How to address cooling system woes.


* Anyone who operates a molding plant knows three things it cannot run without: raw material, electrical power, and cooling water. The plant's machines cannot run steadily or efficiently without a well-functioning water system. But water-cooling systems are fairly complex and prone to many ills and failures. Some are acute and obvious, and some are more silent, creeping failures that slowly erode your plant's productivity.

Catastrophic failures

Abrupt cooling failures are often easiest to diagnose, but not necessarily so. The causes usually relate to issues of system design, equipment selection, or maintenance.

Flow failures are related to the water quality, system design, and pump configuration. Water quality is compromised by biological, chemical, and particulate par·tic·u·late
adj.
Of or occurring in the form of fine particles.

n.
A particulate substance.



particulate

composed of separate particles.
 contaminants introduced by the tower air and by minerals introduced by make-up water. The primary maintenance issue with pumps is seal replacement necessitated by water-quality problems. Prudent system design includes provision for back-up pumping--preferably a pump scheme that permits automatic transfer to the back-up pump to keep the system operating when a failure occurs. One solution is a "dual-arm" pump that incorporates two pumps in one casing.

It is also important to have a comprehensive understanding of the cooling system cooling system: see air conditioning; internal-combustion engine; refrigeration.
cooling system

Apparatus used to keep the temperature of a structure or device from exceeding limits imposed by needs of safety and efficiency.
 design. Often, the system fails because a valve operates incorrectly. It either opens when it shouldn't, or it may open too far, or not far enough. A valve may operate accidentally or even fail internally. Regardless, you will need to have a complete system drawing with valves and components identified and their locations noted for quick reference.

Water-quality problems can cause clogged filters and foul heat-transfer surfaces. Filters should be checked regularly or equipped with alarms to indicate cleanliness.

The most exciting flow problem is a burst pipe. If a main header bursts, the system can empty quickly, inundating operators and equipment. The failure is easy to see. It is normally much harder to identify the cause. Most often it is lack of proper support, such as a hanger failure. All piping must be supported to minimize stress. In addition, some pipe materials are more susceptible to failure than others. Welded steel lines are stronger and more resistant to fatigue from "water hammer Water hammer

The propagation in a liquid of an acoustic wave that is caused by a rapid change in fluid velocity. Such relatively sudden changes in the liquid velocity are due to events such as the operation of pumps or valves in pipelines, the collapse of
" (transient pressure spikes) than plastic lines. However, steel corrodes and plastic doesn't. The answer to this dilemma is to operate your system with procedures that prevent water hammer.

Chiller chill·er  
n.
1. One that chills.

2. A frightening story, especially one involving violence, evil, or the supernatural; a thriller.


chiller
Noun

1.
 failures are usually related to the condenser condenser

Device for reducing a gas or vapour to a liquid. Condensers are used in power plants to condense exhaust steam from turbines and in refrigeration plants to condense refrigerant vapours, such as ammonia and Freons.
. One of the most common air condenser problems is a fan failure. If unit is air condensed con·dense  
v. con·densed, con·dens·ing, con·dens·es

v.tr.
1. To reduce the volume or compass of.

2. To make more concise; abridge or shorten.

3. Physics
a.
, the air stream may be blocked by the location of the condenser. Or perhaps an air filter is clogged or the wafer-thin coil fins are bent over from rough handling.

Water condensers can fail when there is insufficient water flow to remove the heat from the refrigerant re·frig·er·ant
adj.
1. Cooling or freezing; refrigerating.

2. Reducing fever.

n.
1. A substance, such as air, ammonia, water, or carbon dioxide, used to provide cooling either as the working substance of
. The cause is often a leak or blockage blockage

of intestine, urethra, etc. See obstruction under anatomical location, e.g. intestinal, urethral.

blockage Wax, see there
 of the condenser water supply--possibly by a malfunctioning mal·func·tion  
intr.v. mal·func·tioned, mal·func·tion·ing, mal·func·tions
1. To fail to function.

2. To function improperly.

n.
1. Failure to function.

2.
 valve--or else the condensing con·dense  
v. con·densed, con·dens·ing, con·dens·es

v.tr.
1. To reduce the volume or compass of.

2. To make more concise; abridge or shorten.

3. Physics
a.
 water may be too warm.

In either case, the "High Pressure" safety switch will be actuated ac·tu·ate  
tr.v. ac·tu·at·ed, ac·tu·at·ing, ac·tu·ates
1. To put into motion or action; activate: electrical relays that actuate the elevator's movements.

2.
. The cause must be corrected before you manually reset the switch.

A "Low Pressure" refrigerant alarm is an indication that the compressor does not have sufficient gas available to compress into the condenser. There are various possible causes but usually the problem is a refrigerant leak. In any event, low refrigerant pressure will require a qualified technician to locate and repair the problem. "Low Pressure" alarms can reset automatically without operator action, making it likely that the alarm will recur when operation continues.

Chiller compressor failure is rare but can be predicted by observing the system's operation. Frequent on/off cycling of the compressor usually precedes failure. The true cause may not be the compressor but the control system or other system components. This problem will require professional technical assistance. Note that a low load or a chiller too large for the application can lead to premature compressor failure from frequent on/off cycling.

Tower failures are mostly related to the fan drive and bearings. Proper maintenance requires periodic inspection, belt tensioning, and bearing lubrication lubrication, introduction of a substance between the contact surfaces of moving parts to reduce friction and to dissipate heat. A lubricant may be oil, grease, graphite, or any substance—gas, liquid, semisolid, or solid—that permits free action of . Other tower failure modes are related to water flow. The incoming warm water is usually directed into the "fill" of the tower by flow nozzles. They can become clogged or dislodged. It is important to recognize that the tower internal element, the "fill," cannot withstand contact with hot water. A water temperature over 140 F will require a special design. Otherwise, you could cause catastrophic failure of the "fill" very quickly.

Tower water chemistry is critical to long-term reliability. Use a certified water-conditioning service to maintain your water quality.

Performance failures

Catastrophic system failures are easy to recognize and the corrective measures are relatively predictable and straightforward. More frustrating frus·trate  
tr.v. frus·trat·ed, frus·trat·ing, frus·trates
1.
a. To prevent from accomplishing a purpose or fulfilling a desire; thwart:
 cooling-system woes occur when the process performance degrades gradually due to less-obvious cooling-system issues. It is imperative to be prepared with proper diagnostic tools before the inevitable problems occur.

It is a good policy to have a cooling system review and consultation before failures occur. The system troubleshooter must have a comprehensive knowledge of the cooling system. Some system suppliers offer engineering services such as engineering drawings of the cooling system (see accompanying example), as well as employee training and operating instructions.

Undersized undersized

see dwarfism, runt.
 or oversized o·ver·size  
n.
1. A size that is larger than usual.

2. An oversize article or object.

adj. o·ver·size also o·ver·sized
Larger in size than usual or necessary.
 system components often cause or exacerbate problems. The system load needs to be tabulated to ascertain its cooling-capacity limits. A "load study" can be performed to calculate the heat loads associated with each molding machine (Woodworking) A planing machine for making moldings
(Founding) A machine to assist in making molds for castings.

See also: Molding Molding
 in the plant. Some processors find it valuable to keep periodic records of key system parameters for trend analysis and scheduling predictive maintenance Predictive maintenance (PdM) techniques help determine the condition of in-service equipment in order to predict when maintenance should be performed. This approach offers cost savings over routine or time-based preventive maintenance because tasks are performed only when .

Maintaining water quality is the best preventive measure you can take. Any contaminants in the water will degrade TO DEGRADE, DEGRADING. To, sink or lower a person in the estimation of the public.
     2. As a man's character is of great importance to him, and it is his interest to retain the good opinion of all mankind, when he is a witness, he cannot be compelled to disclose
 the cooling surfaces and reduce the heat capacity of the system. Reducing the oxygen content helps to reduce corrosion of metal surfaces. Proper water chemistry control and additives will also reduce the frequency of maintenance of heat-transfer surfaces. Strainers Water lines or kitchen systems can get gravel, deposits that break free, and other stray items in the line. The velocity of the water pushing them, they can severely damage or clog devices installed in the flow stream of the water line.  and filters can be used to reduce the suspended particle contamination in the water system and prevent potential damage to other components such as temperature controllers. Draining off "old" water and feeding in fresh make-up water will help reduce the mineral composition of the circulating fluid.

Jim Horne is systems project manager for Wittmann, Inc. in Torrington, Conn. He has more than 25 years of experience in plastics. He can be reached at (860)496-9603 or e-mail jhorne@wittmann-ct.com
COOLING SYSTEM WOES

Catastropic Failures

Flow Failures
   Pumps fail
   Valves not set properly
   Filters clog
   Pipe breaks or leaks

Chiller Failures
   Condenser off on high pressure
   Low-pressure ("freeze-stat") function actuates
   Loss of evaporator water flow
   Compressor faults
   Refrigeration gas loss

Tower Failures
   Fan stops
   Freeze-up
   Distributor flow blocked

Performance Failures

"Cycle Creep"
   Process window narrows
   Cycle times lengthen

Excess Variations in Setpoints
   Product quality variations
   Process instability
   Control instability

Reduced Heat Transfer
   Components "run hot"

Capacity Limitations
   Plant production capacity not attainable
   "End of circuit" phenomenon (last-machine syndrome)
   Plant expansion strains system capacity


Jim Horne

Wittmann, Inc.
COPYRIGHT 2005 Gardner Publications, Inc.
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2005, Gale Group. All rights reserved. Gale Group is a Thomson Corporation Company.

 Reader Opinion

Title:

Comment:



 

Article Details
Printer friendly Cite/link Email Feedback
Title Annotation:Troubleshooter: WATER COOLING
Author:Horne, Jim
Publication:Plastics Technology
Date:Jun 1, 2005
Words:1153
Previous Article:Large two-platen presses gain speed & flexibility.(Close-Up: INJECTION MOLDING)
Next Article:MIDs make a comeback: 3d molded interconnect devices were supposed to be the 1980s' breakthrough for plastics in electronics--but they flopped. New...



Related Articles
Full line extrusion equipment. (Infofile: Advertisement).
Liquid temperature-control equipment.(Product Lines Reviewed)
Industrial process cooling.(Equipment)
Liquid temperature-control equipment.(Product Lines Reviewed)
Close the loop on clean cooling water.(Process cooling: troubleshooter)
Liquid temperature-control equipment.(PRODUCT LINES REVIEWED)
Full line extrusion equipment.(Infofile)(Advertisement)
Heating & cooling.(What to See at NPE 2006)
'Fluid cooler' offers alternative to cooling towers or central chillers.(Close-Up: PROCESS COOLING)
Liquid temperature-control equipment.(PRODUCT LINES REVIEWED)

Terms of use | Copyright © 2009 Farlex, Inc. | Feedback | For webmasters | Submit articles