Analysis of hysteretic response of glass infilled wooden frames.

Introduction

Use of glass as a structural material has received considerable interest over the past decade, which is reflected in development of the new generation of structural codes (Zarnic et al. 2007). In the majority of modern earthquake resistant building design codes, glass facades in buildings are considered as non-structural elements, despite the fact that the term "structural glass" is usually referred to the glass facades. Considering the relative novelty of structural use of glass, several research directions are still open. In particular, novel structural components composed of structural glass and other contemporary materials need to be developed in order to facilitate the use of these materials in buildings.

Building experiences story drifts during an earthquake, which can result in development of serious damage to the glazing when it is not properly designed. In order to mitigate the damage of non-structural elements, the story drifts need to be limited which can be achieved by the adequate design (and execution) of the building's structural components. The inter-story drift limits as defined in the Eurocode 8 (2004) depend on the type and behaviour of non-structural elements (i.e. glass facade), and are categorized into three groups. The most rigorous drift limit requirement is set for brittle materials attached to the main structure (0.5% of the story height), while for the ductile non-structural elements it is limited to 0.75% of the story height. In the building with non-structural components separated from the main structure, the inter-story drifts can amount up to 1% of the story height. These requirements are obligatory in order to diminish the life safety hazard of the building occupants from falling glass and in order to limit post-earthquake repairing costs.

The general purpose of the research reported in this paper is development and testing of tool for analysis of hysteretic behaviour of wall panels in general. The main information related to response of the structural element on earthquake action that can be obtained from hysteretic curves is the level of ductility, energy dissipation and stiffness degradation. The application of tool is illustrated for the case of hysteretic response of glass infilled wooden frames.

The combination of laminated timber frame and laminated glass presents an innovative approach for achieving improved earthquake resistance of buildings. Timber frame can be easily inserted in any type of structural system and at the same time enables the efficient and safe load transfer from the structural system to the inserted glass panel. To achieve adequate post-fracture behavior of the glass panel, heat strengthened laminated glass is used to provide high load bearing capacity after the potential cracking of the glass during an earthquake or extreme wind action. Panels composed of laminated or cross-laminated timber and laminated glass have a wide range of applications, among which the building refurbishment (Kaklauskas et al. 2005) presents only one of the possibilities.

1. Literature review

During the last two decades numerous in-plane racking tests of the wood-framed panels have been conducted. Among them the load-bearing glazing systems are rather rare (Antolinc et al. 2012). The majority of conducted in-plane racking tests on glazing systems (Behr et al. 1995; Behr 2001, 2006; Eva, Hutchinson 2011; Hutchinson et al. 2011; Memari et al. 2007; McBean 2005; Sivanerupan et al. 2008, 2011; Pantelides et al. 1996) are mostly dealing with glass panels shattering with glass fragments falling out of the framework and drift capacity of the whole system. There are also a few studies in which the glass panels are employed as a bracing and load-bearing elements. Niedermaier's (2003) research of the shear wall assembled of timber frame and glass panels can be considered as pioneering work in this field. The conceptual difference of his study compared to the previous ones is that the glass panel, glued to the timber frame, does not have just a function of transparent barrier between exterior and interior but it is also acting as an in-plane load bearing element. Such curtain wall can well contribute to stabilizing of building in horizontal direction. The author concludes that timber-glass hybrid can represent a very efficient alternative to conventional stiffening systems for timber structures.

An extensive research on glass panels acting as a shear wall has also been performed by Huveners (2009). His research has focused on steel frame with a single glass sheet that is circumferentially adhesive bonded to the frame and as such, it is considered as a load-bearing element. He has compared the results of three different types of steel to glass glued connection. The first type of joint connected circumferentially surface of glass sheets across its entire thickness. The second type of joint was in form of both-sided circumferentially lateral glass-to-steel glued connection, while the third type was only one-sided lateral glued connection. Influence of different types of adhesives (polyurethane and epoxy) was studied as well. The specimens were tested for the horizontal in-plane point load at the top transom. He concluded that glass panels as bracing elements in steel frames have a great potential. Polyurethane joints show more acceptable behavior than stiffer epoxy-based joints.

Another concept where the glass panels are used solely without any additional frame is applied in fully transparent pavilions. In this case, glass panels are considered to act as the vertical structural elements that have to support and transfer all the applied loads from the roof to the foundation. They also stabilize and stiffen the entire structure (Mocibob 2008). Two approaches to design of fully transparent pavilions have been studied (Mocibob 2008). In the first one, the glass panel is attached to the substructure by the bolted connections at the corners (point support concept). In the second one, named linear support concept, glass panels are linearly connected to the substructure by adhesives along the top (roof) and bottom (foundation) edges of panel. Panels are simultaneously loaded by the in-plane shear and vertical load along their upper edge and by the out-of-plane load q, which is distributed evenly across its surface. The research concludes that point supported glass panel has a high potential as a load bearing structural member for in-plane shear transfer where the linearly supported glass panel has a limited potential because of large deformation and low strength.

Mechanical pre-stressing of the glass panel, which can be further used as a structural bracing, can enhance in-plane shear capacity of windowpanes. This concept was a subject of research of Freitag and Woerner (2009) who tested two pre-stressing systems. In the first system, pre-stressing of the glass panel was induced in the corners of the steel frame. In the second one, pre-stressing was applied circumferentially along the edges of panel. Pre-stressing of glass panels diminish tensile stresses induced by the action of the lateral in-plane load. The authors conclude that proposed window system can serve as bracing structural component.

From the short overview of research follows that glass panels, if designed properly, can be used as bracing structural element with the minimal risk of glass falling out of supporting frame. Specific combination of glass panel and frame can have a considerable energy dissipative capacity, which can be activated during the event of the earthquake, in some cases even similar to the diagonal hydraulic dampers as described by Sung et al. (2010).

2. Experimental program

In order to learn about the hysteretic behavior and to evaluate stiffness, damping and energy dissipation of the above described wood-glass hybrid structural component, the in-plane racking tests have been conducted.

2.1. Test specimens

Three different types of specimens have been tested with the racking facility. Dimensions of specimens were 3222 mm in length and 2722 mm in height (Fig. 2). Frame infill was composed of two laminated glass panels having dimensions of 2900 mm in length and 2400 mm in height. Each panel was composed of two heat strengthened glass sheets, each of them 10 mm thick. They were bonded together by 1.6 mm film of ethylene and vinyl acetate copolymer EVA (EVA SAFE interlayer). Six timber frames were made of three-layered cross-laminated wood (specimens FR3-FR8), while the other six were made of glue-laminated wood (specimens FR9FR14). Cross section of frame elements was 90 mm in height and 160 mm in depth. For the production of frames the wood of class GL24h has been used.

All three types of specimens were of the same geometry and dimensions, with different detailing of timber frame joints (labeled CD1, CD2 and CD3) as presented in Figure 1. Two steel bolts ([empty set] 20 mm) connected timber frame elements in the joint of type CD1. In other two types of joints--CD2 and CD3--only one steel bolt ([empty set] 24 mm) was used as a connector. In order to prevent progressive shear failure (splitting) of frame joints and to increase the ductility of the timber frame, punched steel plate connectors were added in the case of CD3 type of joint.

2.2. Racking test setup and instrumentation

In order to obtain information on the in-plane behavior and the capacity of the shear wall panels, the in-plane quasi-static racking tests were conducted. Racking test facility is presented in the Figure 2. The reinforced concrete foundation beam is mounted on the top of the testing facility. Tested specimen is fixed to beam by four steel angle connectors. Specimen is actually turned upside down regarding its natural position in building for the safety reasons. Along the lower edge, three different boundary conditions (BC1, BC2, BC3) can be applied. Specimens are simultaneously loaded by the constant vertical load (Q) and displacement controlled monotone or cyclic force.

Boundary conditions at the bottom of the test specimen can be changed in the way to simulate three possible cases: free rotation, vertical and horizontal displacements (BC1), free horizontal displacement and uplift (due to deformation of specimen) (BC2) and free horizontal and vertical displacement (BC3). Types of boundary conditions are schematically presented in Figure 2.

Fourteen specimens were tested: 2 wooden bare frames and 12 wooden frames with glass infill. One half of them were tested by monotonous horizontal force and the other half by cyclic horizontal force. All three types of boundary conditions were applied. Table 1 shows the plan and organisation of the experiments.

The testing of vertical load-bearing capacity of laminated sheets and their resistance to buckling has been reported in Rajcic and Zarnic (2012). There were two specimens of laminated sheets (h/w/t = 2400/1250/ 22 mm) tested by vertical load uniformly distributed along the upper edge of specimens. The lower value of buckling load was 138.1 kN/m' at horizontal displacement measured in the mid-height of specimen of 21.4 mm and strain measured in vertical direction of 0.029%. The glass panels in wooden frames exposed to racking load were simultaneously loaded by vertical load of 12.5 kN/m'. The maximal horizontal displacement measured in mid-height of glass panel was 1 mm and strain in vertical direction 0.003%.

Comparison of monotone responses in Figure 3 shows that specimens subjected to boundary condition BC1 exhibited very similar response to the specimen subjected to boundary conditions BC3. Therefore, it has been decided to apply BC3 only in the case of one type of specimens (FR3 and FR4). Each of the specimens was equipped with twelve linear variable differential transformers (LVDT1-LVDT14) to measure the displacements and to capture the overall behavior. There were also eleven strain gauges (SG1-SG12) placed on the glass panels to control the load distribution over the panel.

The instrumentation is depicted in Figure 2. LVDT1 measured the story drift that is the basis for further analysis of the panel performance. LVDT2 and LVDT3 measured the relative displacements between the glass panel and timber frame in order to obtain information on the share of energy dissipation provided by friction.

2.3. Loading protocol

Horizontal in-plane load was applied by the displacement controlled hydraulic actuator of 250 kN load capacity and displacement ranges of [+ or -]200 mm. Specimens were tested in pairs. The first of two equal specimens was tested with monotonous load (Fig. 3) of up to 20% drop of load-bearing force. The force-displacement curve of monotonous test was used to define the displacement controlled hysteretic load protocol according to the prEN 12512 (Heine, Dolan 2000). The cyclic story drift protocol for the specimen FR12 is presented in Figure 4.

The constant vertical load Q of 80 kN, is distributed evenly along the bottom edge of specimen (q' = 25 kN/m) and represents the loading with upper building floors in the real building.

2.4. Hysteretic response of tested specimens

The investigated hybrid shear wall has a specific transfer of the applied in-plane load between the individual elements due to specially designed friction connection between glass panels and timber frame. It was designed in way that enables sliding of glass panel within timber frame until some drift limit. This phenomenon is visible as hysteresis loop pinching (Fig. 5). The overall behavior of the specimens is predominantly characterized by the connection details of timber frame elements, glass to timber friction capacity and contribution of the diagonal effect.

The main purpose of the conducted experiments was to obtain the hysteretic response, as it contains the information on stiffness degradation, strength deterioration, viscous damping and energy dissipation capacity. All six specimens have pinched shape of hysteresis loops. This behavior is expected due to the glass panel sliding. On each of the diagrams in Figure 5, the first failure points are highlighted by red dots. It can be seen that in all cases, the first failure appears at around 0.5% of story drift, which corresponds to the displacement amplitude where diagonal effect (glass panel) becomes dominate in taking over of the applied load. With increasing of the horizontal displacement amplitude, the splicing of timber frame propagates, and thus larger force is required for deforming of specimen. This is the reason for increasing of overall bearing capacity of the hybrid wall after the occurrence of first cracks in frame joints.

The amount of energy dissipated by glass-to-wood friction depends on magnitude of horizontal displacements induced to specimen and on boundary conditions along the lower edge of specimens. In the beginning at low displacements (in the range of 0.05% story drift) up to 80% of energy has been dissipated by friction. Level of dissipation lowered to 30% at displacements where the joint failure stared to develop (in the range of 0.5% story drift). After development of failure mechanism in frame joints the share of energy dissipated by friction stabilize at approximate value of 25%.

The overall stiffness of tested structural component was governed by stiffness of framed glass panel and configuration of joints. Due to development of damages in frame joints stiffness gradually decreased but it has been relatively high due to "strut effect" of glass infill, which was predominant.

In order to obtain detailed information on the hysteretic behavior of structural components constructed of different materials, the procedure has been developed and applied in computational tool named as HYSPA+ (HYSteresis PArameters). It is simple software that calculates the main parameters from the hysteresis loop coordinates, as follows:

--Hysteresis envelope ("backbone" curve);

--Effective stiffness (Ke) as defined by Eqn (1);

--Idealized bilinear envelope as defined in Figure 6;

--Ductility factor (i) as defined by Eqn (1);

--Secant stiffness (K) associated with each hysteresis cycle defined by the hysteresis turning point (Fig. 7);

--Parameters of the stiffness degradation curve (n and C), as defined by Eqn (4);

Strength deterioration defined as lowering of strength at hysteresis turning point due to cyclic repeating of hysteretic loading;

--Equivalent viscous damping coefficient ([xi]) that quantifies the hysteretic energy dissipation. Each of the above listed properties of glass infilled wooden frames is discussed below except the strength deterioration, because it was of negligible amount.

3. Ductility

In general, ductility factor (i) is defined as a ratio between the ultimate displacement and displacement on elastic limit (Eqn (1)). In herein proposed procedure the parameters of ductility are derived as presented in Figure 6. The idealized bi-linear hysteresis envelope is defined by the energy equality principle of surfaces. They are defined by the experimentally obtained hysteresis "backbone" curve and idealized envelope. The idealized envelope is created by the best fitting of bi-liner shape to the "backbone" curve shape. In the case of discussed structural component the value of effective stiffness [K.sub.e] is defined by the displacement coordinate [[delta].sub.cr] obtained from "backbone" curve at level of 67% of maximal force ([F.sub.max]). Because the response of structural component might be asymmetric, the idealized envelope is calculated separately for each direction of load action (i.e. "positive" and "negative" direction of force action) (Table 2):

[mu] = [[delta].sub.u]/[[delta].sub.e]; (1)

[K.sub.e] = [F.sub.e]/[[delta].sub.e] = 2/3 [F.sub.max]/[[delta].sub.cr]. (2)

4. Stiffness degradation

One of the main parameters characterizing the hysteretic response of the specimen is stiffness degradation. Eqn (3) defines the secant stiffness, [K.sub.i], of each hysteresis loop:

[K.sub.i] = [F.sub.i]/[[delta].sub.i], (3)

where: [F.sub.i] is the force at the applied corresponding displacement amplitude [[delta].sub.i]. To ease the comparison of the stiffness degradation, the secant stiffness of the hysteresis loop K was normalized with the effective stiffness [K.sub.e] of the hysteresis envelope (Eqn (2)).

The experimentally determined relationships between normalized stiffness [K.sub.i]/[K.sub.e] and corresponding normalized displacement amplitude [[delta].sub.i] /[[delta].sub.e] for all hysteresis loops and specimens are presented in Figure 8 as red cross-points.

The stiffness degradation curve has a hyperbolic shape (Eqn (4)):

y (x)= C/[x.sub.n]. (4)

If x = [[delta].sub.i]/[[delta].sub.e] and y (x) = [K.sub.i]/[K.sub.e] hen the transformation of Eqn (4) in logarithmic form results in:

[log.sub.10] [C.sub.i] = [log.sub.10] ([K.sub.i]/[K.sub.e]) +n [log.sub.10] ([[delta].sub.i]/[[delta].sub.e]). (5)

Eqn (6) defines the parameter C (0 < C < 1), where m is a total number of hysteresis loops:

[MATHEMATICAL EXPRESSION NOT REPRODUCIBLE IN ASCII]. (6)

From the known relationship between C and n (Eqn (4)) value of parameter n can be evaluated by the least square method. The procedure is included in program HYSPA+ that by stepwise iteration, taking values of n (0 < n < 1) in increments of 0.01, defines the best-fitted curve to experimentally obtained points.

Stiffness degradation expressed by only two parameters enables simple comparison of hysteretic response of tested structural components as well as comparison between tested and numerically predicted behaviour of structures. Therefore, HYSPA+ can serve as a tool for assessment of accuracy of mathematical model of tested type of structural component.

The intensity of stiffness degradation expresses the magnitude of coefficient n. It is well seen in the range of lower amplitudes of displacements ([[delta].sub.i] < [[delta].sub.e]). The overall stiffness degradation factor C provides information regarding the general magnitude of stiffness degradation.

In the Figure 7 are presented fitted curves, experimentally obtained values and parameters C and n, which define the fitted curves. From the comparison of values C and n it can be concluded that symmetry of behavior expressed by stiffness degradation has been the case where single bolt was used to connect wood frame elements (FR10, FR12 and FR14). It also means that damages in joints were developing gradually with the similar mechanism during acting of external force in each direction. The same conclusion can be derived from observation of hysteresis presented in Figure 5. Response of specimens having two bolts in joints (FR4, FR6 and FR8) was asymmetric as can be seen both from Figures 5 and 7. Also, different intensity of stiffness degradation can be observed from the values of parameter n calculated for the both opposite directions of cyclic force action. The boundary condition effect significantly influenced the response of specimens having two bolts in joints (FR4, FR6 and FR8), while in the case of joints strengthened by punched steel connectors the influence of boundary conditions to stiffness degradation was not observed (FR12 and FR14).

Due to the early failure of joint of specimen FR10 faster degradation of stiffness ([n.sub.average] = 0.69) was observed in comparison to specimens FR12 and FR14 ([n.sub.average] = 0.55). The similar effect of stiffness degradation was observed in the case of joint configuration CD1 due to different boundary conditions. In the case of specimen FR4 where boundary condition BC3 was applied, the stiffness degradation was more intensive ([n.sub.average] = 0.73) than in cases of FR6 (BC1; [n.sub.average] = 0.54) and FR8 (BC2; [n.sub.average] = 0.44). On the same way the other characteristics of the specimen configurations and boundary conditions can be analyzed as well.

5. Equivalent viscous damping

The equivalent viscous damping coefficient [xi] is quantifying the hysteresis response of structural components, and as such, it is one of the key indicators describing their behavior. It is defined by expression:

[xi] = [E.sub.D]/2[pi][E.sub.E] = [E.sub.D]/2[pi]([E.sup.+.sub.E] + [E.sup.-.sub.E]) = [E.sub.D]/2[pi] (1/2 [K.sub.p] [u.sub.max] + 1/2 [K.sub.n] [U.sub.min]). (7)

In above equation [E.sub.D] stands for the dissipated energy in hysteresis loop, [E.sub.E] for the elastic strain energy, [E.sup.+.sub.E] and [E.sup.-.sub.E] for the elastic strain energy in positive and negative direction of force action, [K.sub.p] and [K.sub.n] for secant stiffness of the loop in positive and negative direction, and [d.sub.max] and [d.sub.min] for the maximum and minimum displacements of the considered loop. The parameters employed in the Eqn (7) are graphically presented in Figure 9 below.

Equivalent viscous damping [xi] calculated at hysteresis turning points is presented in Figure 10. For specimens FR10, FR12 and FR14, it can be observed that almost constant maximum value of [xi] is recorded at relatively small displacements, which can be explained with influence of glass-to-wood friction dissipation of energy at lower displacement amplitudes. In the case of FR4, FR8 and FR8 energy was dissipated due to gradual development of damages in frame joints and by friction along the frame-to-glass contact.

Combination of dissipation of energy by friction and development of damages in joints influence the magnitude of totally dissipated energy. From the curves presented in Figure 10 is obvious that configuration of frame with single bolted joint is more energy dissipative than frame with double bolted joints. The single bolted joint allowed higher friction dissipation due its higher deformability.

The specimens FR4, FR6 and FR8 were more rigid than specimens FR10, FR12 and FR14 due to configuration of their joints (CD1). This results in slow increase of equivalent viscous damping coefficients Only after severe damages (after story drift d/h > 0.75%) of connections, the coefficient reaches the values of [xi] and become comparable to those of the specimens having joints of type CD2 and CD3. The highest values of viscous damping coefficients [xi] vary between 0.24 and 0.34.

Conclusions

Hybrid shear walls composed of timber frame and laminated glass were tested to obtain information on their performance when exposed to cyclic horizontal in-plane load (earthquake, wind). Altogether 12 racking tests have been conducted with two different load protocols (monotone, cyclic), three different boundary conditions and three different configurations of timber frame joints.

For all tested specimens is common that the majority of damage was concentrated in timber frame joints, as they are the weakest part of the hybrid wall. The laminated glass panels remained intact during the entire test. The punched steel plate connector used in joints of type CD3, efficiently limited the propagation of damages and contributed to better response of specimens in comparison to those without steel plates.

Test results show that friction force is playing an important role in sharing resistance to in-plane acting load with frame joints. The considerable amount of energy was dissipated by friction. Hysteretic response of the specimens provided the information on ductility, stiffness degradation and viscous damping. The analysis of stiffness degradation shows more symmetric and severe degradation for the specimens with one bolt in frame joint (CD2) and one bolt with punched steel plate connectors (CD3). Fast and nearly constant development of equivalent viscous damping coefficient _ was governed by high level of resistance of friction force to the imposed load in the cases of joint types CD2 and CD3.

It can be concluded that the whole hybrid shear wall shows considerably robust behavior. Damage propagation in joints up to their local failure does not lead to failure of tested specimen that was able to dissipate the induced energy due to wood-to-glass friction. Moreover, performance of joint detailing can be improved to achieve even higher deformation capacity. Learning from experiments and from the mathematical model that is under development, new series of specimens will be tested. The major improvement of next specimens will be in critical details of frame joints.

Acknowledgments

The research reported in article was financed by: the Slovenian Research Agency for funding of young researcher (contract no. 261408-1/2008), the Ministry of Science, Education and Sport of Croatia through the scientific project 082-1491823-1463 entitled "Characteristics of the composite structures wood-structural glass and wood steel" and the Ministry of Education, Science and Sport of Slovenia through the program P2-0182 "Earthquake Engineering". The authors gratefully acknowledge their contribution to success of research.

References

Antolinc, D.; Rajcic, V.; Stepinac, M.; zarnic, R. 2012. Laminated glass panels in combination with timber frame as a shear wall in earthquake resistant building design, in Proc. of the Conference on Architectural and Structural Applications of Glass, Challenging Glass 3, June 2012, Delft, Netherlands, 623-631.

Behr, R. 2001. Architectural glass for earthquake-resistant buildings, in Proceedings of the 12th International Conference on Architectural and Automotive Glass, Glass Performance Days, June, 2001, Tampere, Finland, 341-347.

Behr, R. 2006. Design of architectural glazing to resist earthquakes, Journal of Architectural Engineering 12(3): 122-128. http://dx.doi.org/10.1061/(ASCE)1076-0431(2006)12:3(122)

Behr, R.; Belarbi, A.; Culp, J. H. 1995. Dynamic racking test of curtain wall glass elements with in-plane and out-of-plane motions, Earthquake Engineering and Structural Dynamics 24(1): 1-14. http://dx.doi.org/10T 002/eqe.4290240102

Eurocode 8: Design of structures for earthquake resistance. Part 1: General rules, seismic actions and rules for buildings. European pre-standard, ENV 1998-1, CEN, Brussels, 2008.

Eva, C.; Hutchinson, T. C. 2011. Experimental evaluation of the in-plane seismic behaviour of storefront window systems, Earthquake Spectra 27(4): 997-1021. http://dx.doi.org/10.1193/E3651407

Freitag, C.; Woerner, J-D. 2009. Glass as structural bracings shear capacity of mechanically pre-stressed windowpanes, in Proceedings of the 11th International Conference on Architectural and Automotive Glass, Glass Performance

Days, June, 2009, Tampere, Finland, 329-333. Heine, C. P.; Dolan, J. D. 2000. Cyclic response of multiple bolted connections, in World Conference on Timber Engineering, 2000, Whistler Resort, British Columbia, Canada. 7 p.

Hutchinson, T. C.; Jian, Z.; Eva, C. 2011. Development of a drift protocol for seismic performance evaluation considering damage index concept, Earthquake Spectra 27(4): 1049-1076. http://dx.doi.org/10.1193/E3652707

Huveners, E. 2009. Circumferentially adhesive bonded glass panes for bracing steel frames in facades: h hesis. TU Eindhoven, Netherlands.

Kaklauskas, A.; Zavadskas, E. K.; Raslanas, S. 2005. Multivariant design and multiple criteria analysis of building refurbishments, Energy and Buildings 37(4): 361-372. http://dx.doi.org/10.1016/j.enbuild.2004.07.005

McBean, P. 2005. Drift intolerant facade systems and flexible shear walls. Do we have a problem?, in Proc. of the Annual Technical Conference of the Australian Earthquake Engineering Society, 2005, Albury, Australia, 1-8.

Memari, A. M.; Shirazi, A.; Kremer, P. A. 2007. Static finite element analysis of architectural glass curtain walls under in-plane loads and corresponding full-scale test, Structural Engineering and Mechanics 25(4): 365-382. http://dx.doi.org/10.12989/sem.2007.25A365

Mocibob, D. 2008. Glass panel under shear loading--Use of glass envelopes in building stabilization: PhD Thesis. EPFL, Switzerland.

Niedermaier, P. 2003. Shear-strength of glass panel elements in combination with timber frame constructions, in Proc. of the 8th International Conference on Architectural and Automotive Glass, Glass Performance Days, June, 2003, Tampere, Finland, 262-264.

Pantelides, C. P.; Truman, K. Z.; Behr, R. A.; Belarbi, A. 1996. Development of a loading history for seismic testing of architectural glass in a shop-front wall system, Engineering Structures 18(12): 917-935. http://dx.doi.org/10.1016/0141-0296(95)00224-3

Priestley, M. J. N.; Seible, F.; Calvi, G. M. 1996. Seismic design and retrofit of bridges. John Wiley & Sons, Inc. 721 p. http://dx.doi.org/10.1002/9780470172858

Rajcic, V.; []arnic, R. 2012. Racking performance of wood-framed glass panels, in Quenneville, P. (Ed.). WCTE 2012: The Future of Timber Engineering: Final Papers. Auckland: WCTE, 57-62.

Sivanerupan, S.; Wilson, J. L.; Gad, E. F. 2008. Drift performance of facade systems, in Proc. of the Earthquake Engineering in Australia Conference, November, 2008, Ballarat, Victoria, Australia, 21-23.

Sivanerupan, S.; Wilson, J. L.; Gad, E. F.; Lam, N. T. K. 2011. Structural analysis and design of glazed curtain wall systems, Australian Journal of Structural Engineering 2(1): 57-67.

Sung, W.; Shih, M.; Zhao, Y. 2010. Energy dissipation behaviors and seismic reduction performance of a proposed velocity and displacement dependent hydraulic damper (), Journal of Civil Engineering and Management 16(3): 428-138. http://dx.doi.org/10.3846/jcem.2010.49

Tomazevic, M. 1999. Earthquake-resistant design of masonry buildings. Imperial College Press. 268 p. http://dx.doi.org/10.1142/p055

Zarnic, R. 1992. Neelasticni odziv armiranobetonskih okvirov z zidanimi polnili na potresno obtezbo [Inelastic response of reinforced concrete frames with masonry filler on the seismic load]: PhD Thesis. University of Ljubljana, Faculty of Civil and Geodetic Engineering, Slovenia. 195 p.

Zarnic, R.; Tsionis, G.; Gutierrez, E.; Pinto, A.; Geradin, M.; Dimova, S. 2007. Purpose and justification for new design standards regarding the use of glass products in civil engineering works: support to the implementation, harmonization and further development of the Eurocodes. JCR Scientific and Technical Reports, EUR 22856 EN. 1st ed. Luxembourg: Office for Official Publications of the European Communities: Joint Research Centre European Commission. 30 p.

David ANTOLINC, PhD, Teaching Assistant at the Faculty of Civil and Geodetic Engineering at the University of Ljubljana. Publications: 9 articles about structural glass and computational modelling of FRP structures. Research interests: structural glass in earthquake resistant buildings, composite materials and resistance of buildings on blast loads.

Vlatka RAJCIC, PhD, Professor at the Faculty of Civil Engineering at the University of Zagreb Participating in many international projects, lately was dissemination leader of recent FP7 projects EU-CHIC, WP leader in FP7 SMooHS, FP7 Climate for Culture. She is a coordinator of the Horizontal Issue: Ethics, Education and Training in Cultural Heritage of the activities of Focus Area Cultural Heritage (FACH) within the European Construction Technology Platform (ECTP). Publications: 5 university textbooks and more than 100 articles in books, journals and conference proceedings. Research interests: development of hybrid structural elements of wood and emerging materials (structural glass, steel, cross- laminated wood, FRP), design of contemporary large-span timber structures, research in structural aspects of cultural heritage buildings.

Roko, ZARNIC, PhD, Professor at the Faculty of Civil and Geodetic Engineering at the University of Ljubljana. Participating in 31 international projects (EU FP4 to FP7, EUREKA and COST), coordinating the recent EU FP7 Project EUCHIC, Coordinator of the Focus Area Cultural Heritage (FACH) within the ECTP. Publications: 2 university textbooks and more than 260 articles in books, journals and conference proceedings. Research interests: development of structural elements of wood and emerging materials (FRP, laminated glass, laminated wood), research in earthquake strengthening of masonry and reinforced concrete structures, research in material and structural aspects of cultural heritage buildings and development of strategies for preservation and preventive conservation of heritage buildings and objects.

David ANTOLINC (a), Vlatka RAJCIC (b), Roko ZARNIC (a)

(a) Faculty of Civil and Geodetic Engineering, University of Ljubljana, Jamova 2, 1000 Ljubljana, Slovenia

(b) Faculty of Civil Engineering, University of Zagreb, Kaciceva 26, 10000 Zagreb, Croatia

Received 01 Jul 2013; accepted 17 Oct 2013

Corresponding author: Roko Zarnic

E-mail: roko.zarnic@fgg.uni-lj.si

Table 1. Boundary conditions and connection details
assignments to the cyclic loaded specimens

                   SPECIMENS FR2--bare wooden frame
                   FR4--FR14 glass-infilled wooden frames

                   FR2       FR4       FR6       FR8

Boundary     BC1                       [check]
conditin     BC2   [check]                       [check]
             BC3             [check]
Connection   CD1             [check]   [check]   [check]
detail       CD2
             CD3   [check]

                   FR10      FR12      FR14

Boundary     BC1   [check]   [check]
conditin     BC2                       [check]
             BC3
Connection   CD1
detail       CD2   [check]
             CD3             [check]

Table 2. Comparison of ductility factors u. based on hysteresis
response for positive and negative direction

Specimen   [d.sup.+.sub.e]   [d.sup.-.sub.e]   [d.sup.+.sub.max]

FR4        10.2              -6.57             31.29
FR6        16.52             -9.5              36.58
FR8        21.39             -9.87             25.42
FR10       15.28             -16.76            40.18
FR12       16.65             -19.9             49.42
FR14       16.81             -23.95            39.99

Specimen   [d.sup.-.sub.max]   [[mu].sup.+]   [[mu].sup.-]

FR4        -27.35              3.07
FR6        -43.15              2.21           4.54
FR8        -25.98              1.19           2.63
FR10       -33.3               2.63           1.99
FR12       -53.08              2.97           2.67
FR14       -44.93              2.38           1.88
COPYRIGHT 2014 Vilnius Gediminas Technical University
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2014 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Antolinc, David; Rajcic, Vlatka; Zarnic, Roko