5. Eyewash stations and bottles locations not properly marked--64.7% had eyewash stations or bottles that were not clearly marked with visible signs. Ref: OPNAVINST 5100.19E para B0508a

4. Potable water equipment painted blue -70.6% had potable water hose ends, caps, wrenches or risers that were not painted dark blue. Ref: NAVMED P-5010 para 6-19

3. Missing eyewash bottles--70.6% were missing eyewash bottles in nucleonics and near the secondary sample sink. Ref: OPNAVINST 5100.19E para B0508c

2. Potable water hose connections not properly marked--72.2% had potable water hose connections that were not marked with a warning sign (1 inch red letters) "CAUTION DISCONNECT HOSE WHEN NOT IN USE" Ref: NSTM 533 para 2.1.2

1. Vacuum breakers missing--83.3% had vacuum breakers (backflow preventers) missing from sinks or faucets with threaded hose connections. Ref: NSTM 533 para 2.3.5.1 and NAVMED P-5010 para 6-42.