1250-3500 VA Rating

HPI Series

Specifications

* Power--1250,1500, 1750, 2000, 2750, 3500 VA ratings

* Dielectric Strength-4.0Kv

* Available Input Voltage--100V, 115V, 215V, 230V, 50/60HZ

* Output Voltage--115/230V

Design Features

* Flammability Rating--UL 94-V0

* Constructed to meet UL 60601-1

* Agency Certified UL, CSA, VDE and TUV

* Leakage Current @ <50 micro Amps

* Touch Safe Terminals (IP20 Type)

RoHS Compliant

[ILLUSTRATION OMITTED]

Description:

The HPI series is constructed on a concentric platform, Signal's HPI series provides reinforced insulation while maintaining superior volumetric efficiency. Easily modified to your exact application. Available in 6 power ratings.

How To Order

www.signaltransformer.com

sales@signaltransformer.com or call 866 239-5777

              VA     Secondary RMS Rating       Mechanicals

Part number  Size     Series       Parallel        Length

HPI-25 *     1250  230V @ 5.4V   115V @ 10.9A   7.06 (179.3)

HPI-15 *     1500  230V @ 6.5A   115V @ 13.0A   7.06 (179.3)

HPI-17 *     1750  230V @ 7.6V   115V @ 15.2A    7.06(179.3

HPI-20       2000  230V @ 8.7A    115V @ 17AA   7.50 (190.5)

HPI-27       2750  230V @ 12.0V  115V @ 24.0A   7.50 (190.5)

HPI-35       3500  230V @ 15.2A  115V @ 30.4A   7.50 (190.5)

                   Mechanicals

Part number     Width         Height       RoHS        Weight
                                         Compliant

HPI-25 *     5.1 (129.6)   6.10 (154.9)     Yes     31.0 (14.07)

HPI-15 *     5.5 (139.7)   6.10 (154.9)     Yes     35.75 (16.23)

HPI-17 *     5.89 (149.7)  6.10 (154.9)     Yes     38.50 (17.50)

HPI-20       5.26 (133.7)  6.56 (166.5)     Yes     40.1 (18.16)

HPI-27       5.89 (149.7)  6.56 (166.51     Yes     48.0 (21.77)

HPI-35       6.99 (177.6)  6.56 (166.5)     Yes     62.4 (28.30)

Modification to standard parts and customs design available on reques.
Consult our customer service center to discuss your specific
application.

Electrical schematics, mechanical outlines and data sheets available on
www.signaltransformer.com

* All models have UL, CSA, TUV and VDE agency approvals except those
marked with * which have TUV instead of VDE. To learn more about our
agengy certification advantage visit our website

Technical Support

Technical Support: Signal's staff of application and design engineers is one of the largest in the industry. Their extensive knowledge of regulatory and safety agency requirements insures expeditious handling of complex certification issues. Using the latest SPICE and CAD/CAM software, the Signal team stands ready to respond quickly to your unique, design and application needs.

Signal Transformer maintains an in-house ISO 17025 certified laboratory that enables us to participate in CSA's "Shared Manufacturer Testing & Certification" (SMTC) This program makes it possible to certify and use the CSA/cCSAus mark on new designs within days.

Contact us for your next wire wound magnetic application--we can help! techhelp@signaltransforme.com

COPYRIGHT 2010 Advantage Business Media
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2010 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Title Annotation:Signal Transformer
Publication:ECN-Electronic Component News
Date:Jun 1, 2010
Words:452
Previous Article:Super High Efficiency SHE series.
Next Article:Multi purpose international MPI series.

Terms of use | Privacy policy | Copyright © 2020 Farlex, Inc. | Feedback | For webmasters