Selection of energizing quantities for sensitive ground fault protection of MV electric power networks/vidutines itampos elektros tinklu izeminimo gedimo apsaugos dinaminiu parametru parinkimas.

Introduction

Effective detection and clearing of ground faults in MV networks particularly under high fault resistance is difficult to achieve due to too low values of both voltage and current being used as threshold for fault indication.

It must be noted that MV networks employed in mining industry operate with different neutral point arrangement i.e. isolated, compensated and ineffectively grounded via selected resistor as well.

Many scientific works were performed if about as detection, modeling and measurement as well as methodology of restoring power supply such failures [1]. Therefore after many years of experience authors have found that one of the possibility to overcome this problem can be application of argument difference detection as a criteria. Thus the argument difference between 1st and 2nd harmonic of both zero sequence voltage ([U.sub.0]) and current ([I.sub.0L]) for healthy and faulty lines were found to be convenient. However, it requires application of a suitable both voltage and current measuring units.

Paper presents and discusses simulation results of possible variations of selected quantities for different network and fault conditions. The influence of leakage (ground fault) resistance and line loading were taken under consideration. On the basis of the investigated results conclusions on reliable operation of the new developed ground fault protection are formulated.

Principle of operation of the sensitive ground fault protection

A simplified scheme of MV network with sensitive ground fault protection is presented in Fig. 1. It's operation is based on detection of 1st and 2nd harmonic arguments in both zero sequence voltage ([U.sub.0]) and current ([I.sub.0L]). Since 2nd harmonics does not exist under normal state of the network operation therefore the injection unit (UW) has been developed and applied what is described in more details in [2, 3].

Filtering of zero sequence value of both voltage (arising between neutral point and ground during ground faults) and currents of protected lines is carried out through Rogowski coils based measuring units [4].

Considering high sensitivity of developed protection a Hall sensor based unit was taken into account and tested.

The UW unit injects current harmonics into the protected network at a moment of the ground fault occurrence. The currents and voltages selected harmonics being measured are than extracted using [FU.sub.H], [FI.sub.H] units. At the next step the phase comparator unit (PC) is delivered with the arguments of filtered harmonics so that it could provide initiation signal based on selected harmonics arguments difference between the protected lines.

[FIGURE 1 OMITTED]

The harmonics argument differences (obtained from PC) can be further used for signalizing of the decrease in the leakage resistance as well as for tripping faulty line.

Analysis of selected indication quantities

Respective analysis has been performed for considering content of harmonics and possibility of application of their relations when used as efficient energizing quantities for the sensitive ground fault protection for MV networks especially under the increased value of fault resistance (leakage resistance). In Fig. 2 and 3 are presented (as an example) selected secondary current wave forms [I".sub.BL1] provided by current transformer [PP.sub.L1] installed at the beginning of the protected line in phase B (faulty one), and currents from the neutral conductor ([I.sub.0z], [I".sub.0z]) respectively. The simulation results obtained for unloaded as well as loaded network ([I.sub.load]=200A ) are respectively presented in Fig. 2 and Fig. 3.

[FIGURE 2 OMITTED]

[FIGURE 3 OMITTED]

As one can observe the [I".sub.BL1] wave gets smoother for the loaded network and harmonics visible in the phase current (without the load) are significantly smaller.

It was found that the load inflicts the content of harmonics of the fault current what has been presented in Fig. 4.

As a result detection of selected even harmonics is made difficult what recommends the use of signals only provided by the zero sequence filters.

[FIGURE 4 OMITTED]

The zero sequence voltage is also dependent on the ground fault resistance value as indicated in Fig 5.

[FIGURE 5 OMITTED]

[FIGURE 6 OMITTED]

It must be noted that use of the Rogowski coil arrangement significantly improves sensitivity of the fault detection due to increased amplification rate with the harmonic number, what can be compared in Fig. 6 and Fig. 7.

[FIGURE 7 OMITTED]

There was also found that content of higher harmonics in selected signals for protection depends on the leakage resistance value [R.sub.p]. With the increase of the [R.sub.p] value their contribution becomes more significant (Fig. 8) what is considered as a good for the protection reliability.

[FIGURE 8 OMITTED]

On the basis of comparison of higher harmonics content (Fig. 9) in the zero sequent current of both faulty and healthy lines it is clear that using above mentioned comparison as the criteria one can also discriminate the faulty feeder successfully.

[FIGURE 9 OMITTED]

It can be particularly convenient for detection and clearance of the ground faults in the MV mining networks where the short circuit currents values are significantly reduced due to safety reasons (fire and explosion hazard as well as the electric shock for servicing personal).

Efficiency of operation of the developed sensitive protection under ground faults can be deduced from Fig. 10 and 11 when compare the argument differences for various [R.sub.p] value. It is seen that employment of mutual differences values results in detection of the grounding up to about 10k[ohm] successfully.

[FIGURE 10 OMITTED]

[FIGURE 11 OMITTED]

Conclusions

Effective discrimination and clearing of the high resistive ground faults in MV networks is difficult due to decreased both voltage and current values provided by measuring transformers. It is particularly onerous in MV mining networks operated with isolated neutral point.

On the basis of theoretical results it was found that in such case the comparison of arguments value for selected electrical quantities (zero sequence voltage and current) when injected even harmonics under the ground faults can be used as a choice. It is recommended to apply the diode with resistor in series (as current limiter) between the transformer neutral point and grounding electrode.

There are two possibilities of providing the protection operation as follows:

--Tripping signal is due to selected harmonics argument difference between zero sequence current provided by the filters applied on protected lines and zero sequence voltage.

--Tripping signal is due to selected harmonics argument difference between zero sequence current provided by the filters applied on protected lines and zero sequence current in neutral conductor.

Both the current and the voltage zero sequence filters should be based on Rogowski coil arrangements to increase sensitivity of the protection. It must be underlined that as the difference value as well as its variation under the ground fault conditions can be used as criteria.

References

[1.] Sylwester F. Application of Classifier System and Co Evolutionary Algorithm in Optimization of Medium-Voltage Distribution Networks Post-Fault Configuration // Electronics and Electrical Engineering.--Kaunas: Technologija, 2011.--No. 9(115).--P. 9-15.

[2.] Miedzinski B., Dzierzanowski W., Belka H., Szymanski A. Uklad detekcji wysokorezystancyjnych zwarc ziemnych w sieciach srednich napiec // Mechanizacja i Automatyzacja Gornictwa, 2008.--No. 7-8.--P. 45-51.

[3.] Szkolka S., Wisniewski G., Fjalkowski Z., Lisowiec A. Filtr skladowej zerowej pradu z cewka Rogowskiego w srodowisku pradow odksztalconych // Mechanizacja i Automatyzacja Gornictwa, 2008.--No. 7-8.--P. 20-25.

[4.] Miedzihski B., Dzierzanowski W., Belka H., Szydlowski K Zastosowanie harmonicznych parzystych w detekcji zwarc doziemnych sieci SN // VI Konferencja naukowo-techniczna Sieci elektroenergetyczne w przemysle i energetyce Szklarska Poreba, 2008.--P. 217-222.

Received 2012 04 04

Accepted after revision 2012 05 22

B. Miedzinski, D. Pyda, M. Habrych

Wroclaw University of Technology, Institute of Electric Power Engineering,

Wybrzeze Wyspianskiego 27,50-370 Wroclaw, Poland, phone: +48 71 3203693, e-mail: bogdan.miedzinski@pwr.wroc.pl

cross ref http://dx.doi.Org/10.5755/j01.eee.123.7.2374
COPYRIGHT 2012 Kaunas University of Technology, Faculty of Telecommunications and Electronics
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2012 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Title Annotation:ELECTRICAL ENGINEERING/ELEKTROS INZINERIJA
Author:Miedzinski, B.; Pyda, D.; Habrych, M.
Publication:Elektronika ir Elektrotechnika
Article Type:Report