Investigation of branchy track circuit parameters/Sakotosios toninio daznio begiu linijos parametru tyrimas.

Introduction

Track circuit is the main part of automation circuitry that is used to safeguard railroad traffic safety. The main function of a track circuit is to control the occupation of a railroad section. Lots of various types of track circuits are in use. Lithuanian railway system starting from beginning of electrical signalling until present day mostly uses track circuits of 50 Hz current signalling. Only at electrified sections frequency of signalling current is set to 25 Hz to safeguard receiver of track circuit from impact of 50 Hz power current [1, 2]. There are also track circuits that implement constant current to feed the track receiver and to control railroad section. Actually that is all the variety of track circuits implemented at Lithuanian railway system [8].

During the design of a track circuit the most important task is to find a correct set of track circuit feeder electric parameters:

* The feeder current must be high enough to ensure the relay-on state when controlled section is free (normal mode);

* In case the train is in controlled section (shunt mode) the feeder current must be low enough to ensure the relay-off state--the section is occupied state.

At this point to calculate optimal feeder voltage all the factors that can be significant (i.e. rail resistance, track circuit length, conductance of road ballast, frequency of signalling current etc.) have to be investigated.

Usually, when there are only a few track circuit types in use, the track circuit design rules and appropriate tables are prepared. They give information on different scheme electrical parameters and other necessary information that is important during the design of particular track circuit. This information saves designing time as no additional calculations have to be made. All the necessary information about electrical parameters is given in these tables partitioned by type of track circuit, length or count of branches in a section, length of separate sections, etc [4, 5, 9].

During the modernisation of Siauliai--Klaipeda railway sector new type of electronic track circuits were implemented. Those are type TRC3 audio frequency track circuits that utilise signalling current in one of the following frequencies: 420, 480, 580, 720 or 780 Hz. Additionally the signalling current of specific frequency is manipulated at 8 or 12 Hz frequency.

There is almost no literature on audio frequency track circuits or the processes that occur in track line at audio frequency. Also there are no tables prepared that may be helpful during the designing of these track circuits.

The novelty of the work lies in application of theoretical methods to analyse branchy track circuits type TRC3. The aim of the work is to investigate parameters of a branchy track circuit type TRC3 at normal operating conditions.

Track line is the only part of track circuit that has variable parameters. The parameters of track line describe or sets track circuit operating conditions. The main task of track line analysis is the calculation of track circuit feeder voltage. The first part of analysis is calculation of track line parameters at audio frequency. The second part is the investigation of impact of track line branches count and the length of separate sections on track circuit operating conditions.

Mathematical model of a branchy track line

Track line parameters of a track circuit can be calculated using simple theoretical electrotechnics formulas. However classic theory is limited to a simple task when the line analysed has no branches. Then track line is modelled using a quadripole model that has voltage and current inputs and outputs and their relation is described using quadripole coefficients.

The schematics of a branchy track line analysed is presented in Fig. 1.

[FIGURE 1 OMITTED]

To calculate parameters of a branchy track line presented in Fig. 1 we suggest forming a structure of quadripoles where each of the quadripoles represents section of track line between the shunt and line-end or between two shunts. The most complicated structure of a branchy track circuit is a three-branch structure. Modelling of such a structure leads to a five quadripoles combination, presented in Fig. 2.

[FIGURE 2 OMITTED]

Let us suppose that n is a quadripole sequence number. Then [I.sub.pn] and [U.sub.pn] is current and voltage of quadripole input respectively. [[bar.I].sub.gn] and [[bar.U].sub.gn] is quadripole output current and voltage respectively. [[bar.U].sub.p1] and [[bar.I].sub.p1] is voltage and current that is supplied to the track circuit by the feeder. Additional condition--branch marked by quadripole number 3 is the branch that has most distant relay-end from the feeder, even more distant than branches marked by quadripoles 4 and 5:

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (1)

here [l.sub.n]--length of non-branchy sections of track line.

The load of the quadripoles [Z.sub.A] is the resistance of relay-ended equipment. It is considered, that resistance of the load is linear and equal for each of the branches. The Fig. 2 layout is suitable to analyse normal mode or shunt mode of the track circuit. However as the mode changes, the coefficients of the quadripoles (line parameters) also change.

The aim of the task is to evaluate parameters of the track line when in normal mode and to calculate the lowest voltage [[bar.U].sub.p1] so that each of the road receivers at each of the branches is on. The second task is to investigate changes in voltages [[bar.U].sub.g4] and [[bar.U].sub.g5], or how high they are relative to [[bar.U].sub.g3].

In order to evaluate load [Z.sub.A], the lowest voltage [[bar.U].sub.g3] and corresponding current [[bar.I].sub.g3]is measured. Then using quadripole coefficients, load [Z.sub.A] and voltage [[bar.U].sub.g3], the feeder voltage [[bar.U].sub.p1] and current [[bar.I].sub.p1] can be described [3]:

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (2)

Quadripole coefficients in normal mode are calculated as described in classical theoretical electrotechnics:

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (3)

The coefficient of propagation [gamma] and undulatory resistance [Z.sub.b] is estimated at the length of track line according to track line isolation resistance [r.sub.i], resistivity of track line Z that is complex and is current frequency dependant. Z can be found at special tables, that presents experimental data for each type of rail.

Mathematical experiment

Investigation object is a three-branch track line that has separate sectors of given length: [l.sub.1]=40 m, [l.sub.2]=50 m, [l.sub.3]=100 m, [l.sub.4]=40 m, [l.sub.5]= 70 m. The results are presented in Table 1.

The results are very important during the setup of track circuit and checking its operation. Parameters n4 and n5 show how many times voltage at the beginning of the sector is higher related to the most distant end of the sector. These parameters are reference in designing of relay-end equipment--the smoothing transformers to equalise voltages at all road receivers at he same track circuit are selected according to it. Technically the coefficient of transformation is limited to n = 4.16 and this limits possible lengths of a branchy track line and also some other parameters.

The resistance of track line isolation [r.sub.i] also has influence on calculation results. In real life it changes: if there is higher humidity on rail ballast, the electrolytic conductance occurs and isolation resistance decreases. At the temperatures below 0[degrees]C electrolytic conductance is the lowest and thus [r.sub.i] is the highest. The branchy track circuits control sectors where train passes shunts. Shunts make train trajectory curvy and this causes that shunts are mostly contaminated by powdery products that crumbled out of the freight train. This causes all the conditions for electrolytic conductance to occur and decreases the isolation resistance [6, 7].

In order to investigate what influence track line isolation has on track circuit efficiency, the dependency of sector five and three relay-end voltage ratio on isolation resistance [r.sub.i] was analysed at all the frequencies that are implemented (Fig. 3).

[FIGURE 3 OMITTED]

Fig. 3 shows that at certain value of [r.sub.i] relay-end voltage ratio is too high ([n.sub.53]>4.16) to compensate it with smoothing transformer and the track circuit can not be tuned. At frequency of signaling current of [f.sub.sig] = 780 Hz the scheme can be tuned only when [r.sub.i]>0.0332 [OMEGA]*km. At normal conditions [r.sub.t] is never below 0.5 [OMEGA]*km, so it can be stated that audio frequency track circuit is resistant enough to [r.sub.i] changes and that track line resistance [r.sub.i] is not the main factor during investigation of audio frequency track circuit in normal mode.

[FIGURE 4 OMITTED]

It is clear that change in length of one of the track line sectors results in change of voltage at relay-end of track line. In order to evaluate impact of track sector length on voltage of most distant relay-end, the mathematical experiment was performed. The feeder voltage and sector lengths [l.sub.1], [l.sub.2] and [l.sub.3] were set constant. As the sector 5 length [l.sub.5] changes the voltage at relay-end [absolute value of [U.sub.g3]] was recalculated. The same was repeated with sector 4 and the results are presented in Fig. 4.

Experimental data can be approximated using the following polynomial (4):

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII] (4)

where [l.sub.4] = 0 ... 100, [l.sub.5] = 0 ... 100.

The results presented in Fig. 4 show what influence the sectors 4 and 5 length have on most distant relay-end voltage. The road receiver reacts more sensitively to a change of sector 5 length rather than sector 4 length. Also the presence of potentially dangerous length of sectors was discovered ([l.sub.4]=23m and [l.sub.5]=31m).

The voltage [absolute value of [U.sub.g3]] at relay-end of track line is stepped-up by transformer n=38 times. In this case [DELTA][absolute value of [U.sub.g3]] = 0.001 V gives 0.038 V deviation, which, in turn, equals 9.5% of relay operation voltage, that is 0.4 V. It appears that such a small change is significant for correct functioning of the circuit.

One more factor that may limit possibilities of scheme tuning is the ratio of voltages at sector endings (Fig. 5).

[FIGURE 5 OMITTED]

Fig. 5 shows that at sector 5 length l5<15 m ratio [n.sub.53] is more than 4.16 and in this case tuning of track circuit is not possible. Change in sector 4 length voltage ratios [n.sub.53] or [n.sub.43] do not achieve specified ratio at which tuning of track circuit is no longer possible. Critical parameters or critical track lengths can be specified in each particular case using the suggested analysis.

Conclusions

The analysis and results of presented system of equations dedicated to calculate parameters of track line with three branches allows concluding in following:

1 The results show that change in length of a branch nearer to the feeder results in higher influence on track circuit operation in normal mode. A critical length of a branch, nearest to the feeder, exists at which tuning of the track circuit becomes impossible (dependency on a branchiness).

2 The critical lengths of branches exist. In this case the most adverse conditions for normal mode occur.

3 The results show that in normal operating conditions, when [r.sub.i] is never below 0.5 [OMEGA]*km, there will never be such a condition when tuning of the circuit is impossible (dependency on isolation resistance).

Received 2009 03 30

References

[1.] Hill R. J., Coles P. C. A User-Friendly Simulator for Modelling Audio Frequency Track Circuit Operation // Railroad Conference.--Pittsburgh, PA, USA.--1993.--P. 77-86.

[2.] [TEXT NOT REPRODUCIBLE IN ASCII.], 1990.--P. 256.

[3.] Buinevicius V. A., Gargasas V. Gelezinkelio objektu diagnostika // Elektronika ir elektrotechnika.--Kaunas: Technologija, 2002.--Nr. 5(40).--P. 73-75.

[4.] Buinevicius V. A., Gargasas V. Gelezinkelio objektu bukles ivertinimas atsitiktiniu procesu klasifikavimo metodu // Elektronika ir elektrotechnika.--Kaunas: Technologija, 2003.--Nr. 4(46).-P. 83-86.

[5.] Buinevicius V. A., Gargasas V. Gelezinkelio begiu diagnostika naudojant geometrinius klasifikatorius // Elektronika ir elektrotechnika.--Kaunas: Technologija, 2004.--Nr. 4(53).-P. 86-89.

[6.] Magyla T., Bagdonas V. Application of the indistinct subjective criteria method for systems evaluation // [TEXT NOT REPRODUCIBLE IN ASCII.], 18 [TEXT NOT REPRODUCIBLE IN ASCII.] 2002 r. H. 1.--[TEXT NOT REPRODUCIBLE IN ASCII.], 2002.--ISBN 594633088X.--P. 22-28.

[7.] Povilaitiene I., Kamaitis Z., Podagelis I. Influence of gauge width on rail side wear on track curves // Journal of civil engineering and management.--Vilnius: Technika, 2006.--Vol. 12, No. 3.--P. 255-260.

[8.] Butkevicius J. Development of passenger transportation by railroad from Lithuania to European States // Transport.--Vilnius: Technika, 2007.--Vol. 22, No. 2.--P. 73-79.

[9.] Dailydka S., Lingaitis L. P., Myamlin S., Prichodko V. Modelling the interaction between railway wheel and rail // Transport.--Vilnius: Technika, 2008.--Vol. 23, No. 3.--P. 236-239.

V. Gargasas, A. Knys

Department of Control Technology, Kaunas University of Technology, Studentu str. 48-220, LT-51367 Kaunas, Lithuania, e-mail: vytautas.gargasas@ktu.lt
Table 1. Parameters of a branchy track line using audio
frequency track circuit

           [absolute   [absolute    [absolute
[f.sub.    value of    value of     value of
sig], Hz   p1], mV     g4], mV      g5], mV

420        140         42.5         60.4
480        156         43.9         63.5
580        184         46.3         68.2
720        229         49.5         74.5
780        248         50.7         77.0

[f.sub.
sig], Hz   [n.sub.4]   [n.sub.5]

420        1.42        2.01
480        1.47        2.12
580        1.54        2.27
720        1.65        2.48
780        1.69        2.57
COPYRIGHT 2009 Kaunas University of Technology, Faculty of Telecommunications and Electronics
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2009 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Title Annotation:AUTOMATION, ROBOTICS/AUTOMATIZAVIMAS, ROBOTECHNIKA
Author:Gargasas, V.; Knys, A.
Publication:Elektronika ir Elektrotechnika
Article Type:Report