Structural factors of solar system cluster ground coupled storage rationalization.

UDC 697.329+662.997+697.7

Introduction. The seasonal solar heat storage system are an essential element of solar systems designed for heating. Often this objective considering, namely ground coupled storage [1, 2] are selected. Among them the stand vertical multiprobe (cluster) design is characterized with best performances. The heat exchanger is presented as vertical probe with concentric tubes arrangement in the wells. Sectional structure of the batteries varies by spatial distribution, probes number and heat exchangers size. These structural factors are determined by the conditions of heat storage operation in the soil, as well--as conditions of its dual operation with solar system. Significant transiency of solar systems operation does complicate practical research, due to which fact we still are in an acute need for reliable recommendations on the choice of cluster structures rational parameters, particularly, the well configuration: interval between probes and heat exchangers' length.

A typical recommendation as to the ground coupled storage structure refers to arranging a rectangular cluster at regular intervals between the probes [2 ... 5]. Such clusters differ in the number of probes, their length and positioning distance. Structural design parameters are usually set arbitrarily. Research [4] exposes the heat exchangers number selected with respect to the area under the building foundation, and an arbitrarily chosen step of 3 m. At study [5] the interval between probes was chosen to be 5 m, and the source [6] reveals the 6 m step length. Assessment of the heat exchanger length as determined with the solar collectors' area, and therefore, their thermal capacity estimation, were effected only for single-probe ground storage [7]. And as to the cluster structure, none similar data found at the references. Thus, studies with unfounded-chosen storage size, are rather empirical and can never be used for practical purposes. Another scarcity of well-known studies limiting their applicability consists in the simplified processes modeling [3], in particular, mono-parametric studies of heat transfer in soil and the real solar system work environment substitution replacing the soil coupled accumulator with conventionally definable laws of heat accumulation. However, for practical purposes, it is important to establish the reliable operating parameters that implies the need to resolve tasks of the ground coupled storage structural parameters rationalization based on mathematical models of higher informational content.

The aim of this study is to optimize the cluster ground coupled storage--the probes quantity in cluster, their lengths and interval--using high precision mathematical model.

Materials and Methods. The storage cluster consists of 9 coaxial ground heat exchangers of length h vertically positioned with interval between probes S. The problem was solved as conjugated with this one of the radiant energy absorption by solar collectors (SC) and considering the heat transfer process in the heat exchanger and the ground. The heat transfer in the ground coupled heat exchanger is described with a system of energy balance [1] differential equations: for the inner (supply) tube heat carrier; for the inner tube wall; for outer (return) tube heat carrier; for the outer wall. The soil heat transfer is described with the equation of unsteady heat conductivity in Cartesian coordinates, three-dimensional problem statement.

The equations system was solved by finite difference method. Material used for heat exchanger tubes: plastic, wall thermal conductivity [[lambda].sub.w] = 0,28 W/(m x K). Heat exchanger outer tubes' diameter, in accordance with [1], was assumed to be 180 mm. Heat carrier is water. The ground heat exchanger was coupled with SC through introduction to calculated mathematical model of an equations' system describing the conditions of solar energy getting and conversion at solar collectors [1]. The solar system operation conditions were specified with Odessa region coordinates for the period that began on April 15th (the heating season closure) and ended 6 months (180 days) elapsed. Equipment selected for study: modern flat solar collectors with the characteristics as above

U/([tau][alpha]) = 4,4 W/([m.sup.2]K),

where U--heat losses coefficient;

([tau][alpha])--solar collector optic characteristics.

At the issue of mathematical model solution assessed were the heat exchanger's and ground array's temperature fields, the ground array heat content, temperature and velocity of the heat carrier circulating in the solar system as unfolds along seasonal operation. The iterative calculation of heat pumping process served to determine the total area of SC, whose thermal performance meet the criteria of maximum specified heat carrier velocity (2 m/s) in ground heat exchangers at a fixed heat carrier temperature at the heat exchanger inlet.

Analysis of data obtained shows that the cluster probes' spacing has a significant impact on the amount of heat accumulated in the ground [Q.sub.sum] (Fig. 1). The increased step involves an increase in ground array heat content. The data represented at Fig. 1 were obtained for probes of 10 m length in the ground, morphologically corresponding to the clay. Similar results were obtained also for other soils.

At the end of the six-month heat accumulation cycle period under the said conditions, increasing the step from 2 to 6 meters involved the 2,7-folds growth of the peak heat [Q.sub.peak] greatest amount. This phenomenon is explained by the heat transfer intensification when increasing the temperature difference between the probe heat carrier and the ground, as the step growth reduces the soil array temperature at inter-probe space. However, the peak heat quantity dependence of the interval between probes is nonlinear. Step increased, the [Q.sub.peak] growth decreases asymptotically approaching a certain level (Fig. 2). These conditions threshold can be considered as the value S = (5 ... 6) m, beyond which the [Q.sub.peak] function is low-sensitive to the step value. However, the step increasing leads to changes in the soil temperature, taking [t.sub.m] as an indicator of temperature on the mean of interval between probes for a depth equal to half the length of the probe, we obtain (soil type: clay), the result for 180th day of the cluster charging (step 2 m: [t.sub.m] = 47[degrees]C, 4 m: [t.sub.m] = 37,3[degrees]C, 6 m: [t.sub.m] = 25,9[degrees]C). Given the two mentioned factors, as a compromise can be selected the step of 4 m, as corresponding to a desired storage thermal accumulation level and a sufficiently high temperature.

[FIGURE 1 OMITTED]

[FIGURE 2 OMITTED]

Another factor influencing the efficiency of heat accumulation is the number of active probes in the cluster (Fig.3). The design scheme was formed by sequentially excluding the heat exchangers making part to 9-probes cluster. Basic diagram represents case of all heat exchangers operative, this one with five active coils was obtained upon disconnecting the lateral four probes lying on the cross-sectional diagonal; the diagram of one heat exchanger was obtained upon disconnecting the lateral eight coils. Interval between probes is 4 m. The data obtained shows that a single probe is significantly inferior to the cluster storage (Fig. 3). However, a further increase in the number of cluster heat exchangers has little effect on the storage thermal characteristics improvement. This is due to the restructuring of the temperature field thus reducing the temperature gradient that affects the heat transfer between probes and the ground. Thus, despite an increase in the cluster heat transfer area, separate heat exchangers at 9-elements cluster are less productive that at 5-elements one.

More informative results can be obtained using the criterion of the solar collectors' total area ratio to peak heat quantity accumulated in the soil [A.sub.sum]/[Q.sub.peak]. This figure represents a specific SC area required for charging the ground coupled storage up to a predetermined limit. Analysis of this parameter dependence on the number of cluster probes shows that an increase in the probes number is concurrent to the [A.sub.sum]/[Q.sub.peak] increase (Fig. 4). The dependency growth rate is related to the interval between probes. The highest growth rate is observed for interval of 2 m, while the interval of 4 to 6 m does insignificantly influence this rate. The cluster of five probes with interval of 4 m, previously defined as a rational one, has the least necessary specific area of solar collectors.

Fig. 5 shows the dependence of probe length h from the related solar collectors area A required for one heat exchanger operation at sectional structure. The data suggests that an increased SC area requires increasing the probe length. The dependence is close to linear, and its parameter is the soil thermal conductivity [a.sub.s]. With the growth of [a.sub.s], the degree of SC area influence onto probe length decreases.

[FIGURE 3 OMITTED]

[FIGURE 4 OMITTED]

[FIGURE 5 OMITTED]

Results. A summary of the researched data gives grounds to elaborate recommendations on the organization of the solar system cluster ground coupled storage structure. The interval between probes preferably should be chosen equal to 4 m as corresponding to good level of storage thermal accumulation at sufficiently high temperature. A more informed choices as to the arrangement step should be based on thermo-physical properties of the soil, as well as modes of solar system when charging and discharging the ground storage, which question requires an additional research. Use of 9-probes cluster system is assessed as inappropriate by factor of ground array thermal accumulation; the optimal and rational structure is a 5-probes one.

The obtained data for determining the probe length at solar systems with different values of the absorbing surfaces' area and for different soils can be approximated with an error of no more than 3 % by the following expression:

h = 5, 1 x A x exp(-1,8 x [10.sup.6] x [a.sub.s]) +1,133 - [(0,365 - 1,92 - [10.sup.6] x [a.sub.s]).sup.2].

The generalizing expression is obtained for solar systems with flat SC within the definition area: U/([tau][alpha])=4,4 W/([m.sup.2]K); the SC area calculated per one probe A = (2,9 ... 28) [m.sup.2]; for soils with thermal conductivity coefficients [a.sub.s] = (2,78 ... 9,61) x [10.sup.-7] [m.sup.2]/s.

Conclusions. The recommendations for organization of heat exchangers of the collector work are offered. The five-probe structure is the most effective one for cluster arrangement of seasonal heat storage. The recommended interval between probes is 4 m. A generalized dependence suggested, allows determining the solar probe length at the cluster structure for the condition of rational operation modes, depending on the solar collectors' area and thermal properties of the soil.

DOI 10.15276/opu.3.47.2015.08

References

[1.] Wysochin, V.V., & Gromovoy, A.J (2013). The role of the ground heat exchanger to leveling irregularity of solar plant system operation. Odes'kyi Politechnichnyi Universytet. Pratsi, 2, 148-152.

[2.] Nakorchevsky, A.I., & Basok, B.I. (2005). Optimal design of ground heat exchangers. Industrial Heat Engineering, 27(6), 27-31.

[3.] Wysochin, V.V., & Kozhukhar, Ye.I. (2015). The conditions of twenty-four-hour charging of the group ground accumulator of solar plant system. Odes'kyi Politechnichnyi Universytet. Pratsi, 2, 92-96. DOI: 10.15276/opu.2.46.2015.17

[4.] Trofimenko, A., Dmitrenko, A., Lapko, D., & Nazarenko, M. (2010). Experimental researches of operating conditions of the soil accumulator in system of the heat supply of the house. Industrial Heat Engineering, 32(5), 67-71.

[5.] Nakorchevsky, A.I., Basok, A.I., & Belyaeva, T.G. (2003). Problems of soil heat accumulation and methods of their solution. Industrial Heat Engineering, 25(3), 42-50.

[6.] Nakorchevsky, A. (2007). Rational decision in a heat generating system "soil massif--heat pump". Industrial Heat Engineering, 29(4), 77-82.

[7.] Wysochin, V.V., & Motsny, V.I. (2014). Effect of the ground heat exchanger dimensions on the heliosystem operation with coupled modes. Odes'kyi Politechnichnyi Universytet. Pratsi, 1, 137-141. DOI:10.15276/opu.1.43.2014.23

[TEXT NOT REPRODUCIBLE IN ASCII]

Received May 11, 2015

Accepted July 7, 2015

V.V. Wysochin, PhD, Assoc.Prof., A.S. Golovatyuk, PhD, Assoc.Prof.

Odessa National Polytechnic University, 1 Shevchenko Ave., 65044 Odessa, Ukraine; e-mail: ostapenko.ieksu@mail.ru
COPYRIGHT 2015 Odessa National Polytechnic University
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2015 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Wysochin, V.V.; Golovatyuk, A.S.
Publication:Odes'kyi Politechnichnyi Universytet. Pratsi
Article Type:Report
Date:Nov 1, 2015
Words:2002
Previous Article:The new designs of diamond drill bits for composite polymers tooling.
Next Article:Ergodicity of project management system.
Topics:

Terms of use | Privacy policy | Copyright © 2019 Farlex, Inc. | Feedback | For webmasters