Binary enthalpy wheel humidification control in dedicated outdoor air systems.


INTRODUCTION

Dedicated outdoor air systems (DOAS DOAS Department of Administrative Services
DOAS Differential Optical Absorption Spectroscopy
DOAS Death of A Salesman (book/play)
DOAS Differential Optical Absorption Spectrometer
DOAS Default Option-Adjusted Spread
) (Mumma 2001), when used, are generally required to employ total energy recovery, or an enthalpy enthalpy (ĕn`thălpē), measure of the heat content of a chemical or physical system; it is a quantity derived from the heat and work relations studied in thermodynamics.  wheel (EW), by ANSI/ASHRAE/IESNA Standard 90.1-2004, Energy Standard for Buildings Except Low-Rise Residential Buildings (ASHRAE ASHRAE American Society of Heating, Refrigerating & Air Conditioning Engineers  2004b). The enthalpy wheel transfers excess moisture and sensible heat Sensible heat is potential energy in the form of thermal energy or heat. The thermal body must have a temperature higher than its surroundings, (also see: latent heat). The thermal energy can be transported via conduction, convection, radiation or by a combination thereof.  contained in the outdoor airstream to the relatively dry and cool exhaust airstream during the summer (i.e., precooling and dehumidification). Similarly, the entering outdoor air (OA) is heated and humidified during the winter by recovering sensible heat and moisture from the relatively warm and humid exhaust air. This free heating and humidification Humidification

The process of increasing the water-vapor content (humidity) of a gas. This process and its reverse operation, dehumidification, are important steps in air conditioning for human comfort and in many industrial operations.
 is the advantage that should not be overlooked in the EW application. However, observed systems with EWs have often not utilized the EW to maximum benefit, particularly during periods of low ambient dew-point temperatures (DPTs). When the OA is dry, humidification of the supply air (SA) is required to maintain the space relative humidity relative humidity
n.
The ratio of the amount of water vapor in the air at a specific temperature to the maximum amount that the air could hold at that temperature, expressed as a percentage.
 (RH)--a key health and thermal comfort Human thermal comfort is the state of mind that expresses satisfaction with the surrounding environment, according to ASHRAE Standard 55. Achieving thermal comfort for most occupants of buildings or other enclosures is a goal of HVAC design engineers.  factor in buildings. ANSI/ASHRAE Standard 55-2004, Thermal Environmental Conditions for Human Occupancy (ASHRAE 2004a), recommends that the RH be maintained in the 30%-60% range.

Most technical literature on EWs is focused on their operation as an aid during cooling to reduce both the design load and energy use. Consequently, no simple and universally accepted EW humidification performance control sequence currently exists for low DPT OA conditions, hereafter referred to as dry conditions. The objective of this paper is first to justify the use of the EW for humidification under dry conditions, then introduce a simple binary EW control. The EW binary control was evaluated in a university campus facility (Mumma and Jeong 2005).

Enthalpy Wheel Overview

In the mid 1970s, two EW products were introduced to the HVAC (Heating Ventilation Air Conditioning) In the home or small office with a handful of computers, HVAC is more for human comfort than the machines. In large datacenters, a humidity-free room with a steady, cool temperature is essential for the trouble-free  industry. One was the oxidized oxidized

having been modified by the process of oxidation.


oxidized cellulose
see absorbable cellulose.
 aluminum wheel made of corrugated cor·ru·gate  
v. cor·ru·gat·ed, cor·ru·gat·ing, cor·ru·gates

v.tr.
To shape into folds or parallel and alternating ridges and grooves.

v.intr.
 aluminum foil Noun 1. aluminum foil - foil made of aluminum
aluminium foil, tin foil

foil - a piece of thin and flexible sheet metal; "the photographic film was wrapped in foil"
. The corrugated aluminum foil assembly is dipped into a bromide bromide, any of a group of compounds that contain bromine and a more electropositive element or radical. Bromides are formed by the reaction of bromine or a bromide with another substance; they are widely distributed in nature.  solution to cause the aluminum to oxidize oxidize /ox·i·dize/ (ok´si-diz) to cause to combine with oxygen or to remove hydrogen.

ox·i·dize
v.
1. To combine with oxygen; change into an oxide.

2.
 and form a layer of alumina alumina (əl`mĭnə) or aluminum oxide, Al2O3, chemical compound with m.p. about 2,000°C; and sp. gr. about 4.0. , a known desiccant desiccant /des·ic·cant/ (des´i-kant)
1. promoting dryness.

2. an agent that promotes dryness.


des·ic·cant
n.
. The second EW product introduced then used silica gel silica gel, chemical compound. It is a colloidal form of silica, and usually resembles coarse white sand. It may be prepared by partial dehydration of metasilicic acid, H2SiO3. Because it has many tiny pores, it has great adsorptive power.  as the desiccant. The silica gel desiccant was bonded to an aluminum foil assembly, or matrix.

In the 1980s, molecular sieves, also known as synthetic zeolite zeolite

Any member of a family of hydrated aluminosilicate minerals that have a framework structure enclosing interconnected cavities occupied by large metal cations (positively charged ions)—generally sodium, potassium, magnesium, calcium, and barium—and water
 desiccants A desiccant is a substance that absorbs water. It is most commonly used to remove humidity that would normally degrade or even destroy products sensitive to moisture.

See also:
, that could be designed at the molecular level emerged. Fabrication fabrication (fab´rikā´shn),
n the construction or making of a restoration.
 of silica and other compounds were derived from the semiconductor industry. Manufacturing processing advances that allowed a breathable breath·a·ble  
adj.
1. Suitable or pleasant for breathing: breathable air.

2. Permitting air to pass through: a breathable fabric.
 layer of desiccant to be bonded to the corrugated aluminum foil surface made molecular sieve EWs possible.

The type of desiccant used determines the moisture transfer performance of the EW, while the sensible heat transfer of the wheel depends on the thermal properties of the matrix-desiccant material combinations. Currently the vast majority of EWs employ either silica gel or molecular sieve desiccants.

Silica Gel. Silica gel can absorb up to 40% of its own weight in water and withstand relatively high acidic environments. Because of its good water vapor adsorption adsorption, adhesion of the molecules of liquids, gases, and dissolved substances to the surfaces of solids, as opposed to absorption, in which the molecules actually enter the absorbing medium (see adhesion and cohesion).  characteristic, or sorption isotherm A sorption isotherm is a stochastic model of the sorption behaviour of a chemical entity which depicts the partitioning between sorbed phase and dissolved phase. See also
  • Freundlich equation
References
  • http://jan.ucc.nau.
, over a wide range of relative humidities, silica gel is a highly favored solid desiccant. In addition, it has no known toxic properties. However, the adsorption capacity of silica gel decreases significantly with increasing temperature. Strong alkalis (e.g., ammonia) degrade silica gel.

Molecular Sieves. Molecular sieves have an equilibrium capacity of up to 20% by weight water. Molecular sieves have no known toxic properties, but exposure to air with high concentrations of strong acids can be harmful.

ENTHALPY WHEEL HUMIDIFICATION

EW control, in HVAC applications in general and DOAS specifically, has been addressed in the open literature (Mumma 2001). When humidity control Humidity control

Regulation of the degree of saturation (relative humidity) or quantity (absolute humidity) of water vapor in a mixture of air and water vapor. Humidity is commonly mistaken as a quality of air.
 is addressed during dry conditions, the literature calls for the EW speed to be modulated mod·u·late  
v. mod·u·lat·ed, mod·u·lat·ing, mod·u·lates

v.tr.
1. To adjust or adapt to a certain proportion; regulate or temper.

2.
 as necessary to maintain a DPT setpoint, then sensibly heat or cool the air as necessary by a variety of methods. However, modulation of an EW to maintain the supply air DPT setpoint in the dry condition can lead to surprises. The EW total, sensible, and latent effectivenesses (ratio of actual heat transfer to that of an infinite area counterflow heat exchanger heat exchanger

Any of several devices that transfer heat from a hot to a cold fluid. In many engineering applications, one fluid needs to be heated and another cooled, a requirement economically accomplished by a heat exchanger.
) at design operating speeds are generally all about the same. However, at reduced speeds, the effectiveness of each component drops, with the latent effectiveness dropping faster than the sensible (Stiesch et al. 1995). In some wheel designs, this can lead to an unexpected increase in the subsequent sensible cooling load.

Consequently, some researchers (Simonson and Besant 1999) indicated that the wheel rotating speed is impractical to use as a control parameter. Another surprise is the degree of speed control sensitivity required to meet a target DPT, since the majority of the effectiveness reduction generally occurs in the lowest 20% of the wheel speed modulation where the gain is very high. Finally, some EWs exhibit a negative latent effectiveness at speeds of 0-2 rpm (Simonson et al. 2000a). These potentially surprising performance traits are a result of the complex and highly nonlinear heat and mass transfer characteristics of the EW.

Wheel bypass control (Simonson et al. 2000b) may also be used to modulate the EW effectiveness. In this approach, the SA condition is maintained by mixing OA preconditioned by the EW rotating at full speed with unconditioned unconditioned /un·con·di·tion·ed/ (un?kon-dish´und) not a result of conditioning; unlearned; occurring naturally or spontaneously.  OA bypassed around the EW. This approach overcomes some of the surprises discussed above, but EW face and bypass dampers add considerably to the size of the already large equipment. It also introduces stratified stratified /strat·i·fied/ (strat´i-fid) formed or arranged in layers.

strat·i·fied
adj.
Arranged in the form of layers or strata.
 air that can lead to coil freeze-up problems.

Confronted with the surprises discussed above, the authors will suggest a simple and effective way to overcome them by using a binary (ON or OFF) control of the EW when used for humidification during operation in the dry condition.

Enthalpy Wheel Humidification Example

Before discussing the binary EW control issues, the following example is presented in an effort to provide an understanding of the performance, energy, and cost associated with using the EW for humidification in dry conditions. For the example, assume the following:

* Internally load-dominated building with 100 people (standing), assumed latent load 250 Btu/h*person (73.3 W/person). Building design latent load 25,000 Btu/h (7.3 kW).

* 2000 cfm (940 L/s) OA ventilation for the building.

* Room design condition 72[degrees]F (22[degrees]C) dry bulb temperature (DBT DBT Department of Biotechnology (India)
DBT Dibenzothiophene
DBT Drive-By Truckers (band)
DBT Design Basis Threat
DBT Deutscher Bundestag (German Parliament) 
), 30% RH. This corresponds to a humidity ratio (W) of 35 gr/[lbm.sub.DA] (5.0 g/[kg.sub.DA]) and an enthalpy (h) of 22.7 Btu/[lbm.sub.DA] (35 kJ/[kg.sub.DA]).

Consider a dry OA condition of 55[degrees]F (12.8[degrees]C) and 20% RH (W = 12.8 gr/[lbm.sub.DA] [1.8 g/[kg.sub.DA]], h = 15.2 Btu/[lbm.sub.DA] [17.4 kJ/[kg.sub.DA]]). Under these conditions, the latent load would cause the humidity ratio of the DOAS supply air to increase by 18.4 gr/[lbm.sub.DA] (2.6 g/[kg.sub.DA]) as it passed through the space. Without humidification, the resulting room RH would be 26.7%. In order to get the humidity up to 30%, assuming an EW effectiveness of 80%, the EW would need to operate at a very slow modulating speed to achieve an effectiveness of only 17% or operate at full speed 21% of the time. The psychrometrics of the process are illustrated in Figure 1, and a moisture mass balance is illustrated in Figure 2.

[FIGURE 1 OMITTED]

[FIGURE 2 OMITTED]

If the building occupancy were to drop to 25%, with the same dry OA condition, the 25 occupants would cause the space RH to be only 15%. At the lower limit, with no occupant moisture addition, the space RH would be 11%, with or without the EW, assuming no auxiliary humidification. In order to bring the building RH up to 30% when 25% occupied, the EW effectiveness would need to be 79%. Under these conditions, an 80% effective EW would be operating at full speed continually. Sample operating costs operating costs nplgastos mpl operacionales , for this reduced occupancy condition, will be considered next.

For the sample operating cost analysis, the following assumptions will be made:

* Chiller chill·er  
n.
1. One that chills.

2. A frightening story, especially one involving violence, evil, or the supernatural; a thriller.


chiller
Noun

1.
 electrical consumption rate: 0.7 kW/ton (5.0 COP)

* Electricity, $0.08/kWh or $23.50/million Btu ($0.022 MJ)

* Efficiency of a gas heating plant to produce steam for humidification, 80%

* Gas, $14.00/million Btu ($0.013/MJ)

The 80% effective EW would elevate the 55[degrees]F (12.8[degrees]C) SA temperature to 70.9[degrees]F (21.6[degrees]C), which would subsequently need to be cooled back down to 55[degrees]F (12.8[degrees]C). That chiller load from 2000 cfm (940 L/s) of air is 2.85 tons, which would cost $0.16 per hour to operate. The humidification would be accomplished via the EW.

If a steam humidifier humidifier,
n a device for adding moisture to dry air inside the home to help counteract the reduction in saliva that often occurs as a result of hyposalivation, radiation therapy, or other treatments that cause xerostomia.
, rather than an EW, had been used to humidify the OA, the supply air humidity ratio would have to be elevated with the humidifier from 12.8 gr/[lbm.sub.DA] (1.8 g/[kg.sub.DA]) to 30.4 gr/[lbm.sub.DA] (4.3 g/[kg.sub.DA]), which would cost $0.42 per hour. In this example, humidification with the steam humidifier cost 220% more than it would to use the EW and sensibly cool.

It may be noted that for the example OA and space conditions, the ratio of humidifier cost and chiller cost remain constant as a function of the slope of the line between the two state points. In the dry condition, increasing the slope of the line causes the ratio of humidifier cost to chiller cost to increase, and vice versa VICE VERSA. On the contrary; on opposite sides. .

BINARY EW HUMIDIFICATION CONTROL

In this article, a simple binary (i.e., full-speed and OFF) EW control is proposed as a practical method for modulating the EW humidification performance. The dry condition (where humidification is required), as shown in Figure 3, is the region under the horizontal line (Descriptive Geometry & Drawing) a constructive line, either drawn or imagined, which passes through the point of sight, and is the chief line in the projection upon which all verticals are fixed, and upon which all vanishing points are found.

See also: Horizontal
 (SA DPT setpoint line) and consists of two regions (Regions III and IV) separated by the vertical line representing the SA DBT setpoint.

[FIGURE 3 OMITTED]

The basic idea is to control the EW either at "full-speed" or "OFF" in order to maintain the space RH higher than a prescribed lower limit (Figure 4) during the DOAS "dry region" operation. This control does not utilize an SA DPT setpoint; rather, it is the space or return air RH that is used to control humidification. To avoid short cycling of the EW near the RH setpoint, there should be a minimum ON-OFF time limit or deadband where the controller's output signal changes from "OFF" to "full speed" mode. Details of the EW control for each DOAS operating region are discussed in following sections.

[FIGURE 4 OMITTED]

Binary Control in Region III

Region III defines OA conditions that are below the DPT necessary to maintain acceptable space RH, and DBTs exceeding the SA DBT setpoint (55[degrees]F [12.8[degrees]C] in this example). For illustration purposes, Region III is divided into two regions, one bounded by OA DBTs between 55[degrees]F (12.8[degrees]C) and 75[degrees]F (23.9[degrees]C) and a second bounded by OA DBTs greater than or equal to 75[degrees]F (23.9[degrees]C) (the example space DBT).

The first region is illustrated in Figure 5a. The binary EW control in this region places the EW in the "ON" position when the space or return air RH is below setpoint, recovering both heat and moisture. The resulting EW leaving conditions exceed the desired SAT, so the air is sensibly cooled to the desired SAT setpoint. The use of the EW for humidification here increases the cooling energy use (if not from an economizer e·con·o·mize  
v. e·con·o·mized, e·con·o·miz·ing, e·con·o·miz·es

v.intr.
1. To practice economy, as by avoiding waste or reducing expenditures.

2.
 source) beyond that needed to simply sensible cool. Once the space or return air RH setpoint has been met, the binary control places the EW in the "OFF" mode. Sensible cooling is still required.

[FIGURE 5 OMITTED]

In the second region, illustrated in Figure 5b, the binary EW control behaves identically to that of Figure 5a. The difference is that operating the EW (in the "ON" mode) for humidification results in a decrease in the DBT of the air, thus reducing the sensible cooling performed by the cooling coil compared to times when the EW is in the OFF mode.

Note, when the EW operates in Region III, latent cooling at the cooling coil should be avoided. In other words Adv. 1. in other words - otherwise stated; "in other words, we are broke"
put differently
, the cooling coil chilled-water supply temperature setpoint should be high enough to avoid condensation formation on the cooling coil. Otherwise, the humidification accomplished with the EW will be nullified nul·li·fy  
tr.v. nul·li·fied, nul·li·fy·ing, nul·li·fies
1. To make null; invalidate.

2. To counteract the force or effectiveness of.
.

Binary Control in Region IV

In Region IV, the OA DBT is below freezing much of the time, so to avoid low-temperature incidences (freezing) at the cooling coil (if chilled water), a freeze-proof preheat coil is required to elevate the OA DBT to about 40[degrees]F (4.4[degrees]C). During periods when the space or return air RH meets or exceeds setpoint, and the EW is off, the OA temperature can be elevated to the SAT DBT setpoint with a sensible heat recovery device such as sensible wheel (SW), if it is included in the DOAS arrangement. If sensible heat recovery is not included in the arrangement, the preheat coil can be used to bring the OA up to the desired SAT.

The binary control logic for this region, as illustrated in Figure 6, places the EW in the "ON" mode whenever the space or return air RH is below setpoint. And if necessary, the air is sensibly cooled, either with a cooling coil or by a parallel sensible cooling system cooling system: see air conditioning; internal-combustion engine; refrigeration.
cooling system

Apparatus used to keep the temperature of a structure or device from exceeding limits imposed by needs of safety and efficiency.
 installed in the space. In either case, waterside free cooling should be considered. If the space or return air RH is above setpoint, the EW is placed in the "OFF" mode.

[FIGURE 6 OMITTED]

Auxiliary Humidification

There are at least two situations where the EW may not be able to provide sufficient moisture recovery to maintain the minimum space RH prescribed by Standard 55-2004. One is at low occupancy levels. The other is extremely low OA DPTs that would require the EW effectiveness to exceed its capability. In either of these cases, in order to operate within ASHRAE standards, auxiliary humidification will be required. It should be noted, however, that not all buildings have been constructed in sufficient compliance with Standard 90.1-2004 to take an indoor RH of 30% in the winter without condensation problems. Some owners may not wish to use extra energy for humidification.

The auxiliary humidifier, if used, would be best placed in the conditioned space. Placing it in the relatively cold DOAS supply ductwork duct·work  
n.
A group or system of ducts: installed new ductwork in the building. 
 could easily lead to problems with water in the ductwork.

BINARY ENTHALPY WHEEL TEMPERATURE CONTROL

Binary control of the EW can be used to accomplish SAT setpoint (e.g., 55[degrees]F [12.8[degrees]C]) without regard for humidification as well. In this case, the control only applies in Region IV. In order to meet a desired SAT, the EW must be duty cycled. The duty cycle concept involves adjusting the EW on-time within a cycle period to achieve the desired SAT. The on-time is a function of the return air temperature, the OA DBT, the desired SAT, and the EW sensible effectiveness. To limit the number of times the EW is energized per hour and, hence, the wear and tear on the drive, the period is often set at 15 minutes. As a result, the on-and off-times are frequently long enough for the EW SAT to nearly reach its steady-state "ON" or "OFF" value, which will always be above and below the desired SAT.

Consequently, control of the heating and cooling coils when in the duty cycle mode becomes an issue. Since the SAT will drop below the desired SAT when the wheel is off in the cycle, but heating is not desired, the heating coil control valve A device that modulates the flow of fluid in a conduit in response to a signal from a process measurement control system.  must be closed during duty cycling. Similarly, when the EW is on in the cycle, the SAT will rise above the desired SAT, but cooling is not desired, so the cooling coil control valve must be closed during duty cycling. Duty cycling can only operate down to a lower limit, a temperature just above that necessary to trip the low-limit temperature sensor. In order to avoid tripping the entire system off, with the resulting indoor environmental quality problems, the EW is not permitted to duty cycle below an OA DBT of 40[degrees]F (4.4[degrees]C). A freeze-proof preheat coil can make this provision. An example of the duty cycle trending as the OA temperature rises above 40[degrees]F (4.4[degrees]C) is illustrated in Figure 7.

[FIGURE 7 OMITTED]

A by-product by·prod·uct or by-prod·uct  
n.
1. Something produced in the making of something else.

2. A secondary result; a side effect.


by-product
Noun

1.
 of using binary SAT control in Region IV is that much of the time the EW is in the "ON" mode, and humidification is being accomplished. However it is the controlled variable.

CONCLUSION

A simple, proven, and generally applicable binary EW humidification control has been presented. The control overcomes the surprising issues discussed above that arise when modulating EW speed control is attempted during humidification. It was noted that use of an EW does not eliminate the potential need for an auxiliary humidifier. It has also been illustrated that it is less expensive to operate the chiller to achieve sensible cooling after the EW during dry OA conditions than to not use an EW and simply humidify the OA. In Regions III and IV, there is an energy penalty to humidify, but it is less when using the EW to humidify the OA than to have an auxiliary humidifier. Humidification is a worthy investment and operational expense for occupant health and productivity.

REFERENCES

ASHRAE. 2004a. ANSI/ASHRAE Standard 55-2004, Thermal Environmental Conditions for Human Occupancy. Atlanta: American Society of Heating, Refrigerating re·frig·er·ate  
tr.v. re·frig·er·at·ed, re·frig·er·at·ing, re·frig·er·ates
1. To cool or chill (a substance).

2. To preserve (food) by chilling.
 and Air-Conditioning Engineers, Inc.

ASHRAE. 2004b. ANSI/ASHRAE/IESNA Standard 90.1-2004, Energy Standard for Buildings Except Low-Rise Residential Buildings. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.

Mumma, S.A. 2001. Dedicated outdoor air-dual wheel system control requirements. ASHRAE Transactions 107(1):147-55.

Mumma, S.A., and J.W. Jeong. 2005. Field experience controlling a dedicated outdoor air system. ASHRAE Transactions 111(2):433-42.

Stiesch, G., S.A. Klein, and J.W. Mitchell. 1995. Performance of rotary heat and mass exchangers. HVAC&R Research 1(4):308-23.

Simonson, C.J., and R.W. Besant. 1999. Energy wheel effectiveness: Part II--Correlations. International Journal of Heat and Mass Transfer 42:2171-85.

Simonson, C.J., W. Shang, and R.W. Besant. 2000a. Partload performance of energy wheels: Part I--Wheel speed control. ASHRAE Transactions 106(1):286-300.

Simonson, C.J., W. Shang, and R.W. Besant. 2000b. Partload performance of energy wheels: Part II--Bypass control and correlations. ASHRAE Transactions 106(1):301-31.

Jae-Weon Jeong, PhD

Associate Member ASHRAE

Stanley A. Mumma, PhD, PE

Fellow ASHRAE

Jae-Weon Jeong is assistant professor in the Department of Civil and Architectural Engineering Architectural engineering

A discipline that deals with the technological aspects of buildings, including the properties and behavior of building materials and components, foundation design, structural analysis and design, environmental system analysis and
 of Texas A&M University, Kingsville, TX. Stanley A. Mumma is a professor emeritus in the Department of Architectural Engineering, Pennsylvania State University Pennsylvania State University, main campus at University Park, State College; land-grant and state supported; coeducational; chartered 1855, opened 1859 as Farmers' High School. , University Park, PA.
COPYRIGHT 2007 American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2007 Gale, Cengage Learning. All rights reserved.

 Reader Opinion

Title:

Comment:



 

Article Details
Printer friendly Cite/link Email Feedback
Author:Jeong, Jae-Weon; Mumma, Stanley A.
Publication:ASHRAE Transactions
Article Type:Report
Geographic Code:1USA
Date:Jul 1, 2007
Words:3178
Previous Article:An experimental study of falling film evaporation on inclined plates using R-141b and R-134a.(Technical report)
Next Article:Calibrated simulation for retrofit evaluation of demand-controlled ventilation in small commercial buildings.(Technical report)
Topics:



Related Articles
Something in the air. (ensuring a safe, healthy nursing home environment)
Reducing air-conditioning via desiccants. (desiccant technology decreases humidity levels) (Technology)
A cool time for tea.(News)(Finlay Beverages has installed air cooling units from Delta Neu )(Brief Article)
Occurrence of humid air diagrams within a short period at three distant places on a globe.
Exergy analysis of psychrometric processes for HVAC&R applications.(Heating, Ventilation, and Air-conditioning and Refrigeration)(Report)
Field testing of a supervisory optimal controller for an air-conditioning system.(Technical report)
Study on the energy conservation performance of the plate enthalpy exchanger.(Technical report)
Thermodynamic properties for saturated air, an engineering correlation.(Report)
The volatile organic compound (VOC) removal performance of desiccant-based dehumidification systems: testing at sub-ppm VOC concentrations.(Technical...

Terms of use | Copyright © 2009 Farlex, Inc. | Feedback | For webmasters | Submit articles