Characterization of a high-density data center.ABSTRACT This paper shows the results of a characterization of an 11,490 [ft.sup.2] (1067 [m.sup.2]) high-density data center, with focus on a zone with heat dissipation Noun 1. heat dissipation - dissipation of heat chilling, cooling, temperature reduction - the process of becoming cooler; a falling temperature greater than 8 kW and up to 26 kW per frame. To gain insight into the operational health, a data center survey is conducted. The purpose of the survey is to measure and collect data on power consumption, airflow, and temperature throughout the data center. The results are used to profile and validate the data center via a computational fluid dynamics Computational fluid dynamics The numerical approximation to the solution of mathematical models of fluid flow and heat transfer. Computational fluid dynamics is one of the tools (in addition to experimental and theoretical methods) available to solve (CFD CFD - Computational Fluid Dynamics ) model for detailed analysis. The methodology used in the study is similar to that of the National Center for Environmental Prediction (NCEP NCEP National Cholesterol Education Program ) data center case study (Schmidt 2004). INTRODUCTION High-density installations are planned based on published best practices, consultant advice, guidance from industry associations and organizations, as well as equipment manufacturer recommendations. Because of the choices available in the marketplace, every data center is different, from computer room air-conditioning (CRAC CRAC, n contract-relax, antagonist contract; a proprioceptive neuromuscular facilitation (PNF) technique that uses antagonist and agonist muscles to stretch and relax taut muscles. See also PNF. ) unit selection and placement to raised-floor height and perforated per·fo·ra·ted adj. Pierced with one or more holes. panel locations. While publications such as ASHRAE's Thermal Guidelines for Data Processing data processing or information processing, operations (e.g., handling, merging, sorting, and computing) performed upon data in accordance with strictly defined procedures, such as recording and summarizing the financial transactions of a Environments (ASHRAE ASHRAE American Society of Heating, Refrigerating & Air Conditioning Engineers 2004) provide a common set of guidelines for equipment placement and layout configurations, there is not a cookie cutter way to plan a high-density installation. Airflow in a high-density data center is complex and requires engineering analysis of the environment. However, the end goal is to provide the information technology (IT) equipment operating in the data center with the proper temperature and humidity at the air intake. Datacom Equipment Power Trends and Cooling Applications (ASHRAE 2005) provides power trends at the equipment level and tells how to use the trends when making infrastructure decisions. Many leading datacom equipment manufacturers offer equipment that tracks the heat load density trend. As needs for processing and storage increase to handle application growth and the footprint decreases due to technology compaction, air cooling a. 1. In devices generating heat, such as gasoline-engine motor vehicles, the cooling of the device by increasing its radiating surface by means of ribs or radiators, and placing it so that it is exposed to a current of air. Cf. Water cooling. is becoming increasingly challenging. The questions of when liquid cooling Liquid Cooling may refer to:
DATA CENTER GENERAL INFORMATION The data center profiled is San Diego San Diego (săn dēā`gō), city (1990 pop. 1,110,549), seat of San Diego co., S Calif., on San Diego Bay; inc. 1850. San Diego includes the unincorporated communities of La Jolla and Spring Valley. Coronado is across the bay. Super Computer (SDSC SDSC San Diego Supercomputer Center SDSC Singapore Disability Sports Council SDSC Strategic and Defense Studies Center (Australia) SDSC Switched Data Service Center (Sprint) ) located on the University of California The University of California has a combined student body of more than 191,000 students, over 1,340,000 living alumni, and a combined systemwide and campus endowment of just over $7.3 billion (8th largest in the United States). San Diego campus. The data center area based on the drawing is 88 x 140 ft (26.8 x 42.7 m). However, the area usable for CRAC units, power distribution panels, and IT equipment is 11,490 [ft.sup.2] (1067 [m.sup.2]). Figure 1 shows an overall plan view with the zone considered for further investigation outlined. The IT equipment installed in the outlined zone is 7039-651 IBM eServer This article is about the IBM family of computer servers. For the open access electronic text archive, see EServer.org. IBM eServer was a family of computer servers from IBM Corporation. pSeries 655 Server Model 651, IBM eServer pSeries 690, and 7045-SW4 IBM eServer pSeries High Performance Switch (HPS See Seer*HPS. ) Model SW4. The data center slab-to-slab height is 16 ft (4.9 m) broken down as follows: 2 ft (0.6 m) concrete subfloor to raised floor, 10 ft (3.0 m) raised floor to suspended ceiling, and 4 ft (1.2 m) above the suspended ceiling. Selected ceiling panels are removed in the hot aisles to facilitate IT equipment exhaust air to the CRAC units with return duct extensions, as shown in Figure 2. The CRAC units also have turning vanes installed. [FIGURE 1 OMITTED] [FIGURE 2 OMITTED] A pseudo Similar to; made up to appear like something else. See pseudo compiler, pseudo language and pseudonymous. (jargon) pseudo - /soo'doh/ (Usenet) Pseudonym. 1. An electronic-mail or Usenet persona adopted by a human for amusement value or as a means of avoiding negative arrangement of hot aisle/cold aisle is used throughout the data center with varying aisle pitch (distance from the center of one cold aisle to the center of the next cold aisle), ranging from 7 to 10 raised floor panels. All panels are 2 x 2 ft (0.6 x 0.6 m). The perforated raised floor panels are estimated to be 22% open based on the diameter of each hole and the hole pattern. There are several underfloor blockages from insulated in·su·late tr.v. in·su·lat·ed, in·su·lat·ing, in·su·lates 1. To cause to be in a detached or isolated position. See Synonyms at isolate. 2. chilled-water supply and return pipes as well as from cable bundles and cable trays A cable tray system, according to the US National Electrical Code, is "a unit or assembly of units or sections and associated fittings forming a rigid structural system used to securely fasten or support cables and raceways." Cable trays are used to hold up and distribute cables. (see Figures 3 and 4). MEASUREMENT TOOLS Airflow through the perforated panels is measured with an Alnor Balometer Capture Hood. Because the capture hood obstructs the airflow from the perforated panel, the readings must be adjusted by a correction factor. However, the Alnor capture hood has a built-in back pressure compensation feature, via a flap, that accounts for the flow impedance of the capture hood. The feature is used for every measured perforated panel. Measurement accuracy based on the manufacturer's specification sheet is [+ or -]3% of the airflow reading. Cable cutouts are measured with an Extech wind vane wind vane: see weather vane. with anemometer anemometer: see wind. anemometer Instrument for measuring the speed of airflow. The most familiar instruments for measuring wind speeds are the revolving cups that drive an electric generator (useful range approximately 5–100 knots). . Measurement accuracy based on the manufacturer's data sheet is [+ or -]2% of the velocity reading. Temperature measurements of the IT equipment air intakes are made with an Omega Model HH23 Digital Thermometer thermometer, instrument for measuring temperature. Galileo and Sanctorius devised thermometers consisting essentially of a bulb with a tubular projection, the open end of which was immersed in a liquid. with type-T thermocouple. Measurement accuracy based on the manufacturer's product specification is [+ or -]0.1% of the temperature reading. All test equipment cited is calibrated cal·i·brate tr.v. cal·i·brat·ed, cal·i·brat·ing, cal·i·brates 1. To check, adjust, or determine by comparison with a standard (the graduations of a quantitative measuring instrument): on a yearly basis to ISO/IEC ISO/IEC International Organization for Standardization/International Electrotechnical Commission (ITU-T M 3000) Standard 17025 (ISO/IEC 2005). All voltage and current measurements are provided by the staff at SDSC. The amperage amperage strength of an electric current in amperes or milliamperes. data by circuit supplied by SDSC is measured with a Fluke fluke, parasitic flatworm of the trematoda class, related to the tapeworm. Instead of the cilia, external sense organs, and epidermis of the free-living flatworms, adult flukes have sucking disks with which they cling to their hosts and an external cuticle that T5-600 electrical tester and Fluke 33 clamp meter A clamp meter (clamp-on ammeter) is a type of ammeter which measures electrical current without the need to disconnect the wiring through which the current is flowing. . The instruments are not calibrated, but the input power to several frames is checked. A laptop with custom communications software (communications, software) communications software - Application programs, operating system components, and probably firmware, forming part of a communication system. These different software components might be classified according to the functions within the Open Systems is connected to an interface on the frame and the percent difference is less than 5%. [FIGURE 3 OMITTED] [FIGURE 4 OMITTED] MEASUREMENT METHODOLOGY AND RESULTS Power Measurements The heat load of the data center, including the IT equipment, CRAC units, and lighting, is collected on site with the help of SDSC personnel. The IT equipment in the data center is supplied by 208 V AC, either three-phase or line-to-line, and 120 V AC line-to-neutral. The CRAC units are supplied with 480 V AC line-to-line. Table 1 shows a breakdown of the power dissipation Dissipation See also Debauchery. Breitmann, Hans lax indulger. [Am. Lit.: Hans Breitmann’s Ballads] Burley, John wasteful ne’er-do-well. [Br. Lit. . The CRAC units have a range of heat output that seems to vary significantly and requires further investigation. The heat output of the IT equipment is calculated from the sum of the amperages multiplied by the associated mains connection. The result is volt-amps (VA), but a power factor of 0.95 is provided by SDSC to determine the watts, as most IT equipment has active mitigation to comply with the harmonics emissions standard 61000-3-2 (ISO/IEC 2005). However, it is important to note that all the IBM (International Business Machines Corporation, Armonk, NY, www.ibm.com) The world's largest computer company. IBM's product lines include the S/390 mainframes (zSeries), AS/400 midrange business systems (iSeries), RS/6000 workstations and servers (pSeries), Intel-based servers (xSeries) p690 and p655 three-phase servers, which are a significant load in the data center and are not within the scope of 61000-3-2, include active mitigation and have a power factor very close to one. Table 2 shows a breakdown of the zone with the high-density servers A server that contains a large number of CPUs, each of which may be hot swapped in and out on its own printed circuit board. See blade. . The numbers in parentheses See parenthesis. parentheses - See left parenthesis, right parenthesis. are the pieces of IBM hardware. The maximum error in the total heat load is estimated to be [+ or -]5%. Several p655s are measured directly at the frame through a communications interface on the bulk power system. The measurements compare favorably to the data from the power panels, although the power panels are consistently higher by less than 5%. This result is most likely due to measurement error with noncalibrated instruments and distribution losses. Airflow Measurements and Modeling There is a total of 12 Liebert Deluxe System/3 chilled-water CRAC units installed on the raised floor. Table 3 provides the manufacturer's specifications on each of the individual CRAC units. The sensible cooling is calculated based on a return air temperature of 73[degrees]F (23[degrees]C) dry bulb, a return air relative humidity relative humidity n. The ratio of the amount of water vapor in the air at a specific temperature to the maximum amount that the air could hold at that temperature, expressed as a percentage. of 37%, a supply water temperature of 41[degrees]F (5[degrees]C), and a return water temperature to the chiller chill·er n. 1. One that chills. 2. A frightening story, especially one involving violence, evil, or the supernatural; a thriller. chiller Noun 1. of 53[degrees]F (12[degrees]C). The return air data are collected from the Liebert monitoring system and averaged, as the temperature and humidity sensors are located in various locations as shown in Table 3. The method used to measure airflow through each CRAC unit for the NCEP data center could not be used because of the return duct extensions, and there was not enough time during our study to do a rectangular duct velocity traverse via the equal area or the log Tchebycheff method (Richardson 2001). However, the results from a computational fluid dynamics (CFD) simulation tool for airflow and temperature distribution in raised-floor environments indicate that the actual airflow is within the measurement tolerance to the manufacturer-specified airflow. The CFD results will be discussed at the end of this section. The data center has a total of 233 perforated panels. The total open area is 200 [ft.sup.2] (18.6 [m.sup.2]) based on 22% open perforated panels. Each perforated panel is measured via the Alnor capture hood with back pressure compensation, and the airflow is recorded. The total volumetric volumetric /vol·u·met·ric/ (vol?u-met´rik) pertaining to or accompanied by measurement in volumes. vol·u·met·ric adj. Of or relating to measurement by volume. airflow from the 233 perforated panels is 99,947 cfm (2830 [m.sup.3]/min). The data center also has a total of 306 cutouts used for power and communications cable Communications cable A cable that transmits information signals between geographically separated points. The heart of a communications cable is the transmission medium, which may be optical fibers, coaxial conductors, or twisted wire pairs. routing. The open area of each opening is measured and adjusted for the estimated cable blockage blockage of intestine, urethra, etc. See obstruction under anatomical location, e.g. intestinal, urethral. blockage Wax, see there . The total open area is 92 [ft.sup.2] (8.5 [m.sup.2]) Because of time constraints In law, time constraints are placed on certain actions and filings in the interest of speedy justice, and additionally to prevent the evasion of the ends of justice by waiting until a matter is moot. , only 17 openings are measured using the anemometer with wind vane. The data collected on the CRAC units, perforated panels, and cutouts during the study are used to build a CFD model and to compare the results to the measurements. In addition, significant underfloor blockages from cable trays and cable bundles as well as chilled-water supply and return lines are added to the model. Also, the data center is spot checked for perimeter openings in the raised-floor cavity. None are revealed, but an exhaustive review is not done. Finally, the distributed leakage area of air between perforated panels is estimated to be 0.2% based on the average width of the gaps between floor panels. Typical percent leakage area values can range from 0.1% to 0.2%, but it can be as high as 0.35% (Radmehr et al. 2005). The model is run several times with different distributed leakage values to arrive at an acceptable comparison between measured and predicted values. However, the leakage may be larger than assumed since the data center has been in existence for some time and there are areas of high static pressure, as high as 0.094 inch of water gauge (w.g.) (0.023 kPa). All in all, there is only a 1.7% difference in total cfm between the measured and simulated airflow. Figure 5 shows the measured versus modeled results on a perforated panel-by-panel basis. The average static pressure for the entire raised floor is 0.048 in. w.g. (0.012 kPa). Initial runs of the model showed some wide excursions because of dampers that are used on some of the perforated panels. Since the measured airflow rates are available and the pressure drop usually varies as the square of the airflow rate, it is possible to refine the model. The additional airflow resistance is entered in the polynomial polynomial, mathematical expression which is a finite sum, each term being a constant times a product of one or more variables raised to powers. With only one variable the general form of a polynomial is a0xn+a expression for a particular perforated panel and the model is rerun re·run n. The act or an instance of rebroadcasting a recorded movie or a recorded television performance. tr.v. re·ran , re·run, re·run·ning, re·runs To present a rerun of. . The airflow from the perforated panels in row AA, closest to the CRAC units CCU CCU abbr. 1. coronary care unit 2. critical care unit CCU critical care unit. CCU Critical care unit, see there 8-12, shows the largest discrepancy between measured and modeled values, but perforated panels in adjacent rows show good correlation. A comparison of the cutouts shows good correlation between measured and modeled openings less than 25 [in..sup.2] (161 [cm.sup.2]). The percent difference is less than 15%. The larger cutout cut·out n. 1. Something cut out or intended to be cut out from something else. 2. Electricity A device that interrupts, bypasses, or disconnects a circuit or circuit element. 3. comparison shows that the predicted volumetric airflow is significantly higher than the measured airflow. The reason for the discrepancy most likely has to do with the measurement technique. Regardless of the size of the cutout, three measurements are taken to obtain data in the shortest amount of time. Because the wind vane area is 5 [in..sup.2] (32 [cm.sup.2]), it is very difficult to obtain a representative linear airflow with three readings of a large opening, say 100 [in..sup.2] (645 [cm.sup.2]), before integrating over the area. [FIGURE 5 OMITTED] Temperature Measurements Temperatures are logged at the air intakes of the frames in the outlined zone shown in Figure 1. A single temperature reading is captured for each frame at a height of 68.9 in. (1750 mm) and in accordance with ASHRAE (2004) Thermal Guidelines for Data Processing Environments guidelines of 2 in. (50 mm) in front of the covers. The temperature of the air exiting each perforated panel is measured by the capture hood and recorded. The return air to the CRAC units could not be easily measured because of the return duct extensions. Instead, the CRAC sensor data are recorded. HIGH-DENSITY ANALYSIS The gross density of air-conditioning capacity is 138 W/[ft.sup.2] (1485 W/[m.sup.2]) and the current heat load density is 132 W/[ft.sup.2] (1421 W/[m.sup.2]). Although this information is not particularly useful in the overall operational health evaluation, as it does not indicate airflow distribution problems, hot spots hot spots acute moist dermatitis. , etc., gross W/[ft.sup.2] (W/[m.sup.2]) is commonly used by real estate operation personnel in figuring data center costs. Table 4 gives a view of the total airflow in the data center with estimated accuracy. Table 4 shows that approximately half of the airflow in the data center is from cutouts and leakage. Although there may be some benefit to cooling of IT equipment, prior studies (Schmidt and Cruz 2002) show that the cutout air is heated by the IT exhaust air before returning to the IT air intakes. The frame power, airflow rates, and inlet temperatures for the zone outlined in Figure 1 are examined similarly to the NCEP data center profile. The zone is divided into three sections for further study. The environmental characteristics are charted in Figures 6-10, which show that the air intake temperatures are within or below the ASHRAE Class 1 recommended dry-bulb temperature The dry-bulb temperature is the temperature of air measured by a thermometer freely exposed to the air but shielded from radiation and moisture. In construction, it is an important consideration when designing a building for a certain climate. range of 68[degrees]F-77[degrees]F (20[degrees]C-25[degrees]C) regardless of frame power consumption and airflow rate through the IT equipment. Table 5 shows a correlation between average perforated panel supply airflow, cutout airflow, frame airflow, and frame temperature rise for a section and subsection. The average perforated panel supply airflow comes from the panels directly in front of the frames for this analysis, even though a cold aisle may be 4 ft (101.6 mm) wide. For comparison to the average frame airflow, the average perforated panel airflow is adjusted for the frame width of 1.25 panels. The frame airflows are as follows: 2960 cfm (84 [m.sup.3]/min) for the p655, 1100 cfm (31 [m.sup.3]/min) for the p690, and 800 cfm (23 [m.sup.3]/min) for the switch frames. The frame temperature rise is calculated based on the difference between the average temperature of the air exiting a given row of perforated panels and the aggregate return air temperature of the CRAC sensors within the vicinity of that row. Table 5 shows that the airflow rates from the perforated panels in front of the frames are much less than the frame airflow rates. Despite the imbalance in airflow, air intake temperatures are within or below ASHRAE Class 1 as shown in Figures 6-10. If the perforated panel and cutout adjacent to a frame are combined to provide the airflow, the calculated temperature rise based on average frame power is as shown in Table 6. The calculated temperature rise in Table 6 is higher than the actual temperature rise in Table 5 for each section. Therefore, the conclusion is the same as that for the NCEP data center--the migration of chilled air within the data center from zones of high density to zones of low density is occurring as the local chilled-airflow rates for the high-density frames are much lower than what might be considered adequate. AIRFLOW COMPARISON An airflow comparison is made between the actual airflow and a calculated airflow from the data center measured heat load and temperature difference. The actual airflow--based on perforated panel measurements, limited cable cutout measurements, and modeling--is 185,700 cfm (5258 [m.sup.3]/min) with an estimated accuracy of 10% derived from various simulation results. The actual airflow range is 167,130-204,270 cfm (4733-5784 [m.sup.3]/min). The average temperature difference from perforated panel temperature measurements and CRAC sensors is 59[degrees]F (15[degrees]C) with an estimated error of 10%. The total heat load accuracy is estimated to be [+ or -]5%. The calculated airflow is 177,664 cfm (5031 [m.sup.3]/min) with a range of 153,437-207,205 cfm (4345-5867 [m.sup.3]/min). There is good overlap in the actual and calculated airflow ranges; therefore, the comparison of the data is validated. SUMMARY The paper presents a detailed characterization of a high-density data center. On-site measurements of heat load, airflow, and temperature are measured and collected to study the data center. These parameters are used to build a CFD model and run simulations to provide detail on parameters, such as cutout and leakage airflow, that could not be captured during the study either because of time or physical constraints. The model is validated based on comparison between perforated panel measurements and the results of the model, as the total airflow percent difference is only 2%. An airflow comparison also confirms that the actual and calculated airflow are in agreement. The high-density area of the data center with IT equipment is studied. The key IT equipment health indicator is the inlet temperature, which is within or below the ASHRAE Class 1 guideline even though the sum of the perforated panel and cutout airflow rates is up to two-thirds less than the frame airflow rates. While the local conditions do not seem adequate to satisfy and maintain the air intake temperatures of the high-powered frames, the overall data center flow rate can handle the total data center heat load. However, as more high-density equipment is installed, there is a risk of locally elevated inlet temperatures even though there may be sufficient cooling capacity. The conclusion for SDSC and NCEP data centers are similar. ACKNOWLEDGMENTS The author would like to thank Dr. Roger Schmidt Dr. Roger Schmidt was the acting president of University of the West, a private, non profit, Buddhist-affiliated campus in Rosemead, California. He was replaced by Dr. Allen Huang in 2007. , Dr. Hendrik Hamann, Dane Miller, and Harald Zettl for their help with collection and interpretation of the data. The characterization and paper would not have been possible without their contribution. The author also thanks the staff at SDSC, especially Mike Datte and Jeff Filliez, for their full cooperation in allowing IBM to study the data center and publish the results. REFERENCES ASHRAE. 2004. Thermal Guidelines for Data Processing Environments. Atlanta: American Society of Heating, Refrigerating re·frig·er·ate tr.v. re·frig·er·at·ed, re·frig·er·at·ing, re·frig·er·ates 1. To cool or chill (a substance). 2. To preserve (food) by chilling. and Air-Conditioning Engineers, Inc. ASHRAE. 2005. Datacom Equipment Power Trends and Cooling Applications. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. [FIGURE 6 OMITTED] [FIGURE 7 OMITTED] [FIGURE 8 OMITTED] [FIGURE 9 OMITTED] [FIGURE 10 OMITTED] IEC (International Electrotechnical Commission, Geneva, Switzerland, www.iec.ch) An organization that sets international electrical and electronics standards founded in 1906. It is made up of national committees from over 60 countries. IEC - International Electrotechnical Commission . 2005. Electromagnetic Compatibility (hardware, testing) Electromagnetic Compatibility - (EMC) The extent to which a piece of hardware will tolerate electrical interference from other equipment, and will interfere with other equipment. (EMC (1) (EMC Corporation, Hopkinton, MA, www.emc.com) The leading supplier of storage products for midrange computers and mainframes. Founded in 1979 by Richard J. Egan and Roger Marino, EMC has developed advanced storage and retrieval technologies for the world's largest companies. ), Part 3-2: Limits--Limits for harmonic current emissions (equipment input current [left arrow (character) left arrow - The graphic which the 1963 version of ASCII had in place of the underscore character, ASCII 95. ] 16 A per phase). Geneva Geneva, canton and city, Switzerland Geneva (jənē`və), Fr. Genève, canton (1990 pop. 373,019), 109 sq mi (282 sq km), SW Switzerland, surrounding the southwest tip of the Lake of Geneva. , Switzerland: International Electrotechnical Commission See IEC. (standard, body) International Electrotechnical Commission - (IEC) A standardisation body at the same level as ISO. . ISO/IEC. 2005. General Requirements for the Competence of Testing and Calibration Laboratories. Geneva, Switzerland: International Organization for Standardization International Organization for Standardization (ISO) Organization for determining standards in most technical and nontechnical fields. Founded in Geneva in 1947, its membership includes more than 100 countries. . Radmehr, A., R. Schmidt, K. Karki, and S. Patankar. 2005. Distributed leakage flow in raised-floor data centers. Advances in Electronic Packaging 2005, Proceedings of IPACK 2005-73273, The ASME/Pacific Rim Technical Conference and Exhibition on Integration and Packaging of MEMS (MicroElectroMechanical Systems) Tiny mechanical devices that are built onto semiconductor chips and are measured in micrometers. In the research labs since the 1980s, MEMS devices began to materialize as commercial products in the mid-1990s. , NEMS n. 1. (Zool.) The ichneumon. , and Electronic Systems, pp. 401-08. Richardson, G. 2001. Traversing for accuracy in a rectangular duct. Associated Air Balance Council TAB Journal, summer 2001 Issue, pp. 20-27. Schmidt, R. 2004. Thermal profile of a high-density data center--Methodology to thermally characterize a data center. ASHRAE Transactions 110(2):635-42. Schmidt, R., and E. Cruz. 2002. Raised-floor computer data center: Effect on rack inlet temperatures of exiting both the hot and cold aisle. Thermomechanical Phenomena in Electronic Systems, Proceedings of the Intersociety Conference, 2002, pp. 580-94. Joseph F. Prisco, PE Joseph F. Prisco is a senior engineer with IBM, Rochester, MN.
Table 1. Total Data Center Power Dissipation
CRAC kW kW
CCU1 15.8
CCU2 23.3
CCU3 7.5
CCU4 7.3
CCU5 8.1
CCU6 14.1
CCU7 10.0
CCU8 10.8
CCU9 14.1
CCU10 10.8
CCU11 14.1
CCU12 19.1
CRAC Power 155.0
Lights 15.0
Power Panels
CL1U 426.2
U3 55.5
RDC 595.7
U4 175.7
SATA 53.1
GG 39.5
1345.7
Total Power Consumption 1515.8
Table 2. Select IT Power Dissipation
IT Equipment kW
p690 (11) 91.4
p655 (18) 420.9
HPS (6) 46.3
Total Power Consumption 558.6
Table 3. CRAC Unit Detail
Sensible
CRAC Unit Number cfm Cooling (kW) Sensor Location
MHB-CCU01 16,500 142 Power Pillar 56
MHB-CCU02 16,500 142 Power Pillar 56
MHB-CCU03 12,400 102 Return Duct
Extension
MHB-CCU04 12,400 102 Return Duct
Extension
MHB-CCU05 12,400 102 Return Duct
Extension
MHB-CCU06 16,500 142 Power Pillar 20
MHB-CCU07 16,500 142 Backside Power
Pillar 54
MHB-CCU08 16,500 142 Backside Power
Pillar 54
MHB-CCU09 16,500 142 Return Duct
Extension
MHB-CCU010 16,500 142 Backside Power
Pillar 54
MHB-CCU011 16,500 142 Return Duct
Extension
MHB-CCU012 16,500 142 Power Pillar 20
Total 185,700 1584
Table 4. Data Center Airflow
Airflow cfm Notes Accuracy
Total volumetric flow 185,700 Liebert 10%
specifications
Perforated panels 99,947 Measured 5%
Cut-outs 75,156 Calculated with 15%
approx. blockages
Leakage 10,597 0.2% distributed
area in the model 5%
Table 5. Section Analysis of Airflow and Temperature Rise
Average Average Average
Perforated Cut-Out Frame Average Frame
Panel Airflow, Airflow, Airflow, Temperature
Section Number cfm cfm cfm Rise, [degrees]C
1 645 762 2420 12.9
2(1) 672 386 2077 12.0
2(2) 816 189 2960 12.4
3(1) 390 182 1100 11.4
3(2) 537 584 1025 11.7
Table 6. Calculation of Average Frame Temperature Rise
Calculated
Average Perforated Average Frame Average Frame
Panel and Cut-Out Power Temperature
Section Number Airflow, cfm Consumption, kW Rise, [degrees]C
1 1408 19.0 23.8
2(1) 1057 17.8 29.6
2(2) 1005 19.7 34.5
3(1) 571 8.7 26.7
3(2) 1121 8.6 13.5
|
|
||||||||||||||||

Printer friendly
Cite/link
Email
Feedback
Reader Opinion