Performance analysis of a nano refrigerant mixtures in a domestic refrigeration system.

INTRODUCTION

The most common refrigerant in current time is R134a in all the refrigeration systems like vapour compression refrigeration system, domestic refrigerators and air conditioners. But the only problem with this type of refrigerant is they need large amount of electric power. The new technology which is being introduced in present time is nanotechnology. By the help of nanotechnology nano refrigerants are formed. As compared to alternative refrigerant the nano refrigerant has better heat transfer. We have seen some research has been done by taking the nano refrigerant and they have found better heat transfer and energy consumption.

Sheng-shan Bi et al. [5] studied the nanoparticles application in domestic refrigerators. They observed that HFC134a and mineral oil with Ti[O.sub.2] nanoparticles works safely in the refrigerator. The HFC134a and nano particle/mineral oil system improves the refrigerator performance and Ti[O.sub.2]-R134a consumed less energy of 26.1%. Kai Guo et al. [6] states that Ti[O.sub.2]-R600a can work normally and efficiently in refrigerators. Compared with refrigerator with pure R600a as working fluids, 0.1 and 0.5 g/L concentrations of Ti[O.sub.2]-R600a can save 5.94% and 9.60% energy consumption respectively. Sabareesh et al. [7] presents the application of Ti[O.sub.2] nanoparticles in vapour compression refrigeration systems-an experimental investigation. According to their results, the usage of nano refrigerant in the VCR system decreases compressor work by 11% and increases the COP. D. Sendil Kumar et al. [8] studied on [Al.sub.2][O.sub.3]-R134a Nano Refrigerant in VCR System. They found that the replaced nano refrigerant increases the heat transfer rate .The system performance was improved with 10.2% less energy consumption when 0.2%v [Al.sub.2][O.sub.3]-R134a refrigerant was added. Subramani et al. [9] investigated the performance of refrigeration system with the help of nano-lubricant. The results showed that SUNISO 3GS lubricant oil produced a very effective result. By usage of Ti[O.sub.2] nano particles with R134a, the COP was increased and 15.4% less energy was consumed.

In another work, D. Sendil kumar et al. [10] presents the ZnO nano refrigerant in R152a refrigeration system for energy conservation and green environment. The result indicates that ZnO nano particles improved the thermo physical properties of refrigerant. The system performance was significantly improved and 0.5%v ZnO-R152a refrigerant can save 21% energy consumption. T.Coumaressin et al. [11] presents the performance analysis of a vapour compression refrigeration system using CuO nano fluid. In this paper the VCR system was analyzed on FLUENT software with CuO-R134a as working fluid. The results showed that the evaporating heat transfer is improved by adding CuO nano particles to an alternate refrigerant R134a. Fadhilah et al. [12] presents the Copper oxide nano particles for advance refrigerant thermo physical properties. They noted that the ABOs nano-particle used with R134a reduces the energy consumption by 10.32% while Ti[O.sub.2] nano-particles with R600a can reduce the power consumption by 5.94% with a nano particle concentration of 0.1g/L. Melih Aktas et al. [13] presents a theoretical comparative study on nano refrigerant performance in a single-stage vapourcompression refrigeration cycle. In this paper five different nano refrigerants such as R12, R134a, R430a, R436a, and R600a with [Al.sub.2][O.sub.3] nanoparticles was used. The compressor work and Coefficient of performance (COP) are investigated at various condenser and evaporation temperatures. The nano refrigerants enthalpy is obtained through the density. The results showed that COP is enhanced by adding nanoparticles ([Al.sub.2][O.sub.3]) to the pure (R600a) refrigerant. Jose Vicente Hallak d'Angelo et al. [14] presents a performance evaluation of a vapour injection refrigeration system using a mixture refrigerant R290/R600a, through steady-state simulations used to accomplish a parametric analysis such as COP, power consumption by compressor, Refrigerant mass flow rate. The results showed that a maximum COP was obtained when mixture containing 60 wt% of R600a and 40 wt% of R290.

Theoritical Analysis:

T-s and p-h diagram of simple vapour compression refrigeration system is shown in fig 1 respectively. It consists of the following four processes:

(1-2) Compressing refrigerant in compressor isentropically,

(2-3) Condensation at constant pressure,

(3-4) Adiabatic expansion in the expansion valve,

(4-1) Evaporation at constant pressure.

The work required to compressor is calculated as follows:

For isentropic compression, [W.sub.C] = m ([h.sub.2]-[h.sub.1]) (1)

For non-isentropic compression, [MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (2)

Heat rejection in condenser is calculated as follows:

[Q.sub.C] = m ([h.sub.2]-[h.sub.3]) (3)

Heat addition in evaporator is calculated as follows:

[Q.sub.e] = m ([h.sub.1]-[h.sub.4]) (4)

Mass flow rate of refrigerant is expressed as follows:

m = [Q.sub.0]/[q.sub.0]

Where, [Q.sub.0] is refrigerant capacity and [q.sub.0] is refrigerating effect

Actual Piston displacement of compressor is calculated as follows:

[V.sub.P] = m[[??].sub.1]/[[eta].sub.v]

Where, [[??].sub.1] is specific volume at inlet of compressor and [[eta].sub.v] is the volumetric efficiency

The performance of vapour compression refrigeration system can be measured in terms of coefficient of performance (COP), which is expressed as follows:

COP = Refrigerating Effect/Workdone

COP = ([h.sub.1] - [h.sub.4])/([h.sub.2] - [h.sub.1]) (7)

A. Thermo-Physical Properties of the Nano Fluid:

Thermo-physical properties of nano fluids are pre conditions for analyze of vapour compression system performance.

1) Density of Nano Fluid:

The nano fluid density for different concentrations of nano particles is developed by Pak and Cho [1] and it is given below.

Density of Nano fluid ([[rho].sub.nf]) = [PHI] [[rho].sub.np] + (1 - [PHI]) [[rho].sub.bf] (8)

2) Isobaric Specific Heat of Nano Fluid:

The equation for evaluating specific heat of nano refrigerant is developed by J. Lee et al [2] and it is given below.

Isobaric specific heat of nano fluid

([C.sub.nf]) = [PHI] [C.sub.np] + (1 - [PHI]) [C.sub.bf] (9)

3) Thermal conductivity of Nano Fluid:

The equation for evaluating thermal conductivity is developed by Maxwell et al [3] and it is given below.

Thermal conductivity of nano fluid

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (10)

4) Viscosity of Nano Fluid:

The equation for evaluating the viscosity of the nano fluid is developed by H. Brinkman et al [4] and it is given below.

Viscosity of nano fluid ([[mu].sub.bf]) = [[mu].sub.bf] [1/[(1 - [PHI]).sup.2.5]] (11)

Methodology:

The various thermo physical properties of the chosen In this paper performance of analysis nano refrigerant ([Al.sub.2][O.sub.3]/R290/R600a) with alternate refrigerant mixture (R290/R600a) in vapour compression refrigeration system has been carried out with help of Refprop software and Visual Basic software. The simulation programme was written based on the mathematical formula of vapour compression refrigeration system. The programming language used for writing the simulation program was Visual Basic .NET. Visual Basic .NET (VB.NET) is a multi-paradigm, object oriented programming language .The tool used for supporting the Programming language was Microsoft Visual Studio.

RESULTS AND DISCUSSION

Comparison of performance of R290/R600a mixture with adding nano particles to the same mixture in vapour compression refrigeration system has been carried out with the help of Refprop software and mathematical coding is developed by using visual studio software and graphs are plotted as below.

5.1 Comparison of Coefficient of performance with various proportion of R290/R600a mixture:

Figure 2 shows that the comparison of Coefficient of performance of various proportion of R290/R600a mixture. It is concluded from fig.2 R290/R600a (0.9/0.1) have notably high coefficient of performance than other proportion of R290/R600a mixture. Therefore, R290/R600a (0.9/0.1) can be suitable alternate mixture for adding the nano particles.

5.2 Comparison of Coefficient of performance with Nano refrigerant ([Al.sub.2][O.sub.3]/R290/R600a):

Figure 3 shows that the comparison of Coefficient of performance of R290/R600a (0.9/0.1) with adding [Al.sub.2][O.sub.3] with different proportion. It is concluded from fig.3 by adding nano particles ([Al.sub.2][O.sub.3]) to alternate refrigerant mixture (R290/R600a), the coefficient of performance will be improved based on concentration of nano particles.

Figure 4 shows the effect of evaporator temperature on Coefficient of performance of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 4 Coefficient of performance increases with increase in evaporator temperature till the optimum evaporator temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly high Coefficient of performance than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the Coefficient of performance is slightly increases.

Figure 5 shows the effect of evaporator temperature on mass flow rate of refrigerant of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 5 mass flow rate of refrigerant decreases with increase in evaporator temperature till the optimum evaporator temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly higher mass flow rate of refrigerant than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the mass flow rate of refrigerant is slightly increases.

Figure 6 shows the effect of evaporator temperature heat rejected in condenser of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 6 heat rejected in condenser decreases with increase in evaporator temperature till the optimum evaporator temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly lower heat rejected in condenser than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the heat rejected in condenser is slightly decreases.

Figure 7 shows the effect of evaporator temperature power consumption by compressor of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 7 power consumption by compressor decreases with increase in evaporator temperature till the optimum evaporator temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly lower power consumption by compressor than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the power consumption by compressor is slightly decreases.

Figure 8 shows the effect of evaporator temperature piston displacement of compressor of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 8 piston displacement of compressor decreases with increase in evaporator temperature till the optimum evaporator temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly higher piston displacement of compressor than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the piston displacement of compressor is slightly increases.

Figure 9 shows the effect of condenser temperature on Coefficient of performance of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). The pressure ratio across the compressor increases, with increase in condenser temperature causing work required by the compressor increases and cooling capacity decreases due to decrease in latent heat of evaporation. Hence, the combined effects of these two parameters decrease the Coefficient of performance decreases with increase in condenser temperature. It is concluded from figure 9 [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly higher Coefficient of performance than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the Coefficient of performance is slightly increases.

Figure 10 shows the effect of condenser temperature on mass flow rate of refrigerant of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 10 mass flow rate of refrigerant increases with increase in condenser temperature till the optimum condenser temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly higher mass flow rate of refrigerant than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the mass flow rate of refrigerant is slightly increases.

Figure 11 shows the effect of condenser temperature heat rejected in condenser of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 11 heat rejected in condenser increases with increase in condenser temperature till the optimum condenser temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly lower heat rejected in condenser than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the heat rejected in condenser is slightly decreases.

Figure 12 shows the effect of condenser temperature power consumption by compressor of R290/R600a (0.9/0.1) mixture and [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1). It is concluded from figure 12 power consumption by compressor increases with increase in condenser temperature till the optimum condenser temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly lower power consumption by compressor than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the power consumption by compressor is slightly decreases.

Figure 13 shows the effect of condenser temperature piston displacement of compressor of R290/R600a (0.9/0.1) mixture and AhOs/R290/R600a (0.04/0.9/0.1). It is concluded from figure 13 piston displacement of compressor increases with increase in condenser temperature till the optimum condenser temperature and here, [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) have significantly higher piston displacement of compressor than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the piston displacement of compressor is slightly increases.

Conclusion:

In this paper performance analysis nano refrigerant (AhOs/R290/R600a) with alternate refrigerant mixture (R290/R600a) in vapour compression refrigeration system has been carried out with help of Refprop software and Mathematical coding is developed by using visual studio software. The conclusions present in this analysis are given as follows.

* R290/R600a (0.9/0.1) have higher coefficient of performance than other proportion of R290/R600a mixture. Therefore, R290/R600a (0.9/0.1) can be suitable alternate mixture for adding the nano particles.

* By adding nano particles ([Al.sub.2][O.sub.3]) to alternate refrigerant mixture (R290/R600a), the coefficient of performance will be improved based on concentration of nano particles.

* [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) has significantly higher Coefficient of performance, mass flow rate of refrigerant, actual piston displacement of compressor than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the Coefficient of performance, mass flow rate of refrigerant, actual piston displacement of compressor is slightly increases.

* [Al.sub.2][O.sub.3]/R290/R600a (0.04/0.9/0.1) has significantly lower heat rejected in condenser, power consumption by compressor than R290/R600a (0.9/0.1). Therefore, by adding the nano particles ([Al.sub.2][O.sub.3]) to the alternate refrigerant mixture (R290/R600a) the heat rejected in condenser, power consumption by compressor is slightly decreases.

* With increasing evaporator temperature the Coefficient of performance increases, where mass flow rate of refrigerant, actual piston displacement of compressor, heat rejected in condenser and power consumption by compressor are decreases.

* With increasing condenser temperature the Coefficient of performance decreases, where mass flow rate of refrigerant, actual piston displacement of compressor, heat rejected in condenser and power consumption by compressor are increases.

REFERENCES

[1.] Pak, B.C., Y.I. Cho, 1998, Hydrodynamic and Heat Transfer Study of Dispersed Fluids with Submicron Metallic Oxide Particles, Experimental Heat Transfer, 11(2): 151-170.

[2.] Lee, J., I. Mudawar, 2007. Assessment of the effectiveness of nanofluids for single phase and two-phase heat transfer in micro-channels, Int. J. Heat Mass Transfer, 50(3-4): 452-463.

[3.] Maxwell, J., 1891. A Treatise on Electricity and Magnetisms, third ed., Clarendon Press, Oxford, 1(9): 310-314, 435.

[4.] Brinkman, H., 1952. The viscosity of concentrated suspensions and solutions, J. Chem. Phys., 20: 571.

[5.] Sheng-shan Bi, Lin Shi, Li-li Zhang, 2008. "Application of Nanoparticles in Domestic Refrigerators" Applied Thermal Engineering, 28: 1834-1843.

[6.] Kai Guo, Zhigang Liu, Shengshan Bi, 2008. Performance of Domestic Refrigerator using TiO2-R600a Nano Refrigerant as working fluid", Applied Thermal Engineering, 28: 1834-1843.

[7.] Sabareesh, R.K., N. Gobinath, V. Sajith, S. Das and C.B. Sobhan, 2012. "Application of TiO2 nanoparticles as a lubricant-additive for vapor compression refrigeration systems-an experimental investigation," International Journal of Refrigeration, 35(7): 1989-1996.

[8.] Sendil Kumar, D., Dr. R. Elansezhian, 2012. "Experimental Study on [Al.sub.2][O.sub.3]-R134a Nano Refrigerant in Refrigeration System", International Journal of Modern Engineering Research, 2(5): 3927-3929.

[9.] Subramani, N., Aswin Mohan, Dr. M Jose Prakash, 2013. "Performance Studies on a Vapour Compression Refrigeration System using Nano-Lubricant", International Journal of Innovative Research in Science, Engineering and Technology An ISO 3297: Certified Organization, 2(1).

[10.] Sendil Kumar, D., R. Elansezhian, 2013. "ZnO nano refrigerant in R152a refrigeration system for energy conservation and green environment International Journal of Modern Engineering Research, 2(5): 39273929.

[11.] Coumaressin, T. and K Palaniradja, 2014. "Performance analysis of a refrigeration system using nano fluid", International Journal of Advanced Mechanical Engineering. ISSN 2250-3234, 4(4): 459-470.

[12.] Fadhilah, SA., RS. Marhamah and A.H.M Izzat, 2014. "Copper oxide nano particles for advance refrigerant thermo physical properties: mathematical modeling", Hindawi Publishing Corporation Journal of Nanoparticles Volume 2014, Article ID 890751, p: 5.

[13.] Melih Aktas, Ahmet Selim Dalkilic, Ali Celen, and Alican Cebi, "A Theoretical Comparative Study on Nanorefrigerant Performance in a Single-Stage Vapor Compression Refrigeration Cycle", Journal of advance in Mechanical Engineering, Article ID 138725, p: 12.

[14.] Jose Vicente Hallak d'Angelo, Vikrant Aute, Reinhard Radermacher, 2016. "Performance Evaluation of a Vapor Injection Refrigeration System using mixture Refrigerant R290/R600a", International Journal of Refrigeration, pp: 1-34.

[15.] Guo-liang Ding, 2007. "Recent developments in simulation techniques for Vapour Compression Refrigeration Systems", International Journal of Refrigeration 30 (2007), pp: 1119-1133.

[16.] Juan Carlos Valdez Loaiza, Frank Chaviano Pruzaesky, Jose Alberto Reis Parise, 2010. "A Numerical Study on the Application of Nanofluids in Refrigeration Systems", International Refrigeration and Air Conditioning Conference at Purdue, July 12-15, pp: 2010- 2495.

[17.] Hao Peng, Guoliang Ding, Haitao Hu, 2011. "Influences of Refrigerant-based nanofluid composition and heating condition on the migration of nanoparticles during pool boiling". Part I: Experimental measurement, International Journal of Refrigeration 34 (2011), pp: 1823-1832.

[18.] Elena Timofeeva, V., Yu. Wenhua, M. David France, Dileep Singh, L. Jules Routbort, 2011. Nanofluids for heat transfer: an engineering approach Timofeeva et al. Nanoscale Research Letters 2011, 6: 182.

[19.] Reji Kumar, R., K. Sridhar, M. Narasimha, "Heat transfer Enhancement in Domestic Refrigerator using R600a/mineral oil/nano-AEOs as working fluid", International Journal of Computational Engineering, 03(4).

[20.] Subramani 1, N., M.J. Prakash, 2011. "Experimental studies on a Vapour Compression System using nanorefrigerants", International Journal of Engineering, Science and Technology, 3(9): 95-102.

[21.] Eed Abdel-Hafez Abdel-Hadi, Sherif Hady Taher Abde Hamid Mohamed Torki and Samar Sabry Hamad, 2011. "Heat transfer analysis of vapour compression system using Nano CuO-R134a", 2011 International Conference on Advanced Materials Engineering IPCSIT, vol, 15.

[22.] Mahbubul, I.M., R. Saidur and M.A. Amalina, 2012. "Investigation of viscosity of R123-TiO2 Nano refrigerant", International Journal of Mechanical and Materials Engineering , 7(2): 146-151.

[23.] Jose Alberto Reis Parise, Ricardo Fernando Paes Tiecher, 2012. "A Simulation Model for the Application of Nanofluids as Condenser Coolants in Vapour Compression Heat Pumps", International Refrigeration and Air Conditioning Conference at Purdue, July 16-19, 2531.

[24.] Lixin Cheng, Lei Liu, 2013. Boiling and two-phase flow phenomena of refrigerant-based nanofluids: Fundamentals, applications and challenges, International Journal of Refrigeration, 36: (421-446).

[25.] Dr. Mishra, RS., 2014. "Methods for improving Thermodynamic performance of Vapour Compression Refrigeration System using twelve ecofriendly refrigerants in primary circuit and nano fluid in secondary", International Journal of Emerging Technology and Advanced Engineering Website: www.ijetae.com (ISSN 2250-2459, ISO 9001:2008 Certified Journal, 4(6).

[26.] Parvinder Singh, 2015. "To Study the Application of Nano Refrigerant in Refrigeration System", International Journal of Research in Engineering and Technology, 4(06): 414-417.

(1) B Pitchia Krishnan, (2) K Gokulnath, (3) R Dr.Vijayan, (4) A Ragland Gazetrin Prabhu

(1,2,4) PG Scholar, Department of Mechanical of Engineering, Government College of Engineering, Salem, Tamil Nadu, 636011, India.

(3) Professor and Head, Department of Mechanical of Engineering, Government College of Engineering, Salem, Tamil Nadu, 636011, India.

Received 28 January 2017; Accepted 22 March 2017; Available online 28 April 2017

Address For Correspondence:

B Pitchia Krishnan, PG Scholar, Department of Mechanical of Engineering, Government College of Engineering, Salem, Tamil Nadu, 636011, India.

E-mail: b.p.krishnan001@gmail.com

Caption: Fig. 1: p-h and T-s diagram of vapour compression refrigeration system

Caption: Fig. 2: Performance comparison of various proportion of R290/R600a mixture.

Caption: Fig. 3: Performance comparison of R290/R600a (0.9/0.1) with adding [Al.sub.2][O.sub.3] with different proportion.

Caption: Fig. 4: Effect of evaporator temperature on Coefficient of performance.

Caption: Fig. 5: Effect of evaporator temperature on mass flow rate of refrigerant.

Caption: Fig. 6: Effect of evaporator temperature on heat rejected in condenser.

Caption: Fig. 7: Effect of evaporator temperature on power consumption by compressor.

Caption: Fig. 8: Effect of evaporator temperature on piston displacement of compressor.

Caption: Fig. 9: Effect of condenser temperature on Coefficient of performance.

Caption: Fig. 10: Effect of condenser temperature on mass flow rate of refrigerant.

Caption: Fig. 11: Effect of condenser temperature on heat rejected in condenser.

Caption: Fig. 12: Effect of condenser temperature on power consumption by compressor.

Caption: Fig. 13: Effect of condenser temperature on piston displacement of compressor.
COPYRIGHT 2017 American-Eurasian Network for Scientific Information
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2017 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Krishnan, B. Pitchia; Gokulnath, K.; Vijayan, R.; Prabhu, A. Ragland Gazetrin
Publication:Advances in Natural and Applied Sciences
Article Type:Report
Date:Apr 30, 2017
Words:3913
Previous Article:Fatigue life investigation of damaged aluminum alloy material plate.
Next Article:Improvisation of clean-in-process for paint filling machine in paint manufacturing industries.