High-Glide Refrigerant Blends & System Retrofits.

Most of these blends are viable replacements for R-22, R-404A, and similar refrigerants, but have properties that require careful consideration to ensure a successful retrofit. This article is Part 1 of a three-part series addressing such retrofits, and deals with the basics of refrigerant blends and temperature glide.

Superheat and Subcooling of Refrigerant Blends

The refrigeration industry has been using refrigerant blends for many years. Some of these are azeotropic, in which the blend constituents form a mixture that changes phase at a constant temperature at a given pressure. This is the same behavior as a pure refrigerant, made up of only one type of molecule. In the evaporator, as the refrigerant boils off from a saturated liquid to a saturated vapor, no sensible heat is gained by the refrigerant until it is 100% vapor.

This is a desirable characteristic for most refrigeration systems. Pure refrigerants and azeotropes have a single saturation temperature at a given pressure. Superheat and subcooling are simply calculated from this single-point relationship. Azeotropic blends are assigned ASHRAE R-numbers in the 500-series, such as R-502 or R-507.

Other blends are zeotropic, in which the blend constituents change temperature with change of phase at constant pressure. This behavior is commonly called temperature glide. As a zeotrope boils off in the evaporator, the constituent with the highest vapor pressure will evaporate first. While the first constituent is evaporating, the remainder of the constituents are gaining sensible heat. As the temperature of the refrigerant increases, the vapor pressure of the next constituent will then be reached and it will evaporate, while the remaining constituents (including those already evaporated) will continue to gain sensible heat.

This will continue for all constituents, until all are boiled off. At a constant pressure, the saturated vapor of the blend will be at a higher temperature than the saturated liquid, thus the term "temperature glide." This also means that at a given pressure, there are now two saturation temperatures to consider: saturated liquid temperature (also known as bubble point) and saturated vapor temperature (also known as dew point).

Because of this behavior, superheat and subcooling for zeotropes must be calculated using the proper point. Zeotropic blends are assigned R-numbers in the 400-series, such as R-404A, R-407C, R-410A, etc.

Because having little or no glide is favorable for heat exchanger design, zeotropes with low glide have been more widely used in the past. In the case of blends such as R-404A or R-408A that have only around 1[degrees]F (0.6[degrees]C) temperature glide, there is very little effect on heat exchanger performance. Even ignoring glide introduces only a small error into superheat and subcooling calculation. With the current movement toward more environment-friendly refrigerants, many blends with significantly higher temperature glide (on the order of 10[degrees]F [6[degrees]C]) are commonly being used, and more are being introduced to the market. These include but are not limited to R-407A, R-407C, R-407F, R-448A, and R-449A. With high-glide zeotropic refrigerants, care must be taken to use bubble point to calculate subcooling, and dew point to calculate superheat.

Figure 1 shows saturation pressure temperature relationships for R-507 (an azeotrope), R-404A (a low-glide zeotrope) and R-407A (a high-glide zeotrope). (3) This is a useful way to visualize temperature glide, and some of the differences between these refrigerant types. The focus is on typical medium-temperature refrigeration evaporator range, from 10[degrees]F to 30[degrees]F (-12[degrees]C to -1[degrees]C).

On this plot, temperature glide is the horizontal distance (meaning at fixed pressure) between the bubble point and dew-point lines of the zeotropic blends. Azeotropic R-507 has a single saturation line, and has no glide. R-404A has just over 1[degrees]F (0.6[degrees]C) glide, while R-407A has over 10[degrees]F (6[degrees]C) temperature glide.

Temperature Glide and the Pressure-Enthalpy Diagram

Temperature glide and subcooling and superheat calculations can also be visualized on a pressure-enthalpy (p-h) diagram. Figure 2 is a p-h diagram for R-407A generated by

NIST REFPROP, (3) and illustrates the refrigeration cycle and proper calculations for a high-glide refrigerant. An idealized cycle is illustrated, with no high- or low-side pressure drops. This simplifies the example calculations, but pressure drops in a real system should be accounted for by using temperatures and pressures measured in close proximity to calculate superheat and subcooling.

As with all p-h diagrams, the liquid saturation line forms the left side of the saturation dome, and the vapor saturation line forms the right side of the dome. The lines of constant temperature (or isotherms) slope downward left-to-right in the saturated region, showing that R-407A is a zeotrope, having temperature glide. For a pure refrigerant or azeotrope, these lines would have no slope: no change in temperature at a given pressure during phase change. Subcooling and superheat are always calculated from the nearest saturation state.

In Figure 2's example, an R-407A refrigeration system is operating at medium-temperature conditions. The measured high- and low-side system absolute pressures are [P.sub.high] = 252 psi (1737 kPa) and [P.sub.low] = 57 psi (393 kPa). Using the proper saturation states:

Liquid Subcooling Calculation:

Measured liquid line temperature: 80[degrees]F (27[degrees]C) From NIST REFPROP, R-407A bubble point at 252 psi (1737 kPa): 100[degrees]F (38[degrees]C)

Liquid subcooling:

100[degrees]F-80[degrees]F=20[degrees]F (38[degrees]C - 27[degrees]C = 11[degrees]C)

Suction Superheat Calculation:

Measured suction gas into the compressor:

65[degrees]F (18[degrees]C)

From NIST REFPROP, R-407A dew point at

57 psi (393 kPa): 20[degrees]F (-7[degrees]C)

Suction superheat:

65[degrees]F - 20[degrees]F = 45[degrees]F [18[degrees]C - (-7[degrees]C) = 25[degrees]F]

Discharge Superheat Calculation:

Measured compressor discharge gas: 165[degrees]F

(74[degrees]C)

From NIST REFPROP, R-407A dew point at 252 psia (1737 kPa): 108[degrees]F (42[degrees]C)

Discharge superheat:

165[degrees]F - 108[degrees]F = 57[degrees]F (74[degrees]C - 42[degrees]C = 32[degrees]C)

The calculated numbers can be checked with the p-h diagram by scaling them with the isotherms. In the case of liquid subcooling, that process extends from the bubble point, leftward into the subcooled liquid region. It extends from the 100[degrees]F (38[degrees]C) isotherm to the 80[degrees]F (27[degrees]F) isotherm, confirming our calculation of 20[degrees]F (11[degrees]C) subcooling.

To show the effect of using the incorrect saturation state, consider Suction Superheat calculated using bubble point:

Measured suction gas into the compressor:

65[degrees]F (18[degrees]C)

From NIST REFPROP, R-407A bubble point at 57 psia (393 kPa): 10[degrees]F (-12[degrees]C)

Suction Superheat:

65[degrees]F - 10[degrees]F = 55[degrees]F [18[degrees]C - (-12[degrees]C) = 30[degrees]C]

An additional 10[degrees]F (6[degrees]C) superheat would be calculated that does not actually exist. This amount of error in calculating superheat at the outlet of an evaporator coil would lead to an improperly adjusted TEV and liquid flooding in the suction line, possibly all the way back to the compressor. We also readily see this is incorrect by checking our calculation against the p-h diagram--the closest saturation state is dew point, not bubble point.

Superheat Control with Glide

The thermostatic expansion valve (TEV) has only one function in the system: to meter the proper amount of refrigerant to the evaporator coil by controlling superheat at the bulb location. To do this, the TEV is located at the coil inlet. However, conditions at the coil outlet indicate whether the TEV is working properly. For zeotropic refrigerants, superheat is calculated based on dew point, the closest saturation condition at the evaporator outlet. It follows naturally that superheat is also controlled based on this condition. This means the vapor pressure or dew point of the refrigerant is used to control the TEV. Following is a diagram and explanation of the fundamental operation of TEVs. (4)

To understand the principles of thermostatic expansion valve operation, a review of its major components is necessary. A sensing bulb is connected to the TEV by a length of capillary tubing, which transmits bulb pressure to the top of the valve's diaphragm. The sensing bulb, capillary tubing, and diaphragm assembly is referred to as the thermostatic element. The thermostatic element on many TEVs is replaceable.

The diaphragm is the actuating member of the valve. Its motion is transmitted to the pin and pin carrier assembly by means of one or two pushrods, allowing the pin to move in and out of the valve port. The superheat spring is located under the pin carrier, and a spring guide sets it in place. On externally adjustable valves, an external valve adjustment permits the spring pressure to be altered.

There are three fundamental pressures acting on the valve's diaphragm, which affect its operation: sensing bulb pressure [P.sub.1], equalizer pressure [P.sub.2], and equivalent spring pressure [P.sub.3] (see Figure 3). The sensing bulb pressure is a function of the temperature of the thermostatic charge, i.e., the substance within the bulb. This pressure acts on the top of the valve diaphragm, causing the valve to move to a more open position. The equalizer and spring pressures act together underneath the diaphragm causing the valve to move to a more closed position. During normal valve operation, the sensing bulb pressure must equal the equalizer pressure plus the spring pressure, i.e.:

[P.sub.1] = [P.sub.2] + [P.sub.3]

Equivalent spring pressure is defined as the spring force divided by the effective area of the diaphragm. The effective area of the diaphragm is simply the portion of the total diaphragm area that is effectively used by the bulb and equalizer pressures to provide their respective opening and closing forces. Equivalent spring pressure is essentially constant once the valve has been adjusted to the desired superheat. As a result, the TEV functions by controlling the difference between bulb and equalizer pressures by the amount of the spring pressure.

Based on the characteristics of high-glide zeotropic blends, we see that the evaporator pressure referred to is in fact vapor pressure or dew point. Considering the three pressures acting on a TEV, [P.sub.1] (bulb pressure) and [P.sub.2] (vapor pressure) are acting on opposite sides of the same diaphragm. TEVs are designed for these two pressures to be very close to one another. These will then be the fundamental forces acting to position the pin in the port, producing the best superheat response.

Since each of these two similar pressures is acting on the same area, only a small amount of additional force (via spring pressure, P3) is needed to fine-tune the balance through adjustment. This is illustrated in Figure 3 by the small size of P3 in comparison to the other two forces. The stroke of the valve is relatively very small, and the force the spring needs to provide is very small, so the spring constant is low. The adjustment assembly is typically designed to provide 8 to 12 full rotations from minimum to maximum design spring force. This allows for virtually infinite tuning, but only within the design range of the spring. It follows that the thermostatic element charge should be designed to be close to the vapor pressure (dew point) of a zeotropic refrigerant to provide the best TEV performance.

What if the thermostatic element charge is significantly lower in pressure than the vapor pressure at the evaporator outlet?

The opening force on the TEV will be very low, and the closing forces will keep the pin and port closed until the bulb gets much warmer, resulting in inadequate refrigerant feed to the evaporator and high superheat. Adjusting spring pressure lower will help compensate by balancing the forces at a more open position.

If evaporator outlet pressure is too much higher, even removing all spring pressure may not be sufficient. The TEV will be operating outside its design parameters, desired superheat may not be obtained, and the evaporator will be fed too little refrigerant for its load.

What if the thermostatic element charge is significantly higher in pressure than the vapor pressure at the evaporator outlet?

The opening force on the TEV will be very high, moving the pin and port more open, and flooding will occur.

Adjusting spring pressure higher will help compensate by balancing the forces at a less open position.

However, if too much additional spring pressure is needed, maximum design spring force may be reached, beyond which the valve will be operating outside its design parameters.

Proper superheat adjustment may not be possible, and superheat response will be compromised. Liquid flood back may occur, particularly at high condensing pressure conditions. TEVs, like most control systems, tend to operate best in the middle portion of their design range.

Part 2 of this series will address TEV thermostatic charges and capacity of some of the alternate refrigerants, and compare sizing and selection of liquid line components for system retrofits.

BY JOHN WITHOUSE, MEMBER ASHRAE

References

(1.) EPA. 2015. "Protection of stratospheric ozone: Change of listing status for certain substitutes under the Significant New Alternatives Policy Program; Final Rule." Federal Register 80(138):42872. U.S. Environmental Protection Agency. http://tinyurl.com/jxsmh9s.

(2.) EPA. 2015. "Pennsylvania-1997 Annual [PM.sub.2.5] NAAQS-Continued." Federal Register 80(136):42053. U.S. Environmental Protection Agency. http://tinyurl.com/hbvu5zb.

(3.) U.S. Secretary of Commerce. 2013. "NIST Standard Reference Database 23: NIST Reference Fluid Thermodynamic and Transport Properties Database (REFPROP): Version 9.1." http://www.nist.gov/ srd/nist23.cfm.

(4.) Sporlan Division, Parker-Hannifin Corp. 2011. "Bulletin 10-9 Thermostatic Expansion Valves: Theory of Operation, Application, and Selection," p. 3-4. http://tinyurl.com/jyo2l9f.

John Withouse is a senior principal engineer at Sporlan Division of Parker-Hannifin in Washington, Mo.

Caption: FIGURE 1 Saturation pressure temperature relationships for R-507 (an azeotrope), R-404A (a low-glide zeotrope) and R-407A (a high-glide zeotrope).

Caption: FIGURE 2 p-h diagram for R-407A with an example cycle.

Caption: FIGURE 3 Fundamental forces acting on the thermal expansion valve.
COPYRIGHT 2016 American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE)
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2016 Gale, Cengage Learning. All rights reserved.

 
Article Details
Printer friendly Cite/link Email Feedback
Title Annotation:Part One
Author:Withouse, John
Publication:ASHRAE Journal
Date:Nov 1, 2016
Words:2355
Previous Article:Improving Commercial Building Energy Performance.
Next Article:Energy Performance Comparison of Fans with Variable Speed Drives.
Topics:

Terms of use | Privacy policy | Copyright © 2018 Farlex, Inc. | Feedback | For webmasters