Incidence of Corrosion on Electric Power Losses in ACSR Cables/Incidencia de la corrosion en las perdidas de energia electrica en cables ACSR.

1. Introduction

In electric power distribution network systems in the Colombian Atlantic coast we can find medium voltage (MV) lines of 13,200 and 34,500 Volts (V). These networks are currently constructed with aluminum (Al) [1] [4] wires with a steel core (ACSR)) [2] [5] [7]. Although in the past cables were made out of copper (Cu), these are no longer used due to their high costs and repeated theft.

Corrosion, a natural phenomenon and the main cause of metal deterioration [11] [15], occurs due to chemical or electrochemical reactions between an electrolytic environment and the material exposed to this environment or the electrical contact between two metal, one more noble than the other.

Colombia's Atlantic zone has problems with its electric networks; in part because it is quite close to the sea and because of high temperatures and relative humidity [2] [7], making them vulnerable to chemical attack due to the mixture of salt and water and/or the reaction of carbon dioxide with water [17] [18].

Companies dedicated to electric power transmission and distribution [19] [24], offering their services in Colombia's Atlantic zone, have shown greater interest in the corrosive effects on their ironwork and structures, given that saltpeter deteriorates metals until their rupture, causing surges and interruptions in the power distribution lines [25] [28].

The aim of this research was to learn of the incidence of corrosion upon electric power losses to study its behavior in saline environments. Thus, ACSR is the conductor studied herein (given that it is the one currently used), through a test bench that simulates an electric network exposed to a normal environment and to a saline environment to obtain results that help to delve into studying the phenomenon described and contributing in the search for solutions to problems caused by electric power losses.

2. Methods

The tests were conducted in two stages: The first consisted in subjecting the three ACSR conductors composed by aluminum wires (1350 H 19), with steel core covered by galvanized zinc, gauges No. 4, 2, and 1/0, lengths of 158, 112, and 83 cm, respectively, connected to a three-phase busbar (240 V / 120 V) of the protection panel of the Corporation for Corrosion Research (CIC, for the term in Spanish), whose electric power supply comes from the Piedecuesta municipal grid. Thereafter, the electric power consumption was measured at the source input and on the installed load, requiring a test bench--as security against electrical risk--for electrical connections where protection and measurement equipment are installed. Afterward, electric measurement instruments were implemented to check on the behavior of currents, voltage, and energy consumption.

It should be mentioned that the first stage is provided as control and reference test to compare the variables presented after the application of accelerated corrosion of the cables. The second phase replicated the previous procedure, adding the saline fog chamber (SFC) intervention to which a saline solution was poured composed of five parts of sodium chloride (NaCl) and 95 parts of type IV demineralized water and prepared according to ASTM B117 standard (chapter 8 --saline solution), under CIC supervision.

The samples (bare ACSR cable) were connected to each other, according to gauges via aluminum-aluminum connector and their loads with bimetallic connectors to permit closing the circuit and accomplishing the reading of parameters like amperage, voltage, and energy. The gauges of the samples exposed were number 4, 2, and 1/0; these were placed on plastic supports and separated to avoid short circuit and subjected during 337.5 h to the simulation of saline atmosphere and with drying times to accelerate the corrosion effects; during this period, the ACSR cable was energized and energy consumption was recorded in kilo watt-hour (kWh).

3. Results and Analysis

With SFC, uniform corrosion was reproduced, associated to a marine atmosphere in which corrosion factors, like temperatures of 35 [degrees], relative humidity at 100%, saline fog, and alternate humidification and drying cycles.

Also, considering the material with which the conductors are composed, it is pertinent to state that it is common for aluminum to present localized (pit type) and galvanic corrosion due to contact between aluminum and galvanized steel.

The marine-type atmospheric conditions reproduced by the SFC is charged with corrosive contaminating agents, like sodium chloride (NaCl); however, due to the SFC characteristics, it was not possible to replicate dust as another one of the contaminants that are part of a marine atmosphere. The spray pressure of the saline solution in mist form was of 12 psi.

3.1. Analysis of the corrosion tests process

Exposure of the cables in the saline fog chamber began on 26 March 2014 at 7:00 a.m. and culminated on 09 April 2014 at 8:30 a.m. The samples were exposed for a total of 337.5 hours (14 days + 1.5 h).

During the 337.5 h of operation, the chamber maintained a constant cycle in which it had two hours of drying from 8:00 to 10:00 a.m. and the saline spray from 10:00 a.m. to 8:00 a.m. of the following day (Fig. 1). These two hours of drying were carried out to diminish the permanence of the humidity film on the metallic surface and, thus, increase the rate of corrosion.

Figures 2 and 3 show, on the metallic surface of the samples, the layers of contaminants; in this case, NaCl residues and the presence of corrosion.

Upon terminating the exposure period, the specimen was dismounted from each of the gauges exposed and then, through scaling the corrosion products were eliminated. By taking the Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens (ASTM G1 standard), the mean rate of corrosion was obtained with the following equation:

R = [K x W]/[A x T x D] (1)

Where:

K: is a constant 8.76e04 (this value of the constant is used to have the results in millimeters per year (mm/p.a.)).

W: mass loss in grams

A: area in [cm.sup.2]

T: time of exposure in hours

D: density in g/cm[conjunction]3 (see appendix X1 ASTM G1).

The area of the #4 ACSR was 316.3279 [cm.sup.2]; its initial mass was 97.1934 g, and the final mass after scaling was 96.06 g; lastly, density was at 2.705 g/[cm.sup.3]. The mean rate of corrosion was 0.343802207 millimeters per year.

The gauge #2 ACSR showed an area of 282.8465959 [cm.sup.2], initial mass of 159.99 g, and final mass of 158.8 g. The rate of corrosion was 0.403700293 MPa. A = 265.2262063 [cm.sup.2], initial mass of 179.3887 g, final mass of 179.69 g, and for the #1/0 gauge the rate of corrosion was 0.976340343 MPa (Fig. 4). Small pits on the aluminum and degradation of the zinc film on the steel were observed via BX46 optical microscope (Figs. 5, 6, 7, and 8).

3.2. Analysis of the energizing test process

Within the use of the correlation, the criteria shown in Table 1 were selected to determine if the test was satisfactory. This was done to verify a linear association between two variables.

The relationship of voltage with respect to current during the tests conducted with load could be observed; by correlating these two factors, an average correlation of 0.99 (0.997585893) and a standard deviation of 0.002 (0.002122663) was obtained, indicating that the test complies with the relationships that can be attributed to the electric variables in question. When comparing between input and output voltage for each phase, the results presented in Fig. 9 were obtained.

According to Table 7, an excellent degree of agreement exists among the voltages registered for each of the three phases, which ranged from a correlation coefficient of 0.998 to 1.

It is important to indicate that for day 02 April, the measurements evidenced a registry of the three phases, which were close to coinciding: Va 0.9998, Vb 0.9997, and Vc 0.9997.

This event may be explained because: for the date the measurement was registered no voltage fluctuation was noted; also, the loads applied to the three phases were basically resistive elements. Consequently, no difference was observed between input and output voltage, which guaranteed the stability of the test in question on voltage registry and control. Similarly, it was established that the only variable in the system is associated to electric power consumption and the variables inherent to the behavior of the electric elements.

Likewise, the input and output currents were measured and compared (Fig. 10) to minimize the variables that can affect the analysis of the test results. Until now, the tests agree with the expectations, but the input voltage is not equal to the output voltage, as with the current. Even so, a variable can explain what occurs in the system, the input voltage, and the output voltage. For this purpose, we take the actual voltage value recorded for the three phases at the input and output; the input voltage corresponds to the voltage provided by the grid, and the output voltage is that delivered to the load (Fig. 11).

To assess the evolution of conductors within the system, voltage, current, and power values are taken during several days of the test around one hour of continuous charge. This difference of the power value presented in a power average for each day, as well as a standard deviation of the results, is shown in Fig. 12, evidencing an average loss in the system. It may be stated that the resistance in the system is determined by the division between the system's voltage and current (Fig. 13).

Given the continuity of the test, during days 07/04/2014 and 08/04/2014 the slope is calculated during one hour every 5 min to contemplate the evolution of the slope and the cut-off point during these two days. The equation of resistance in the system, where "r" represents the system's resistance "per unit", ([R.sub.sist]) is the constant resistance value that represents the system, and "mr" represents the slope that controls the system's total resistance variation over time:

r = [R.sub.sist] + mr x t (2)

By analyzing the data "per unit", the evolution of slope (mr), which is calculated with Equation 3 and its tendency over time, evidenced in Figures 14, 15, and 16 with domain from 0 to 1800 every 5 min, would yield an estimate of the affectation of the material as time passes.

b = [summation](x - [bar.x])(y - [bar.y])/[summation][(x - [bar.x]).sup.2] (3)

4. Conclusions

The samples, after having been subjected to corrosion during the 337.5 h, did not show major surface damage, according to that registered through the Olympus BX46 microscope. This could be attributed to the alumina layer generated when aluminum comes in contact with an oxidizing medium, like oxygen and water. It is worth mentioning that galvanized steel, which is part of the ACSR, did show important surface deterioration because the zinc layer used as corrosion protector was affected. Without this zinc layer and with more hours of exposure to the saline fog, it is likely that due to the effect of the galvanic couple between the aluminum and the steel, the steel corrodes at a higher rate.

The input and output voltage, as well as the input and output current, had excellent correlation; this means that although the values were not equal, their deviations were not sufficiently significant to alter the tests.

Regarding the general aim of this work, no clear evidence indicates that, in this test, corrosion affects electric power losses, probably due to the time the specimen was energized in non-continuous manner during the two weeks the samples were exposed.

Also, not having a daily resistance record sheds doubt on whether the phenomenon observed through the graphics with respect to the resistance slope calculated "per unit" is sufficiently consistent to be attributed as characteristic of corrosion damage, given that electric power losses are directly related to conductor resistance, in this case the ACSR cable.

It is fundamental to ensure prolonged exposure times of the samples in the saline fog chamber, not below 720 h, to obtain samples with a higher degree of representativeness of the corrosion phenomenon as a factor of incidence in the electric power losses.

High-resolution scanning electron microscopy (SEM) was used to obtain more detailed information of the layer formed by the corrosion products, given that the pits and fissures on the material are often too small for the BX45 microscope to register.

Given that the tests performed for this research work used high-gauge cables that withstand at least 140 amps, we may implement one of the wires that make up the aluminum cable with steel core to analyze the incidence of the corrosion phenomenon and the electric power losses in areas with lesser surface through where current can cross. Likewise, the nominal current capacity may be delivered to one of the previously mentioned wires to increase its temperature.

Electric power measuring equipment should be used with one more degree of precision than that used in this experiment to lower the margin of error while measuring.

During the 1-h period when drying takes place of the SFC exposure cycle, a daily record of the sample's resistance could be taken to determine its variation and correlate it to the electric power loss phenomenon.

DOI: http://dx.doi.org/10.18180/tecciencia.2016.20.4

References

[1] MARTIN PIRIS, Nuria y BADIA PEREZ, Jose Maria. Comportamiento en servicio de los materiales metalicos. In: GUEMES GORDO, Alfredo y MARTIN PIRIS, Nuria. Ciencia de materiales para ingenieros. Madrid: Pearson, 2012. p. 243-259.

[2] LINARES PEREZ, Lizeth Maria. Evaluacion de la corrosividad atmosferica y su efecto en los cables de transmision Electrica A 400 Kv de CVG EDELCA. Tesis de Magister scientiarum en corrosion. Maracaibo: Universidad del Zulia. Division de postgrado de la Facultad de Ingenieria, 2007. 134. p.

[3] LAVERDE LAVERDE, Victor Hugo. Diseno y fabricacion de una maquina salina para realizar analisis de corrosion en materiales. Tesis de grado Ingeniero Macarronico. Bogota: Universidad Nacional de Colombia. Facultad de Ingenieria. 131. p.

[4] ROMERO ECHETO, Natalie Maria. Fundamento teorico. In: Evaluacion de recubrimientos expuestos a ambientes marinos y costeros marinos. Tesis de Magister scientiarum en corrosion. Maracaibo: Universidad del Zulia. Division de postgrado de la Facultad de Ingenieria, 2004. p. 31-76.

[5] SURAL. Conductores de Aluminio Desnudos. {On line}. {11 September 2013}. Available in: (http://www.sural.com/productos/desnudos/acsr.htm).

[6] CORMON. Overhead line corrosion detector. {On line}. {11 September 2013}. Available in: (http://www.cormon.com/products/datasheets%5Cptp002.pdf).

[7] CALITZ, JACQUES. Overhead conductor corrosion study. Tesis de Magister technologies engineering metallurgical. Tshwane: Tshwane University of Technology. Faculty of Engineering, 2004. 196. p.

[8] GALLEGOS C, Ramiro. El Cobre (Copper). In: Revista VIRTUALPRO. No 56 (Sept, 2006); p. 5.

[9] CENTRO ESPANOL DE INFORMACION DEL COBRE. El Cobre. {On line}. {11 September 2013}. Available in: (http://www.copperalliance.es/el-cobre/propiedades).

[10] INGEMECANICA. Propiedades mecanico-quimicas del cobre tutorial No 112. {On line}. {11 September 2013}. Available in: (http://ingemecanica.com/tutorialsemanal/tutorialn112.html#seccion5).

[11] REVIE, R. Winston y UHLIG, Herbert H. Definition and importance of corrosion. In: Corrosion and corrosion control. 4ed. New Jersey: John Wiley, 2008. p. 1-6.

[12] ROBERGE, Pierre R. Environments. In: Handbook of Corrosion Engineering. New York: MacGraw-Hill, 2000.p. 58-59.

[13] MARTIN PIRIS, Nuria y BADIA PEREZ, Jose Maria. Comportamiento en servicio de los materiales metalicos. In: GUEMES GORDO, Alfredo y MARTIN PIRIS, Nuria. Ciencia de materiales para ingenieros. Madrid: Pearson, 2012. p. 243-259.

[14] MOTT, Robert L. Propiedades de diseno de materiales. In: Resistencia de materiales. 5 ed. Mexico: Pearson, 2009. p. 53-103.

[15] GRAINGER, John J y STEVENSON, William D. Impedancia serie de lineas de transmision. In: Analisis de sistemas de potencia. Mexico: McGraw-Hill, 1996. p. 131-155.

[16] ROBERGE, Pierre R. Corrosion failures. In: Handbook of Corrosion Engineering. New York: MacGraw-Hill, 2000.p. 332-368.

[17] REVIE, R. Winston and UHLIG, Herbert H. Atmospheric corrosion. In: Corrosion and corrosion control. 4ed. New Jersey: John Wiley, 2008. p. 191-202.

[18] DIAZ RODRIGUEZ, Francisco Miguel. Introduccion. In: Estudio de la corrosion atmosferica del cinc y el acero galvanizado. Tesis Doctoral en Quimica. Tenerife: Universidad de La Laguna. Departamento de Quimica Fisica, 2001. p. 2-26.

[19] MEDINA Z, Jose Gregorio y RIVAS B, Fernando Alberto. Analisis de perdidas tecnicas y no tecnicas a nivel de 13,8kV/ (240-120) V en el circuito Coro 1 ubicado en el Estado Falcon (caso: CADAFE). Trabajo de grado Ingeniero Electricista. Valencia: Universidad de Carabobo. Faculta de Ingenieria, 2008. 129 p. {On line}. {11 September 2013}. Available in: (http://www.riuc.bc.uc.edu.ve/bitstream/123456789/5271/10891.pdf).

[20] ORDONEZ SANCLEMENTE, Jorge P. y NIETO ALVARADO, Leonardo G. Mantenimiento de sistemas electricos de distribucion. Proyecto de grado Ingeniero Electrico. Guayaquil: Universidad Politecnica Salesiana. Facultad de Ingenierias. Carrera de ingenieria electrica, 2010. 101 p. {On line}. {Sept. 2013}. Available in: (http://dspace.ups.edu.ec/bitstream/123456789/2119/15/UPS-GT000156.pdf).

[21] HERRERA LEON, Fernando Augusto y FORERO CARO, Luis Miguel. Perdidas de energia en el sistema de distribucion caso Colombia. Informe Ejecutivo. Bogota, D.C.,: International Copper Association--Procobre, 2008. 18 p. {On line} {Aug 2013}Available in: (https://www.google.com.co/url?sa=t&rct=j&q=&esrc=s&source=web&c d=1&ved=0CCwQFjAA&url=http%3A%2F%2Fprocobre.org%2Fes%2F wp-content%2Fplugins%2Fdownload- monitor%2Fdownload.php%3Fid%3D178&ei=qyY3UvW7Goqu9ATrpID gDg&usg=AFQj CNEAXpPpQiXcA8LN- 3ZgB6qNJypZ_A&sig2=DgSplCSLQXQ8dN9SPFYMkg&bvm=bv.5216 4340,d.eWU).

[22] COLOMBIA. MINISTERIO DE MINAS Y ENERGIA. Resolucion 070 (28, mayo, 1998). Por el cual se establece el reglamento de distribucion de potencia electrica, como parte del reglamento de operacion del sistema interconectado nacional. Bogota, D.C.,: El Ministerio, 1998. 63 p.

[23] COLOMBIA. MINISTERIO DE MINAS Y ENERGIA. Resolucion 18 1294 (06, agosto, 2008). Reglamento tecnico de instalaciones electricas (RETIE). Bogota, D.C.,: El Ministerio, 2008. 164 p.

[24] MOLINA, Juan David. VILLADA, Fernando. MESA, Noe. La Corrosion Atmosferica En Sistemas De Transporte De Potencia Electrica: Modelo De Vida Util Y Su Remuneracion En Colombia. In: Revista Facultad de Ingenieria Universidad de Antioquia. Junio, 2011, no. 59, p. 257-266. {On line}. {17 July 2013}. Available in: (http://aprendeenlinea.udea.edu.co/revistas/index.php/ingenieria/article/vi ewArticle/13830).

[25] GONZALEZ SOUBLETT, Edraz Urvisaely. Estudio de perdidas de potencia electrica en sistemas de distribucion usuarios alto consumo ubicados en el casco central de Puerto la Cruz estado Anzoategui. Trabajo de grado Ingeniero Electricista. Barcelona: Universidad de Oriente nucleo de Anzoategui. Escuela de ingenieria y Ciencias aplicadas, 2010. 168 p. {On line}. {Sep. 2013}. Available in: (http://ri.biblioteca.udo.edu.ve/bitstream/123456789/3112/1/07-TESIS.IE010G33.pdf).

[26] CANAR OLMEDO, Santiago Patricio. Calculo detallado de perdidas en sistemas electricos de distribucion aplicado al alimentador Universidad perteneciente a la empresa electrica Ambato regional centro norte S.A. Tesis de grado Ingeniero Electrico. Quito: Escuela Politecnica Nacional. Facultad de Ingenieria Electrica y Electronica, 2007. 213 p. {On line}. {11 September 2013}. Available in: (http://bibdigital.epn.edu.ec/bitstream/15000/4217/1/CD-0926.pdf).

[27] VAZQUES GRANDA, Paul Marcelo. Parametrizacion, control, determinacion y reduccion de perdidas de energia en base a la optimizacion en el montaje de estaciones de transformacion en la provincia de Morona Santiago. Tesis Magister en sistemas electricos de potencia. Cuenca: Universidad de Cuenca. Faculta de Ingenieria, 2013. 107 p. {On line}. {11 September 2013}. Available in: (http://dspace.ucuenca.edu.ec/bitstream/123456789/423/1/Tesis.pdf).

[28] CHICO, B., DE LA SOURCE, D. y MORCILLO, M. simulacion en laboratorio mediante ensayos de corrosion acelerada de la presencia y contenido en sales solubles en los productos de corrosion atmosferica del acero. In: Revista de metalurgia. 12005, vol. 41 no. extra, p. 438-442. {On line}. {17 July 2013}. Available in: (http://revistademetalurgia.revistas.csic.es/index.php/revistademetalurgia/i ssue/view/97).

Carlos G. Cardenas (1) *, Oscar M. Pardo (1), Edward Barajas (1) y Alfonso Santos (2)

(1) Ingenieria Electromecanica, Universidad Antonio Narino, Bucaramanga, Colombia

(2) Ingenieria Electromecanica, Universidad Pontificia Bolivariana, Bucaramanga, Colombia

Received: 1 Dec 2015

Accepted: 24 Jan 2016

Available Online: 29 Feb 2016

* Corresponding Author.

E-mail: carloscarde@uan.edu.co

Caption: Figure 1 Exposure cycles.

Caption: Figure 2 Specimen after 337.5 h of exposure to the saline fog.

Caption: Figure 3 Samples after 337.5 h of exposure to saline fog.

Caption: Figure 5. Aluminum before entering the SFC

Caption: Figure 6. Aluminum after exiting the SFC

Caption: Figure 7. Steel core before exposure to the saline fog

Caption: Figure 8. Steel core after exposure to the saline fog

Caption: Figure 9 Input vs. output voltage correlation

Caption: Figure 10 Input vs. output current correlation

Caption: Figure 11 Power distribution

Caption: Figure 14 "mr" slope distribution of the A phase.

Caption: Figure 15 "mr" slope distribution of the B phase.

Caption: Figure 16 "mr" slope distribution of the C phase
Table 1 Degree of agreement for the correlation in the test

 Correlation
 coefficient     Degree of agreement

      0                 Null
    <0.40           No agreement
  0.40-0.60      Moderate agreement
  0.60-0.75       Regular agreement
  0.75-0.85        Good agreement
   0.85-1        Excellent agreement

Figure 4 Average rate of corrosion

                        ACSR 1/0        ACSR 2         ACSR 4

Tasa de corrosion     0,976340343    0,403700293    0,343802207

Note: Table made from bar graph.
COPYRIGHT 2016 Escuela Colombiana De Carreras Industriales
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2016 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Cardenas, Carlos G.; Pardo, Oscar M.; Barajas, Edward; Santos, Alfonso
Publication:Tecciencia
Date:Jun 1, 2016
Words:3577
Previous Article:Triad of the Articulation Model of Integrated Management Systems [TAM--(HSEQ)]/Triada del modelo de articulacion de sistemas integrados de gestion...
Next Article:Study of the internal structure of long GRBs with similar redshift/Estudio de la estructura interna de GRB largos con corrimiento al rojo similar.
Topics:

Terms of use | Privacy policy | Copyright © 2021 Farlex, Inc. | Feedback | For webmasters |