Methodology of nondestructive identification of defective concrete zones in unilaterally accessible massive members.

Introduction

The massive members of hydroelectric power plants, dams, and other structures are erected from concrete--one of the principal construction materials (Kmiecik, Kaminski 2011; Soutsos et al. 2011; Angst et al. 2012; Musial 2012). Because of the great thickness and mass of the concrete such structures incorporate they are prone to locally develop defective zones during construction. These are zones in which the concrete mixture was not vibrated. There are also zones in which the concrete mixture contained large aggregate particles, which were not sufficiently enveloped with cement mortar. In such zones, the hardened concrete is excessively porous (honeycombed). The zones are macrononhomogeneities which in extreme cases can locally occupy a volume of up to several cubic meters.

In the course of their service, such structural members are usually simultaneously subjected to unilateral water pressure and vibrations. This applies, for example to the walls of access galleries in hydroelectric power plants. As a result of the continuous vibrations generated by the operating power plant turbines, with time zones of excessively porous state, and so weaker, concrete can interconnect via cracks propagating in the concrete, whereby "paths" pervious to water form across the wall. Water flowing along the "paths" increases the leakiness of the walls. Water dissolves and washes out calcium hydroxide (Ca[(OH).sub.2]) from the hardened cement grout. As lime is being leached, leakiness increases further and the compression strength of the concrete decreases. This adversely affects the durability of the concrete members (Safinowski 2011; Lowinska-Kluge, Blaszczymki 2012; Lydzba et al. 2012).

Water leakages into the gallery make its use difficult. Attempts at sealing the leaking places without a prior reconnaissance aimed at locating the zones of weaker concrete and determining their extent are ineffective at long term, since new leaking places (indicating that new paths of water leakage through the wall have formed) appear besides the already sealed places, as shown in Figure 1. In order to effectively solve the troublesome problem of water leaks it is necessary to detect and locate, adequately early, the defective zones in the unilaterally accessible massive concrete member, at least to a depth of about 1000-1500 mm.

The detection and location of such zones of defective (excessively porous) concrete in members accessible from only one side is not easy. Nondestructive acoustic techniques, especially the state-of-the-art impulse response technique (ASTM C1740-10 2010) and ultrasonic tomography (Hola, Schabowicz 2010; Schabowicz, Hola 2012), increasingly and often used today to diagnose building structures, can be helpful in this regard (Schickert 2005; Beutel et al. 2008; Maksymowicz et al. 2011; Zwolski, Bien 2011; Goszczymka et al. 2012; Leibbrandt et al. 2012; Ozbolt et al. 2012).

In this paper the authors propose, on the basis of their research experience to date (Schabowicz et al. 2010; Gorzelanczyk et al. 2012a, b; Schabowicz, Hola 2012), an original test methodology, integrating the latest nondestructive techniques, for identifying and locating defective zones in unilaterally accessible massive concrete members. The methodology has already been used in practice. An example of its use is provided.

Since the two nondestructive diagnostic techniques have not been commonly used so far, and hence are less known, a concise description of them, necessary to understand the proposed methodology is included.

1. Survey of literature

The identification of defects, including excessively porous zones, in unilaterally accessible concrete members by means of ultrasonic tomography, has been studied, among others by Bishko et al. (2008), Kozlov et al. (1997), Samokrutov et al. (2002, 2006), Samok rutov, Shevaldykin (2011) and Shevaldykin et al. (2003). Also in Bishko (2007) the nondestructive ultrasonic tomography method was recommended for identifying defects in concrete members. Stawiski (2012) used the nondestructive ultrasonic method and point probes to identify concrete nonhomogeneities in horizontally formed members. Quiviger et al. (2010) proposed to use the nondestructive ultrasonic echo method to identify macrononhomogeneities and macrocracks in concrete members. In Garbacz and Piotrowski (2010), Krause et al. (2005) and Taffe, Wiggenhauser (2006) it is proposed to use the impact-echo method for this purpose. In Davis (2003), Davis et al. (1996) Hertlein, Davis (1998) and Ottosen et al. (2004) the nondestructive impulse response method is recommended for locating defects in concrete members. The above authors studied relatively thin concrete members, each time using a single nondestructive method.

In the literature, one cannot find any study dealing with the identification and location of defects in the form of excessively porous concrete in unilaterally accessible massive concrete members, for which purpose, at least two of the above nondestructive acoustic methods, for example, the impulse response method and the ultrasonic tomography method, would be used sim ultaneously. Although the authors Kurz et al. (2012) and Huston et al. (2011) came up with an idea of the integrated use of the methods, the experiments they conducted were not directly connected with the location of zones of excessively porous concrete.

The present authors' research indicates that the nondestructive acoustic methods of impulse response and ultrasonic tomography when used integratively, complement each other. Owing to this they can be useful in identifying and locating defective zones (concrete macrononhomogeneities) in massive members accessible from only one side. The impulse response method is suitable for the fast searching of defects in large concrete surfaces and enables one to approximately identify and locate such defects in up to 1500 mm thick members, but the depth at which a defect occurs cannot be directly assessed. This possibility is offered by ultrasonic tomography, enabling one to identify and spatially locate defects in massive members with a thickness of up to 2500 mm.

2. Concise description of nondestructive methods integrated in proposed methodology

Table 1 presents basic information on the impulse response method, including: a brief description, a schematic of the test setup, the registered parameters, and sample tests results. A more comprehensive description of this test method can be found in Hola, Schabowicz (2010) and Hola et al. (2011).

Table 2 presents basic information on the ultrasonic tomography method. A more comprehensive description of this method can be found in Hola, Schabowicz (2010) and Schabowicz, Hola (2012).

3. Proposed methodology of nondestructive tests

The methodology proposed for the nondestructive identification and location of defective (macrononhomogeneities) concrete zones in unilaterally accessible massive members through the integrated use of state-of-the-art acoustic methods of impulse response and ultrasonic tomography is graphically presented in Figures 2 and 3 and described below.

As Figure 3 shows, it is proposed to carry out the investigations in two stages.

In stage I, the impulse response method is used to identify and superficially locate defective concrete zones present in the tested member.

For this purpose i measuring places should be marked on the tested concrete member. In each of the places one should mark a grid of n measuring points spaced at every 1000 mm, keeping a minimum distance of 500 mm from the edge of the tested member. If the surface area of the latter is very large one can increase the spacing to 2000 mm. The maximum testing range, that is the distance from the surface, amounts to about 1500 mm.

Then an elastic wave is generated by striking with the calibrated hammer in each point of the marked measuring grid, and after each strike the value of elastic force F generated by the hammer, the diagram of elastic wave velocity w and the diagram of mobility N are analyzed. The conditions, the satisfaction of which guarantees satisfactory reliability of the obtained results are specified in ASTM C174010 (2010), Hola et al. (2011) and Hertlein, Davis (1998).

If the results are found to be satisfactory, they should be processed using the dedicated software. In this way the values of the characteristic parameters, that is average mobility [N.sub.av], stiffness [K.sub.d], mobility slope [M.sub.p], mobility times mobility slope [N.sub.av] x [M.sub.p], and voids index w, in each of the measuring grid points are obtained. Then maps showing the distribution of the parameter values on the surface of the tested member should be plotted.

The final step in this stage is a detailed analysis of the maps, the aim of which is to approximately identify the zones where it is highly probable that defects occur.

Then one should move to stage II of the investigations, using the ultrasonic tomography method to confirm the defects detected by the impulse response method and to locate them along the depth of the tested member.

First, k measuring bands should be marked in the zones found to be defective. At least one measuring band with a minimal width equal to that of the measuring antenna and having the desired length should be marked in each such zone. Depending on the type of the antenna, the band is 380 or 500 mm wide while its length may amount to several meters.

Then one should calibrate the tomograph by measuring the velocity of the ultrasonic wave (signal) in a given zone several times and determining its average value.

Subsequently, one should measure the velocity of this wave in each antenna application place in each of the bands. In the course of the measurement the ultrasonic signals should be preliminarily analyzed to determine whether the defect can be identified on their basis. If this is not the case, the test should be repeated. If the answer is yes, the signals should be processed using the dedicated software. The processing consists in assembling the data recorded for a given measuring band.

If the results are satisfactory, they are recorded and flat images B-D, showing the inside of the concrete member in the given zone, in three mutually perpendicular directions are obtained. The defective concrete zone can be identified and located along the depth of the tested member through a detailed analysis of images B and D. Image C helps to determine more precisely the depth at which the defect occurs.

In stage III it is recommended to do a destructive verification, for example, by taking a drill core.

4. Example of practical use of proposed methodology

The proposed methodology was used in practice to locate and identify defective zones of concrete in a massive access gallery in a hydroelectric power plant. The tests were carried out in connection with a planned renovation of the power plant. Figure 4 shows the power plant, the access gallery, and a close up of a water leakage on the gallery wall.

4.1. Description of tested wall

During their operation the turbines (each with a power of a few tens of megawatts) make the massive concrete members (including the access gallery walls) vibrate. The gallery walls are made of C25/20 grade concrete with a maximum aggregate size of 32 mm and since they are situated below the water level they should be leakproof. Despite the repeated local sealing, new leaks keep on appearing.

The massive concrete gallery wall, accessible from only one side, was tested in 30 measuring places along its entire length using the proposed methodology. The location and numbers of the places are shown in Figure 5. A grid (4-5 rows and 3-11 columns) of measuring points (in total 1050 measuring points along the entire length of the wall) was marked in each measuring place. The distance between the measuring points amounted to about 500 mm.

The tests were carried out in accordance with the methodology described in Section 4, using first the impulse response method and then the ultrasonic tomography method.

4.2. Results of tests

In the course of testing by the impulse response method in each of the measuring points an elastic wave was excited using a special rubber-tipped hammer and the values of the characteristic parameters: average mobility [K.sub.d], mobility slope [M.sub.p], average mobility times mobility slope [N.sub.av] x [M.sub.p], and voids ratio v were determined. Sample parameter values determined in 10-20 measuring points are presented in Table 3. On the basis of the parameter values in all the measuring points, maps showing the distribution of the parameter values were plotted. Sample maps for measuring points 3 and 23 are presented in Table 4.

It appears from Table 4 that in almost the whole measuring place no. 3 the value of parameter [N.sub.av] is high, ranging from 5 to 10 m/s x N, whereas within measuring point 5-1 its value is low, ranging from 0 to 5 m/s x N. At the same time the value of parameter [K.sub.d] is high, ranging from 0.4 to 0.8 in most of the measuring place. Therefore, it can be concluded that in measuring place no. 3 a defect in the form of concrete nonhomogeneity is unlikely to occur. This conclusion is confirmed by the map of the distribution of the characteristic parameters, shown in Table 4.

Table 4 also shows that the value of parameter [N.sub.av] is high in almost the whole measuring place no. 23, ranging from 5 to 10 m/s x N, and within measuring points 5-1 and 5-4 it is very high, ranging respectively from 10 to 15 m/s x N. The value of parameter [K.sub.d] is very low, ranging from 0 to 0.2 in most of the measuring place, except for measuring point 3-2 where this parameter ranges from 0.3 to 0.4. On this basis and from an analysis of the map showing the distribution of the characteristic parameters (Table 4) one can conclude that in measuring place no. 23 a defect in the form of a concrete nonhomogeneity is very likely to occur.

Analyses of the results obtained in 30 measuring places showed that, similarly as in the case of measuring place no. 3, in 16 other tested places there are no reservations about the quality of the concrete. Whereas in 13 tested places, as shown for test place no. 23, defective zones characterized by high concrete nonhomogeneity occur.

Then, in accordance with the proposed methodology, tests were carried out using the nondestructive ultrasonic tomography method. Their aim was to confirm the presence of the defective concrete zones previously detected by the impulse response method and locate them along the depth. The tests were carried out in the measuring places in which defective zones had been located in investigation stage I. In each of the zones, three measuring bands, each 500 mm wide and 1500 mm long, were marked.

Sample test results obtained using the ultrasonic tomograph, showing images B and D in measuring place no. 3 (deemed not defective) and in the defective zones (measuring place no. 23) are presented in Table 5. The defective concrete zone identified in measuring place no. 23 is marked with a dotted line in image D. Table 5 also contains photographs showing the results of exposure in the form of drill cores taken from measuring places 3 and 23. The bottom row of Table 5 contains comments stemming from the investigations.

The results obtained using the ultrasonic tomography method confirmed the results, which had been obtained by the impulse response method. As shown for test place no. 23, the presence of highly porous and nonhomogenous concrete zones was confirmed in 13 of the test places. In the particular zones, the defects were located along the depth of the tested member.

Conclusions

A novel methodology integrating the state-of-the-art acoustic methods of impulse response and ultrasonic tomography for the nondestructive identification and location of zones of defective (honeycombed) concrete in unilaterally accessible massive members has been presented. Since the above nondestructive methods are not commonly used for testing, whereby they are less known, the presentation of the methodology was preceded by a concise description of the methods in order to facilitate their understanding.

Three stages are distinguished in the proposed methodology. In stage I, in which tests are carried out using the nondestructive impulse response method, defective zones in the tested member are identified and superficially located. In stage II, in which tests are carried out using the nondestructive ultrasonic tomography method, the defects detected by the impulse response method in stage I are confirmed and located along the depth of the tested member. In stage III, the results obtained by the nondestructive methods are destructively verified in a randomly selected place.

The provided example of the application of the methodology to a real civil engineering structure has shown the methodology to be useful for identifying and locating defective concrete zones in the unilaterally accessible massive wall of the gallery in the hydroelectric power plant.

doi: 10.3846/13923730.2013.812577

References

Angst, U.; Elsener, B.; Jamali, A.; Adey, B. 2012. Concrete cover cracking owing to reinforcement corrosion--theoretical considerations and practical experience, Materials and Corrosion 63(12): 1069-1077.

ASTM C1740-10. 2010. Standard practice for evaluating the condition of concrete plates using the impulse-response method. USA, West Conshohocken, PA: American Society for Testing and Materials (ASTM). 9p.

Beutel, R.; Reinhardt, H.; Grosse, C.; Glaubitt, A.; Krause, M.; Maierhofer, C.; Algernon, D.; Wiggenhauser, H.; Schickert, M. 2008. Comparative performance tests and validation of NDT methods for concrete testing, Journal of Nondestructive Evaluation 27(1-3): 59-65. http://dx.doi.org/10.1007/s10921-008-0037-1

Bishko, A. 2007. Improvement of imaging at small depths for acoustic tomography of reinforced concrete objects, in The 6th International Conference Non-Destructive Testing and Technical Diagnostics in Industry, 15-17 May, 2007, Moscow, Russia. Abstracts book, Vol. 1. Moscow: Mashinostroenie.

Bishko, A.; Samokrutov, A.; Shevaldykin, A. 2008. Ultrasonic echo-pulse tomography of concrete using shear waves low-frequency phased antenna arrays, in the 17th World Conference on Nondestructive Testing, 25-28 October, 2008, Shanghai, China. 9 p.

Davis, A. 2003. The non-destructive impulse response test in North America: 1985-2001, NDT&E International 36(4): 185-193. http://dx.doi.org/10.1016/S0963-8695(02)00065-8

Davis, A.; Hertlein, B.; Lim, K.; Michols, K. 1996. Impact-echo and impulse response stress wave methods: advantages and limitations for the evaluation of highway pavement concrete overlays, in Proc. of Conference on Nondestructive Evaluation of Bridges and Highways, 13 November, 1996, Scottsdale, Vol. 2946. 7 p.

Garbacz, A.; Piotrowski, T. 2010. Zastosowanie metody impact-echo do szacowania grubosci posadzek betonowych [Application of impact-echo method to identify the concrete floor thickness], Materiafy Budowlane 9: 18-19.

Gorzelanczyk, T.; Hola, J.; Schabowicz, K. 2012a. Nondestructive tests aimed at determining the thickness of the concrete shell of a heat pipe carrying tunnel, in 18th World Conference on Nondestructive Testing, 16-20 April, 2012, Durban, South Africa. 8 p.

Gorzelanczyk, T.; Hola, J.; Sadowski, L.; Schabowicz, K. 2012b. Evaluation of concrete homogeneity in massive structural element of hydroelectric power plant by means of nondestructive ultrasonic tomography method, in Proc. of the 42nd International Conference "Defektoskopie", 30 October-1 November, 2012, Sec u Chrudimi, Czech Republic, 71-76.

Goszczyfiska, B.; Swit, G.; Trampczynski, W.; Krampikowska, A.; Tworzewska, J.; Tworzewski, P. 2012. Experimental validation of concrete crack identification and location with acoustic emission method, Archives of Civil and Mechanical Engineering 12(1): 23-28. http://dx.doi.org/10.1016/j.acme.2012.03.004

Hertlein, B.; Davis, A. 1998. Locating concrete consolidation problems using the nondestructive impulse response test, in American Concrete Institute Fall Convention, Los Angeles, October, 1998. 22 p.

Hola, J.; Schabowicz, K. 2010. State-of-the-art nondestructive methods for diagnostics testing of building structures--anticipated development trends, Archives ofCivil and Mechanical Engineering 10(3): 5-18. http://dx.doi.org/10.1016/S1644-9665(12)60133-2

Hola, J.; Sadowski, L.; Schabowicz, K. 2011. Nondestructive identification of delaminations in concrete floor toppings with acoustic methods, Automation in Construction 20(7): 799-807. http://dx.doi.org/10.1016/j.autcon.2011.02.002

Huston, D.; Cui, J.; Burns, D.; Hurley, D. 2011. Concrete bridge deck condition assessment with automated multisensor techniques, Structure and Infrastructure Engineering: Maintenance, Management, Life-Cycle Design and Performance 7(7-8): 613-623.

Kmiecik, P.; Kamini ski, M. 2011. Modelling of reinforced concrete structures and composite structures with concrete strength degradation taken into consideration, Archives of Civil and Mechanical Engineering 11(3): 623-636. http://dx.doi.org/10.1016/S1644-9665(12)60105-8

Kozlov, V.; Samokrutov, A.; Shevaldykin, V. 1997. Thickness measurements and flaw detection in concrete using ultrasonic echo method, Journal of Nondestructive Testing and Evaluation 13(2): 73-84. http://dx.doi.org/10.1080/02780899708953020

Krause, M.; Milmann, B.; Niederleithinger, E. 2005. Assessment of foundation slabs with USecho in the re-use process, in Proc. of the International Conference on Concrete Repair, Rehabilitation and Retrofitting (ICCRRR), 2005, Cape Town, South Africa, 525-530.

Kurz, J.; Stoppel, M.; Taffe, A.; Boller, C. 2012. Condition assessment of reinforced concrete structures using automated multi-sensor systems, in 18th World Conference on Nondestructive Testing, 16-18 April, 2012, Durban, South Africa. CD-ROM.

Leibbrandt, A.; Caprari, G.; Angst, U.; Siegwart, R.; Flatt, R.; Elsener, B. 2012. Climbing robot for corrosion monitoring of reinforced concrete structures, in Proc. of the 2nd International Conference on Applied Robotics in the Power Industry (CARPI 2012), 11-13 September, 2012, Zurich, Switzerland, 10-15.

Maksymowicz, M.; Cruz, P.; Bien, J. 2011. Load capacity of damaged RC slab spans of railway-bridges, Archives of Civil and Mechanical Engineering 11(4): 963-978. http://dx.doi.org/10.1016/S1644-9665(12)60089-2

Lowinska-Kluge, A.; Blaszczynski, T. 2012. The influence of internal corrosion on the durability of concrete, Archives of Civil and Mechanical Engineering 12(2): 219-227. http://dx.doi.org/10.1016/j.acme.2012.03.002

Lydzba, D.; Rozanski, A.; Sobotka, M. 2012. An annual cycle of changes in water temperature as a cause of cracking in massive concrete hydraulic structures, AGH Journal of Mining and Geoengineering 36(2): 217-227.

Musial, M. 2012. Static and dynamic stiffness of reinforced concrete beams, Archives of Civil and Mechanical Engineering 12(2): 186-191. http://dx.doi.org/10.1016/j.acme.2012.04.005

Ottosen, N.; Ristinmmaa, M.; Davis, A. 2004. Theoretical interpretation of impulse response tests of embedded concrete structures, Journal of Engineering Mechanics 130(9): 1062-1071. http://dx.doi.org/10.1061/(ASCE)0733-9399(2004)130: 9(1062)

Ozbolt, M.; Rukavina, T.; Domitrovic, J. 2012. Comparison of the pavement layers thickness measured by georadar and conventional methods--examples from Croatia, The Baltic Journal of Road and Bridge Engineering 7(1): 30-35. http://dx.doi.org/10.3846/bjrbe.2012.04

Quiviger, A.; Zardan, J.; Payan, C.; Chaix, J.; Garnier, V.; Moysan, J.; Jean Salin, J. 2010. Macro crack characterization by linear and nonlinear ultrasound in concrete, Proceedings of Meetings on Acoustics 10: 045003.

Samokrutov, A.; Kozlov, V.; Shevaldykin, V.; Meleshko, I. 2002. Ultrasonic defectoscopy of concrete by means of pulseecho technique, in Proc. of the 8th European conference for Non-Destructive Testing, 2002, Madrid, Spain. Madrid: Spanish Society for NDT, 1-9. CD-ROM.

Samokrutov, A.; Kozlov, V.; Shevaldykin, V. 2006. Ultrasonic testing of concrete objects using dry acoustic contact. Methods, instruments and possibilities, in The 5th International Conference "Non-Destructive Testing and Technical Diagnostics in Industry"',16-19 May, 2006, Moscow, Russia. Abstracts book. Moscow: Mashinostroenie 152 p.

Samokrutov, A.; Shevaldykin, V. 2011. Ultrasonic tomography of metal structures using the digitally focused antenna array method, Russian Journal of Nondestruc tive Testing 47(1): 16-29. http://dx.doi.org/10.1134/S1061830911010098

Safinowski, P. 2011. Diagnostic ultrasonore de la degradation mecanique et structurale du beton [Ultrasonic diagnostics of mechanical and structural degradation of concrete]: PhD Thesis, Universitei Lille Nord-de-France.

Schabowicz, K.; Hola, J.; Stys, D. 2010. Nondestructive elastic-wave tests of concrete in foundation slab, in the 10th European Conference on Nondestructive Testing, 7-11 June, 2010, Moscow, Russia. 1 p.

Schabowicz, K.; Hola, J. 2012. Nondestructive elastic-wave tests of foundation slab in office building, Materials Transactions 53(2): 296-302. http://dx.doi.org/10.2320/matertrans.I-M2011845

Schickert, M. 2005. Progress in ultrasonic imaging of concrete, Materials and Structures 38: 807-815.

Shevaldykin, V.; Samokrutov, A.; Kozlov, V. 2003. Ultrasonic low-frequency short-pulse transducers with dry point contact. Development and application, in International Symposium Non-Destructive Testing in Civil Engineering (NDT-CE), 16-19 September, 2003, Berlin, Germany. Proceedings on BB 85-CD, V66, Berlin.

Soutsos, M. N.; Kang, T.; Khalid, H. A.; Millard, S. G. 2011. The effect of construction pattern and unit interlock on the structural behaviour of block pavements, Construction and Building Materials 25(10): 3832-3840. http://dx.doi.org/10.1016/j.conbuildmat.2011.04.002

Stawiski, B. 2012. The heterogeneity of mechanical properties of concrete in formed constructions horizontally, Archives of Civil and Mechanical Engineering 12(1): 90-94. http://dx.doi.org/10.1016/j.acme.2012.03.006

Taffe, A.; Wiggenhauser, H. 2006. Validation for thickness measurement in civil engineering with ultrasonic echo, in 9th European Conference on Nondestructive Testing, 25-29 September, 2006, Berlin, Germany. 8 p.

Zwolski, J.; Bien, J. 2011. Modal analysis of bridge structures by means of forced vibration tests, Journal of Civil Engineering and Management 17(4): 590-599. http://dx.doi.org/10.3846/13923730.2011.632489

Tomasz GORZELANCZYK, Jerzy HOLA, Lukasz SADOWSKI, Krzysztof SCHABOWICZ

Institute of Building Engineering, Wroclaw University of Technology, Wybrzeze

Wyspianskiego 27, 50-370 Wroclaw, Poland

Received 10 Apr 2013; accepted 3 Jim 2013

Corresponding author: Lukasz Sadowski

E-mail: lukasz.sadowski@pwr.wroc.pl

Tomasz GORZELANCZYK. PhD, Eng, Assistant Professor in the Civil Engineering Faculty at Wroclaw University of Technology, Poland. He obtained his diploma in civil engineering at the WUT in 2001. He is working at WUT, Institute of Building Engineering. Research interests: concrete (especially self-compacting concrete), failure of concrete, acoustic emission, and other nondestructive tests.

Jerzy HOLA. Full professor at the Wroclaw University of Technology, dean of the Faculty of Civil Engineering, Head of the Department of General Building Engineering, and director of the Accredited Research Laboratory at the Institute of Building Engineering. He is a member of the following organizations among others: Senate of the Wroclaw University of Technology, Council of the Faculty of Civil Engineering, Section of Engineering Construction Materials the Committee of Civil Engineering Polish Academy of Sciences, Committee of Mechanics and Civil Engineering at the Polish Academy of Sciences Wroclaw, Science Committee of PZITB (Polish Association of Building Engineers and Technicians), and the program board of the magazine "Builder".

Lukasz SADOWSKI. MSc, Eng, a researcher at Wroclaw University of Technology, Poland. He obtained his diploma in civil engineering at WUT in 2007. He is a research assistant at WUT, Institute of Building Engineering. Research interests: concrete (especially concrete floors), corrosion, adhesion, 3D surface roughness topography measurement, nondestructive tests, acoustic techniques, and artificial intelligence.

Krzysztof SCHABOWICZ. PhD, Eng, Assistant Professor in the Civil Engineering Faculty at Wroclaw University of Technology. Received his PhD in 2003 at Wroclaw University of Technology. Author and co-author of 3 books, over 100 other publications, as well as over 150 research and technical reports. Member of the Polish Association of Civil Engineers and Technicians (PZITB), member of Polish Association of Building Mycology (PSMB). His research interests include concrete, ultrasonic tomography, impact-echo, impulse response, GPR and other nondestructive tests, and artificial intelligence.

Table 1. Concise description of impulse response method
(Davis et al. 1996; Hertlein, Davis 1998; Davis 2003;
Ottosen et al. 2004)

Description of method

The impulse response method consists in exciting an
elastic ultrasonic wave in the tested member by
means of a calibrated hammer with a rubber tip. The
frequency of the excited wave is in a range of 1-800 Hz,
while the range of excitation around the test point
amounts to 1000 mm. The method is suitable for the
approximate location of areas in which defective zones
in the form of concrete nonhomogeneities may occur in
unilaterally accessible members, to a depth of about
1500 mm.

Schematic of test setup

Test procedure

Calibrated hammer strikes are delivered in selected test
points of a grid of, for example, 1000 x 1000 mm,
squares marked on the surface of the tested member.
The signal of the elastic wave propagating in the
member is registered by a geophone and amplified. The
signals recorded in the course of the test are processed
using dedicated software installed on a portable
computer. In this way the values of five parameters are
obtained.

Registered parameters

In each test point the values of the following parameters are
registered:

-- average mobility [N.sub.av];

-- stiffness [K.sub.d];

-- mobility slope [M.sub.p]/N;

-- mobility times mobility slope [N.sub.av] x [M.sup.p]/N;

-- voids index v.

Maps showing the distribution of the above parameters
on the surface of the tested member are plotted on this
basis.

Sample results and their analysis

Typical maps showing the distribution of the registered
parameters on the surface of the tested member are
presented as follows:

An analysis of the parameter values is carried out,
considering that, for example,

-- a local increase in the value of parameter [N.sub.av] in a given
test point may indicate a smaller thickness of the member in
this point or a nonhomogeneity in the concrete;

-- a local decrease in the value of [K.sub.d] in a test point may
indicate a nonhomogeneity in the concrete there, a
delamination of layers, and so on;

-- a high value of parameter [M.sub.p]/N is closely connected
with the presence of defects, for example, delaminations in
the cross section of the tested member or an inadequate
interlayer bond;

-- if parameter [N.sub.av] x [M.sub.p]/N reaches a value higher than
3 [10.sup.-7] m/s -Nthis means that a defective area occurs in the
tested place;

-- if the value of coefficient v is higher than 2, this may
indicate a defective area.

Table 2. Concise description of ultrasonic tomography
method (Kozlov et al. 1997; Bishko 2007; Bishko
et al. 2008)

Description of method

The ultrasonic tomography method consists in exciting an
elastic wave in the tested member. The exciter is a
multihead antenna (incorporating tens of integrated
ultrasonic heads) which is also used to receive and
process ultrasonic signals. The heads generate ultrasonic
pulses with a frequency of 50 kHz. The maximum test
range amounts to 2500 mm of the tested member
thickness.

The tomograph has been designed to determine the
thickness of unilaterally accessible concrete member and
to detect cracks, inclusions, air voids, and other places
which may be empty or filled with a liquid or a material
differing in its density and other physical mechanical
properties from the surrounding concrete.

Schematic oftest setup

Test procedure

In the course of the test the ultrasonic tomograph antenna is
moved stepwise (at a step of 100 mm) in the same
direction in a given 380 mm or 500 mm wide (depending
on the antenna type) test band. The obtained results, in
the form of images of the cross sections in each antenna
position, are collected in a three-dimensional matrix table.
Using this matrix table and the dedicated software
installed on a portable computer one obtains three images
B-D in three mutually perpendicular directions, as shown
in the following figure:

Results and their interpretation

Using this method one obtains three mutually perpendicular
images B-D in each of the 380 or 500 mm wide test band
and an ultrasonic dispersion level color scale assigned to
the images, as shown in the following figure:

The interpretation of the obtained results comes down to the
analysis of the images. From the differences in the level of
ultrasonic dispersion one can infer whether the physical
characteristics of the media differ or do not differ from
each other in the tested area, which means that one can
infer whether within the tested band there is a material
(air voids, concrete zones of different density, large
inclusions, etc.) whose density is different than that of
the concrete.

Table 3. Sample values of characteristic parameters,
determined by impulse response method

No.     Number of               Parameter symbol
        measuring
        place/(row
        no.-column
           no.)

                      [N.sub.av]   [K.sub.d]   [M.sub.p]/
                       (m/s-N)        (-)        N (-)

1        1/(1-1)        1.194        0.069       51.294
2        1/(1-2)        1.022        0.039       43.399
3        1/(1-3)        0.695        0.069       70.227
4        1/(1-4)        0.367        0.050       48.984
5        1/(1-5)        0.677        0.080       65.684
6        1/(1-6)        0.637        0.087       86.766
7        1/(1-7)        0.520        0.085      257.087
8        1/(1-8)        0.293        0.116      344.710
9        1/(1-9)        3.835        0.010      135.950
10       1/(1-10)       3.667        0.030      238.160
1050     30/(4-5)       2.436        0.050       67.180

No.      Parameter symbol

       [N.sub.av] x   v (-)
       [M.subn.p]/N
        (m/s x N)

1         1.417       0.410
2         1.312       0.505
3         1.258       0.547
4         0.920       0.536
5         2.569       1.391
6         2.628       2.449
7         0.783       2.751
8         1.160       2.081
9         1.281       0.449
10        1.115       0.644
1050      0.735       0.298
COPYRIGHT 2013 Vilnius Gediminas Technical University
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2013 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Gorzelanczyk, Tomasz; Hola, Jerzy; Sadowski, Lukasz; Schabowicz, Krzysztof
Publication:Journal of Civil Engineering and Management
Article Type:Report
Geographic Code:4EXRU
Date:Dec 1, 2013
Words:5428
Previous Article:Erratum.
Next Article:Study on compressive bearing capacity of concrete-filled square steel tube column reinforced by circular steel tube inside.
Topics:

Terms of use | Privacy policy | Copyright © 2019 Farlex, Inc. | Feedback | For webmasters