Acoustic emission monitoring of reinforced concrete frame during seismic loading.

Introduction

Old, substandard RC buildings designed in the 60's on the basis of vertical loads only are often characterized by irregular distribution of strength and stiffness in-plan. These structural characteristics, usually dictated by architectural requirements, are coupled with those owing to the design according to non-seismic design codes of the 60-70's in Southern Europe (e.g., insufficient detailing of reinforcement, low concrete strength) result in structures with increased vulnerability to earthquakes. An experimental program of a 0.7-scale model of a real-size frame structure designed and detailed as old RC buildings in Greece, without engineered earthquake resistance, was carried out at the Structures Laboratory of the Department of Civil Engineering at the University of Patras, employing the pseudo-dynamic testing method. To represent the actual torsional seismic response of such a structure, pseudo-dynamic testing was performed with four degrees of freedom (DOF): the displacements of the two floors in the direction of the actuators, plus the two floor rotations with respect to the vertical axis. The structure was excited by a 15-sec-long unidirectional input motion that fitted well with the 5%-elastic spectrum of Eurocode 8 modulated after one component of the Herzegnovi record in the 1979 Montenegro earthquake.

Due to their sub-standard design, the columns of the building, both at ground and upper floor, exhibited low strength and ductility capacity and, thus, damage was expected to develop first at their ends, due to the insufficient reinforcement overlapping length there. Acoustic emission was used as an NDT method, to monitor damage development at these vulnerable areas. Due to the complex nature of the applied loading and structural response, techniques previously proposed (Matsuyama et al., 1993, Yuyama et al., 1999) for AE evaluation during controlled stimulus, are not directly applicable. Different source location techniques (zonal, linear and 3-D location) were applied in order to identify potential high risk areas of increased AE activity during loading. A summary of the experimental procedure and the derived results are reported and discussed herein. Comparison of the differences detected in AE behavior among the different columns as well as between the base and the 1st floor joints is performed and the results are correlated with the applied load. Further processing of the located AE events, enabled the verification of the damage areas observed and the assessment of the building structural integrity.

Experimental Set Up

A nearly full-scale model simulating the structural configuration and seismic response of real-size reinforced concrete structures was constructed and tested. The structure comprised of two floors and one bay per direction, while its four columns formed pairs of unequal resistance and stiffness along the longitudinal (X) direction of the structure. The plan dimensions of the specimen structure were 3.15 x 3.85 m and the floor height was 2.30 m and 2.0 m at ground and top floor, respectively as presented in Fig. 1. To create an asymmetric structure that responds with torsion under translational ground motions, columns of one side were one-half size of those of the other side. All columns were 0.175-m wide while their depth varied from 0.175 m for the pair of columns at one side of the structure, to 0.35 m for the opposite pair. Columns were cast on spread footings anchored on the strong floor of the laboratory and were longitudinally reinforced with four 10-mm-diameter smooth (S220) bars for the columns with the smaller section, and six 10-mm-diameter bars for the larger ones. Transverse reinforcement consisted of 6-mm-diameter smooth (S220) bars placed at 200-mm apart. The beams and the slabs were heavily reinforced so that inelastic response would appear first on columns. A mean concrete strength of 22.8 MPa and 18.05 MPa was obtained on the day of testing at the ground and upper floor, respectively.

[FIGURE 1 OMITTED]

Prior to AE monitoring, the structure was subjected to the selected earthquake record scaled at 0.30 g. During this initial testing phase, the structure exhibited strong torsional response, which - contrary to current beliefs based on simplistic analytical studies - induced larger displacements on the more flexible side of the building. Columns were subjected to biaxial flexure and exhibited damage concentrated at the base of smaller ground-floor columns, owing to the inadequate force transfer along the small bar overlapping length and slippage of vertical bars within the footing. Beams were over-reinforced - as it was common in this category of structures - and displayed no damage. Some hairline diagonal cracks were observed on the sides of the larger columns, owing to the development of torsional moments in these members, which closed after the test. Some cracks formed also at the beam-column interface due to slippage of the (smooth) column reinforcing bars within the joint. To reinstate the torsional balance, smaller columns (denoted here as columns 1 and 2) were reinforced via a 0.05-m-width concrete jacket cast from the footing to the top of the structure. The structure was excited again with the same seismic record at 0.30 g, while being monitored with AE.

[FIGURE 2 OMITTED]

The observation of the structure during testing and the recorded displacement and rotation data (Fig. 2) reveal that the torsional response almost disappeared and the building displaced along the axis of excitation. The observed damage consisted of cracking in the larger columns and spalling of the concrete cover due to and along the lap-spliced bars at the base of the columns. Cracking also developed at the beam-column joints at the ground and the top floor. During the later stages of the excitation though - and due to the damage inflicted on the larger columns - the torsional response re-appeared, albeit at very low amplitude.

Acoustic emission monitoring was performed using a 40-channel PAC-DiSP (PAC, 2001) system. The sensors used were standard PAC resonant type R15I, 150-kHz resonance with 40dB integral preamplifier. The position of the AE sensors and the points of applied deformation are shown in Fig. 1. Sensor position was selected in such a way to permit linear location along the column height and linear x-y location at the 1st floor joints. Prior to the test the AE sensors were calibrated and the velocity of the AE signals was calculated in order to achieve the best possible sensor set-up sufficiently covering the areas with expected high AE activity. In addition to that the attenuation of the AE signals was measured, Fig. 3.

[FIGURE 3 OMITTED]

Acoustic Emission Results

Prior to the actual test a preliminary, trial loading was performed at low load levels. The maximum load of the preliminary test was 2% of the load that the building was eventually loaded. The AE activity that was recorded during the preliminary test was relatively low with low energy levels, as presented in Fig. 4. This preliminary test resulted in useful information concerning the background noise of the system as well as for setting up acquisition parameters for the AE system. In addition to that, the activity recorded in columns 1 and 2, due to the friction between the jackets and the concrete frame, was useful during the analysis phase in discriminating genuine AE signals from friction and defining damage evaluation levels.

The force exerted by each one of the four actuators is presented in Figs. 5 and 6 (four background plots for actuators 1 to 4, respectively) together with AE energy rate from each column. After jacketing the flexible columns, the building response was mainly uniaxial. The complex nature of loading (cyclic loading with varying amplitude and phase shift between actuators) resulted in complicated structural displacements and render infeasible the direct correlation between the applied loading and the AE activity. The majority of the AE activity, around 98%, is emitted from columns 1 and 2. As can be seen from Figs. 5 and 6, the AE activity starts at a deformation level exceeding that which caused the damage during the past loading (initial test at 0.30 g). Direct comparison between past and present loading, as a means to calculate Felicity effect, is not possible due to the different nature of applied loads as well as the addition of concrete jacket on columns 1 and 2. Moreover, it is worth noting that there is an absence of AE activity during a displacement hold at relative high force level between 50005800 sec, implying no creep effects during that period.

[FIGURE 4 OMITTED]

[FIGURE 5 OMITTED]

Finally, it is worth noting that the energy scale for columns 3 and 4 in Fig. 6 is one order of magnitude lower than that for columns 1 and 2 in Fig. 5.

[FIGURE 6 OMITTED]

Source Location and Correlation with Visual Inspection

During the entire test high AE data rates were recorded on most channels covering the structure, especially on the channels attached on flexible columns 1 & 2 after they had been externally reinforced by means of concrete jacketing. The use of various AE signal source-location algorithms provided the necessary focus of the analysis to locate the main areas where damage developed and to find areas with high likelihood of failure. A complex source-location strategy was employed with each column being treated as a separate entity to avoid signal time overlap and event mirroring. The basic source location algorithms used to locate damage was the Linear X-Y and Linear 3D modes in Noesis AE Data Analysis software (Envirocoustics SA, 2005). Typical location results for column 1 are presented in Fig. 7. The height of column 1 is represented on the horizontal axis of the plot, starting from sensor #8 (0 m column bottom) up to sensor #1 (3 m, top area of column) and sensors #3 and #4 projected also on the x-axis.

The linear location strategies showed the areas sustaining damage during the test. This damage is attributed to cracks and hairline cracks or crack face friction in the columns and the reinforcing jacket. The two un-strengthened columns (columns 3 and 4) showed little located AE activity compared to the other two columns. Any activity was mainly from the joint at the first floor and more specifically in the area of beam-column-slab joint at the floor slab. Some activity was also recorded from the lower section of the columns. Columns 1 and 2 that had sustained damage during the initial earthquake record of 0.3 g and had been reinforced with concrete jackets produced significantly more AE activity, which corresponded to more clearly visible hairline cracking on the jacket itself. This is attributed to the eventual slippage between the initial concrete and the jacket. Visual inspection did not yield any information about damage to the inner column. In this case also, the located activity was concentrated to the lower section of the joint and immediately below the joint of the 1st floor. This is clearly shown in Fig. 8 of Column 1, where the concentration of activity is immediately below the node is the most significant of any column in this test.

[FIGURE 7 OMITTED]

This concentration of activity shows the areas that are actually subjected to damage during the test. It is generally estimated that any failure during the re-positioning of the structure to a higher deformation state will occur in these areas first. Visual inspection and correlation of visible cracks with AE located activity was not always possible during the test, since it was found by closer inspection later and the present data analysis that cracking, which was invisible to naked eye produced significant AE. Although no cracks of significant width were observed, either on the retrofitted or the un-retrofitted columns, the amount of AE recorded distinguishes these areas as subject to further damage. The success of AE to individualize, at an early stage, the specific areas, at which medium damage is manifested and most likely enhanced at higher drifts, was demonstrated in subsequent tests to 0.45 g and 0.55 g. These tests (not reported in this work) produced a level of damage sufficient to visually confirm the existence of concrete cracking and reinforcement slippage. Significant damage at the joint at the top of Column 1 mentioned above was observed and in other areas where AE had given early warning. More specifically, increased AE activity recorded from both the node and the base of column 2. Compared with the activity and events identified on column 1, the activity at the node of column 2 was lower while that at the base (channel 16) was higher.

[FIGURE 8 OMITTED]

Concerning the activity from the joints of columns 3 and 4, AE events of similar level, indicating the onset of emission, were recorded from both columns. For example, the events located on column 4 versus time are presented in Fig. 8. More specifically the AE activity is displayed for the full height of the column (y-axis, with sensor number) versus time (horizontal axis). For example, at approximately 800 sec, there is some activity located at joint (sensors #27, #28, #29). On the other hand, the base of column 4 (channels #31 and #32) emitted more signals resulting in well-defined sources. Figure 8, in conjunction with Fig. 6, provides important information about the behavior of column 4 and its correspondence to the level of structural deformation and time parameters. The successful correlation of located events, both in time and position, with the hairline cracks observed, is worth noting.

Discussion and Conclusions

A series of full-scale tests on retrofitted or un-reinforced concrete structures were performed, during which acoustic emission was monitored. The retrofitted columns of the building tested showed minor cracking on the reinforced concrete jacket with some damage developing at the base of the ground floor and the joints of the structure. Throughout the test, AE monitoring identified activity at the bottom of ground floor columns and the joints of the ground-floor beamcolumn intersection, thus, indicating the most damage prone areas. This was evident by the increased overall AE activity in these areas and significant activity concentration.

Results during subsequent loading tests under 0.40 g and 0.45 g seismic events (not reported here) proved that the AE method identified correctly the areas of damage as these were the exact locations where failure occurred (large cracks, concrete spalling and slippage of reinforcement).

Based on conventional analysis, AE data signatures from crack and reinforcement slippage cannot be easily separated. Future work utilizing displacement measurements at the various positions around the structure for correlation with AE activity versus time and position as well as unsupervised pattern recognition for the treatment of AE data, can provide further insight to the damage mechanisms (crack propagation, reinforcement slippage etc) and possibly yield quantitative damage growth assessment in similar structures and repair techniques.

Acknowledgments

The work reported in this paper was funded by the Greek General Secretariat for Research and Technology, through the project ARISTION (ARISTION, 2006) within the framework of the program "Built Environment and Management of Seismic Risk".

References

Anastasopoulos, A., Bousias, S.N., Tsimogiannis, A., Toutountzakis, T., "Acoustic emission testing of concrete frame during pseudodynamic loading", 27th European Conference on Acoustic Emission Testing, Cardiff, Sept. 2006.

DiSP User's Manual Rev 1 & AEWin User's Manual Rev. 2, Physical Acoustics Corp, Sept 2001.

Bousias, S. N, Fardis, M.N., Spathis, L.-A. and Kosmopoulos, A. "Pseudodynamic response of torsionally unbalanced 2-story test structure", J. of Earthquake Engng Struct. Dyn. 36:1065-1087, 2007.

Bousias, S.N., Spathis, A-L, Fardis, M.N., Papanicolaou, C.C., and Triantafillou, T.C. "Pseudodynamic Tests of Non-Seismically Designed RC Structures Retrofitted with Textile-Reinforced Mortar", 8th International Symposium on Fiber Reinforced Polymer Reinforcement for Concrete Structures (FRPRCS-8), Patras, July 2007.

Bousias, S.N., Spathis, A-L, and Fardis, M.N. "Experimental Seismic Response of Eccentric RC Structures, before or after CFRP-Rehabilitation", 8th International Symposium on Fiber Reinforced Polymer Reinforcement for Concrete Structures (FRPRCS-8), Patras, July 2007.

Matsuyama K., Fujiyama T., Ishibashi A. and Ohtsu M., (1993), "Field Application of Acoustic Emission for the Diagnosis of Structural Deterioration of Concrete", J. of Acoustic Emission, 11(4), 65-73.

NOESIS Ver. 4.1 (2005) - Reference Manual, Envirocoustics S.A. www.aristion.gr (2006).

Yuyama S., Okamoto T., Shigeishi M., Ohtsu M. and Kishi T., (1999), "A proposed standard for evaluating structural integrity of reinforced concrete beams by acoustic emission", ASTM STP 1353, pp. 25-40.

A. ANASTASOPOULOS, S. BOUSIAS * and T. TOUTOUNTZAKIS

Envirocoustics SA, El. Venizelou 7 & Delfon, 14452 Athens, GREECE; * Structures Laboratory, Dept. of Civil Eng. Univ. of Patras, 26500, Patras, Greece
COPYRIGHT 2007 Acoustic Emission Group
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2007 Gale, Cengage Learning. All rights reserved.

Article Details
Printer friendly Cite/link Email Feedback
Author:Anastasopoulos, A.; Bousias, S.; Toutountzakis, T.
Publication:Journal of Acoustic Emission
Article Type:Report
Geographic Code:4EUGR
Date:Jan 1, 2007
Words:2718
Previous Article:Acoustic emission techniques standardized for concrete structures.
Next Article:Acoustic emission leak testing of pipes for pressurized gas using active fiber composite elements as sensors.
Topics:

Terms of use | Privacy policy | Copyright © 2019 Farlex, Inc. | Feedback | For webmasters