

The coefficients of strength reduction, [k.sub.modfi] based on the analysis of testing results were proposed. These coefficients should be applied for calculating the strength of timber elements in fire according to Eurocode 5 (EN 1995-1-2:2004). The proposed values of reduction coefficients are included in table 3. A comparison of the reduction coefficients of compressive strengths with data obtained by other authors (Konig 2000) is given in Fig. 22.

[FIGURE 19 OMITTED]

[FIGURE 20 OMITTED]

[FIGURE 21 OMITTED]

[FIGURE 22 OMITTED]

5. Concluding Remarks

This study was conducted to investigate fire resistance to timber specimens (pine and oak). The following conclusions can be drawn:

A significant influence of even low growth in temperature on all strength types was observed. From the point of view of fire resistance evaluation, temperature rise in the range between 100 and 200[degrees]C is important.

The results of thermal analysis have showed similar fire profiles (flammability) of both wood specimens. Thermal decomposition begins at 240[degrees]C in both cases; the highest mass loss rate occurred at approx. 430[degrees]C after 42 minutes for pine and at approx. 460[degrees]C after 47 minutes for oak. Self-ignition occurred at approx. 400[degrees]C for pine and at 430[degrees]C for oak. TG and DTG curves were similar.

Oak specimens have an undisputable advantage over pine specimens at normal as well as elevated temperatures for compressive strength perpendicular to the grain; nevertheless, tests proved that the rate of strength reduction versus temperature was higher in the oak samples. For compressive strength along the grain, oak specimens have higher values than those of pine within the entire range of temperature; still, a higher rate of strength reduction versus temperature was also found analyzing oak specimens.

The above observations give reasons for stating that oak specimens (of a higher density than that of pine specimens) react with a more rapid strength reduction against the rising temperature rather than those of pine.

For calculating wood strength in fire temperatures for both species of wood, it is proposed to apply regression functions as shown in Figures from 11 to 18 or refer to the data included in table 2. The conducted testing discloses that strength reduction against rising temperature has a linear character.

To evaluate the structures of fire resistance to timber, strength reduction coefficients, [k.sub.modfi], as listed in table 3, are proposed for application.

doi: 10.3846/skt.2009.18

Received 10 09 2009; accepted 05 10 2009

References

Bednarek, Z. 1996. Determination of the temperature of uncovered steel constructions using numerical methods, Statyba [Civil Engineering] 4(8): 6-10.

Bednarek, Z.; Kaliszuk-Wietecka, A.; Wisniewski, T. 2002. Research on the influence of fire protection impregnation carried out by the vacuum -and-pressure method on wood dynamic strength, Building Review [Przeglad Budowlany] 10: 12-14 (in Polish).

Bednarek, Z.; Kaliszuk-Wietecka, A. 2004. Scientific research on the influence of fireproof wood preservation carried out by the vacuum-pressure method on strength of wood in normal and elevated temperatures, in Proceedings of the 8th International Conference "Modern Building Materials, Structures and Techniques", Vilnius, 19-21 May 2004. Vilnius, 963-967.

Bednarek, Z.; Ogrodnik, P. 2007. Testing steel-concrete bond in fire conditions, in Proceedings of the 9th International Conference "Modern Building Materials, Structures and Techniques", Vilnius, 16-18 May 2007. Vilnius, 1152-1158.

Debowska, A. 2004. Problems of wood steel constructions in fire. Polytechnic Opole (in Polish).

ENV 1995-1-2:2000 Eurocode 5: Design of timber structures. Part 1-2: General rules structural fire design. Brussels.

EN 1995-1-2:2004 Eurocode 5: Design of timber structures. Part 1-2: General-structural fire design. Brussels.

Frangi, A.; Fontana, M. 2003. Charring rates and temperature profiles of wood sections, Journal of Fire and Materials 27(2): 91-102. doi:10.1002/fam.819

Gribniak, V.; Bacinskas, D.; kaklauskas, G. 2006. Numerical simulation strategy of reinforced concrete tunnel bearing members in fire, The Baltic Journal of Road and Bridge Engineering 1(1): 5-9.

Jong, F.; Clancy, P. 2004. Compression properties of wood as functions of moisture, stress and temperature, Journal of Fire and Materials 28(2-4): 209-225. doi:10.1002/fam.859

Holm, C. 1980. A survey of the goals and results of fire endurance investigations especially from the viewpoint of glued laminated structures, in Symposium in Tbilisi "Fire Resistance of Wood Structures", Tbilisi, 17-24.

Huntierova, Z. 1995. Analysis of the burning behavior of wood and timber considering the use of fire protection layers. Munich: Graefelfing publishing house (in German).

Kordina, K.; Meyer-Ottens, C.; Scheer, C. 1994. Handbook of wood fire safety. Munich: Ernst and son (in German).

Krakovsky, A.; Kral, S. 2004. The influence of thermo mechanical loading on behavior of spruce wood. Technical university in Zvolen (in Polish).

Lache, M. 1992. A survey of the burning rate of solid wood and the fire resistance of wooden ceiling boards exposed to bending. Munich (in German).

Lipinskas, D.; Maciulaitis, R. 2005. Further opportunities for development of the method for fire origin prognosis, Journal of Civil Engineering and Management 11(4): 299-307.

Sauciuvenas, G.; Griskevicius, M. 2009. The behavior or axial compression timber elements at fire, Statybines konstrukcijos ir technologijos [Engineering Structures and Technologies] 1(1): 50-57 (in Lithuanian). doi: 10.3846/skt.2009.06

Schaffer, E. 1997. State of structural timber fire endurance, Wood and Fiber 9(2): 145-170.

Tran, H. C.; White, R. H. 1992. Burning rate of solid wood measured in a heat release rate colorimeter, Fire and Materials 16: 197-206. doi:10.1002/fam.810160406

Zoja Bednarek (1), Mecislavas Griskevicius (2), Gintas Sauciuvenas (3)

(1) The Main School of Fire Service (MSFS) in Warsaw, str. J. Slowackiego 52/54, 01-629 Warsaw, Poland, e-mail: sgsp@sgsp.edu.pl

(2) Department of Labour Safety and Fire Protection, Vilnius Gediminas Technical University, Sauletekio al. 11, LT-10223 Vilnius, Lithuania, e-mail: m.griskevicius@vpgt.lt

(3) Department of Steel and Timber Structures, Vilnius Gediminas Technical University, Sauletekio al. 11, LT-10223 Vilnius, Lithuania, e-mail: gintas.sauciuvenas@st.vgtu.lt

Zoja BEDNAREK. Prof. Dr Sc., the Rector of the Main school of Fire Service in Warsaw, Poland. A member of PN-TTE Polish Maintenance Society. Research interests: the strength of materials and the behaviour of building structures at elevated temperatures. A promoter of Doctoral thesis concerning the problems mentioned above.

Mecislovas GRISKEVICIUS. A lecturer at the Department of Labour Safety and Fire Protection, Vilnius Gediminas Technical university. Research interests: fire prevention services, organization and implementation of lifesaving work.

Gintas SAUCIUVENAS. Assoc. Prof. Dr at the Department of Steel and Timber structures of Vilnius Gediminas Technical University. Research interests: evaluation of the existing steel and timber structures, evaluation of fire resistance to steel and timber structures.
Table 1. Wood combustion characteristics and related fire hazard

Material warming 100[degrees]C Wood drying process. Loss of
up free water and bounded water.

 150[degrees]C Changes in chemicellulose and
 lignin. Slow reaction. Any
 further temperature growth or
 keeping a constant temperature
 for a sufficiently long time
 can cause the material to
 ignite.

Critical 225[degrees]C The commencement of
temperature range decomposition gas generation,
for material mainly C[O.sub.2], acetic
decomposition acid, steam.

 250[degrees]C Cellulose decomposition.

 270[degrees]C Very quick generation of
 decomposition products. Any
 occurring flame can
 incinerate the gas mixture.

 290[degrees]C Wood weight loss is close to
 39%. The material reaches
 temperature necessary for its
 surface to ignite in the
 presence of a flame and for
 self-acting combustion.

Ignition 330[degrees]C Flames spreading over the
temperature range surface; charred layer
 build-up commences.

 400[degrees]C Exothermic course of the
 decomposition process. Fire
 transfer hazard. The maximum
 rate of flammable gas
 generation. The creation of
 glowing layers built mainly
 from high-energy lignin.

Combustion with 450[degrees]C Wood burning out inside the
open fire material.

 500[degrees]C Charcoal residue burning.

Glowing and 700[degrees]C The complete combustion of
complete decomposition products
combustion of (gases) on the material
pyrolisis residue surface.

 800[degrees]C The generation of flammable
 products is completed.

Cooling 1100[degrees]C The results of wood glow in
 the complete material
 destruction. Non-flammable
 mineral residue (ash) remains.

Table 2. Comparison of regression function and correlation
coefficients considering the selected type of testing

No. Testing type Coefficients of regression
 function: y = ax + b

 Regression function
 declination -- coefficient a

 Specimen group

 Pine Oak

1 Tension -0.262 -0.292

2 Bending -0.376 -0.445

3 Compression -0.124 -0.233
 along
 the grain

4 Compression -0.017 -0.06
 perpendicular
 to the grain

No. Coefficients of regression
 function: y = ax + b

 Regression function
 declination -- coefficient b

 Specimen group

 Pine Oak

1 126.312 112.932

2 120.696 124.096

3 55.964 79.808

4 6.342 20.997

No. Correlation coefficient
 of thermal timber
 strength

 Specimen group

 Pine Oak

1 0.9372 0.9833

2 0.9477 0.9880

3 0.8598 0.9712

4 0.9126 0.9793

Table 3. Strength reduction coefficient [k.sub.modfi]

Temperature Bending Tension
[[degrees]C]
 Pine Oak Pine Oak

 20 1.0 1.0 1.0 1.0
 50 0.9 0.9 0.9 0.9
 100 0.7 0.7 0.8 0.8
 150 0.6 0.5 0.7 0.6
 200 0.4 0.3 0.6 0.5
 230 0.3 0.2 0.5 0.4

Temperature Compression along Compression
[[degrees]C] the grain perpendicular
 to grain

 Pine Oak Pine Oak

 20 1.0 1.0 1.0 1.0
 50 0.9 0.9 0.9 0.9
 100 0.8 0.8 0.8 0.8
 150 0.7 0.6 0.6 0.6
 200 0.6 0.4 0.5 0.5
 230 0.5 0.3 0.4 0.4

Fig. 7. Relationship of timber tensile strength along the
grain and evaluated temperature

 Oak Pine

20 104,36 132,27
50 97,63 100,94
100 85,27 96,07
150 73,57 92,49
200 58,94 72,01
230 38,57 67,56

Note: Table made from bar graph.

Fig. 8. Relationship of timber flexural strength
and evaluated temperature

 Oak Pine

20 120,9 128,47
50 101,37 92,59
100 70,56 75,26
150 59,7 54,63
200 31,09 53,86
230 27,3 37,29

Note: Table made from bar graph.

Fig. 9. Relationship of timber compressive
strength perpendicular to the grain and
evaluated temperaturee

 Pine Oak

20 6,95 20,39
50 4,98 17,7
100 3,76 13,62
150 3,72 13,13
200 3,2 9,98
230 2,76 6,37

Note: Table made from bar graph.

Fig. 10. Relationship of timber compressive
strength along grain reduction and
evaluated temperature

 Pine Oak

20 62,15 80,63
50 43,77 64,4
100 36,91 51,29
150 36,78 45,24
200 36,74 39,04
230 26,35 23,54

Note: Table made from bar graph.
COPYRIGHT 2009 Vilnius Gediminas Technical University
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2009 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Bednarek, Zoja; Griskevicius, Mecislavas; Sauciuvenas, Gintas
Publication:Engineering Structures and Technologies
Article Type:Report
Geographic Code:4EXLT
Date:Sep 1, 2009
Words:3682
Previous Article:Modelling deformation behaviour of RC beams attributing tension-stiffening to tensile reinforcement/Gelzbetoniniu siju tempiamosios zonos elgsenos...
Next Article:Professor Herbert A. Mang--inaugurated as Doctor Honoris Causa of VGTU/Profesorius Herbert A. Mang--inauguruotas VGTU Garbes Daktaras.
Topics:

Terms of use | Copyright © 2017 Farlex, Inc. | Feedback | For webmasters